Chapter Five: Type R7xxC Relay System
Electrical Information
59
Electrical Information
Connector
Note
The “Reserved” pin assignment refers to a pin with an internal connection
which may be assigned a function in the future.
The relay module has a 15-pin Type “D” connector to interface to other devices. Connect the
power supply to this connector.
Type R700/R800 Connector Pinout
Pin Number
Assignment
1
Relay A Normally Open
2
Pressure Output
3
Reserved
4
Reserved
5
Power Return
6
-15 Volt
7
+15 Volt
8
Relay A Normally Closed
9
Relay B Normally Closed
10
Trip Point A Setting
11
Trip Point B Setting
12
Pressure Return
13
Relay B Normally Open
14
Relay B Common
15
Relay A Common
Table 22: Type R7xxC Connector Pinout
Electrical Requirements
The R7xxC unit requires ±15 Volts to power the relay module and the pressure transducer. To
power the unit, connect the +15 V source to pin 7, the -15 V source to pin 6, and the power
common to pin 5.