84
-
'10 • SCM-SM-094
Error code
Remote controller:
LED
Green
Red
Indoor
Content
None
Power supply system error
(Power supply to remote controller)
Keeps flashing
Stays OFF
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Isn't there any
loose connection of remote
controller wires?
Isn't remote
controller wire broken or
short-circuited?
Is DC180V
between
-
of
CNW2?
Disconnect remote
controller wires.
NO
Is DC15V or
higher detected between X-Y
of indoor unit terminal
block?
YES
YES
YES
YES
NO
NO
NO
Correct.
Replace wires.
Replace remote controller.
Defective indoor power
PCB
ª
Replace.
Defective indoor control
PCB
ª
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Remote controller wire
breakage/short-circuit
• Defective remote controller
• Malfunction by noise
• Faulty indoor power PCB
• Broken harness
• Faulty indoor control PCB
Note:
Содержание SRR60ZJ-S
Страница 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Страница 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Страница 133: ...132 10 SCM SM 094...
Страница 134: ...133 10 SCM SM 094...
Страница 135: ...134 10 SCM SM 094...
Страница 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Страница 153: ...152 10 SCM SM 094...
Страница 154: ...153 10 SCM SM 094...
Страница 155: ...154 10 SCM SM 094...
Страница 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Страница 160: ...159 10 SCM SM 094 PJA012D783...