Error code
Remote controller:
LED
Green
Red
Content
Indoor
Stays OFF
Keeps flashing
E57
Insufficient refrigerant amount
or detection of service valve closure
Outdoor
–
2
times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
NO
YES
Is the
service valve fully
opened?
Are the
connections of indoor
heat exchanger and/or return air
temperature thermistor
connectors OK?
NO
YES
NO
YES
Are the
characteristics of indoor heat
exchanger and/or return air
temperature thermistor
OK?
Is the low
pressure during operation
normal?
Indoor heat exchanger, return air temperature thermistor
Temperature-resistance characteristics
15
10
5
0
10
30
40
20
50
Temperature thermistor resistance (k
)
Temperature (°C)
5k
at 25°C
(Broken wire)
(Shot circuit)
Open fully.
Correct indoor heat
exchanger, return air
temperature thermistor
connector connections.
Defective indoor heat
exchanger, return air
temperature thermistor
ª
Replace.
Charge refrigerant.
Defective indoor control
PCB
ª
Replace. (Defective
indoor heat exchanger,
return air temperature
thermistor input circuits)
2. Error detection method
• Judge insufficient refrigerant
amount by detecting the
temperature differnce between
indoor heat exchanger (ThI-R)
and indoor return air (ThI-A).
3. Condition of Error displayed
When the insufficient refrigerant
amount is detected 3 times
within 60 minutes.
4. Presumable cause
• Defective indoor heat
exchanger temperature
thermistor
• Defective indoor return air
temperature thermistor
• Defective indoor control PCB
• Insufficient refregerant
amount
Note: When the compressor speed is 50 rps or under at 5 minutes after the start of compressor or the completion of defrosting, the low refrigerant protection control
judges, by detecting the difference between the indoor heat exchanger temperature (Th
I
-R) and the indoor return air temperature (Th
I
-A), that it is in the state of
gas low, and stops the compressor.
Cooling: Indoor return air temperature (Th
I
-A) – Indoor heat exchanger temperature (Th
I
-R)
≧
4 deg
Heating: Indoor heat exchanger temperature (Th
I
-R) – Indoor return air temperature (Th
I
-A)
≦
6 deg
Содержание SRR60ZJ-S
Страница 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Страница 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Страница 133: ...132 10 SCM SM 094...
Страница 134: ...133 10 SCM SM 094...
Страница 135: ...134 10 SCM SM 094...
Страница 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Страница 153: ...152 10 SCM SM 094...
Страница 154: ...153 10 SCM SM 094...
Страница 155: ...154 10 SCM SM 094...
Страница 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Страница 160: ...159 10 SCM SM 094 PJA012D783...