52
-
'10 • SCM-SM-094
'09•SRK-DB-087D
(7) Inspection procedures corresponding to detail of trouble
Sensor error
Sensor temperature characteristics (Room
temp., indoor heat exchanger temp., out-
door heat exchanger temp., outdoor air
temp,outdoor suction pipe temp.)
Temperature (˚C)
Resistance (k
)
30
25
20
15
10
5
30
20
10
40
50
60
70
0
-10
Discharge pipe sensor temperature characteristics
Indoor fan motor error
Broken sensor wire,
connector poor connection
0
0
20
40
60
80
100
120 135
20
40
60
80
100
120
140
160
180
Temperature (˚C)
Resistance (k
)
Defective fan motor, connector poor
connection, defective indoor PCB
57 for the fan motor and indoor PCB check pro-
Power supply reset
Is it normalized?
Malfunction by temporary noise
Replace fan motor. (If the
error persists after replacing
the fan motor, replace the
indoor PCB.)
'09•SRK-DB-087D
Current cut
Compressor lock, Compressor wiring short circuit, Compressor output is open phase,
Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
*
*
Current safe stop
Overload operation, compressor
lock, overcharge
Содержание SRR60ZJ-S
Страница 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Страница 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Страница 133: ...132 10 SCM SM 094...
Страница 134: ...133 10 SCM SM 094...
Страница 135: ...134 10 SCM SM 094...
Страница 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Страница 153: ...152 10 SCM SM 094...
Страница 154: ...153 10 SCM SM 094...
Страница 155: ...154 10 SCM SM 094...
Страница 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Страница 160: ...159 10 SCM SM 094 PJA012D783...