113
-
'10 • SCM-SM-094
Error code
Remote controller:
LED
Green
Red
Content
Indoor Keeps flashing Stays OFF
E58
Current safe stop
Outdoor
–
3
times flash
Error code
Remote controller: E58
LED
Green
Red
Indoor
Outdoor
―
Content
Current safe stop
(Model SRC40 - 60)
Keeps flashing Stays Off
3 time flash
1. Applicable model
5. Troubleshooting
All models
When the current safe control
has operated at the compressor
speed of 30 rps or under:
Same as above
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdor air temp.
sensor
• Defective outdoor main PCB
Diagnosis
Countermeasure
2. Error detection method
3.Condition of Error displayed
4. Presumable cause
Note:
NO
NO
NO
NO
NO
YES
YES
YES
Is outdoor
ventilation condition
good ?
Inspect
outdor air temp.
sensor
Is the refrigerant
amount nomal ?
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor main
PCB
¡
Replace.
(Defective outdor air temp.
sensor input circuit)
Inspect
compressor
Содержание SRR60ZJ-S
Страница 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Страница 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Страница 133: ...132 10 SCM SM 094...
Страница 134: ...133 10 SCM SM 094...
Страница 135: ...134 10 SCM SM 094...
Страница 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Страница 153: ...152 10 SCM SM 094...
Страница 154: ...153 10 SCM SM 094...
Страница 155: ...154 10 SCM SM 094...
Страница 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Страница 160: ...159 10 SCM SM 094 PJA012D783...