89
-
'10 • SCM-SM-094
Error code
Remote controller:
LED
Green
Red
Indoor
Stays OFF
Keeps flashing
Content
WAIT
Communication error at
initial operation (3/3)
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
When the remote controller
display is extinguished after the
power on.
Diagnosis
Countermeasure
YES
NO
Remote controller display is
extinguished after the power on.
YES
NO
NO
YES
NO
YES
Is the
green LED on the indoor unit
flashing?
Is the
fuse on the indoor control
PCB OK?
Is
approx. 10-11V detected
between wires at the remote controller
side after disconnecting the
remote controller?
Are wires
connected properly between the indoor and
the outdoor units?
Is approx.
DC20V detected between
-
on the outdoor unit terminal
block?
NO
YES
Is approx
DC20V detected between
-
on the indoor unit terminal
block?
YES
NO
NO
Replace fuse.
Short-circuit on remote
controller wire
Defective remote controller
Correct wires.
Defective outdoor sub
PCB
ª
Replace.
Defective connection wire
(Broken wire)
Noise
Defective indoor control
PCB
ª
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Blown fuse
• Connection between PCB’s
• Blown fuse
• Faulty indoor control PCB
• Defective remote controller
• Wire breakage on remote
controller
• Faulty outdoor sub PCB
Note:
Содержание SRR60ZJ-S
Страница 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Страница 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Страница 133: ...132 10 SCM SM 094...
Страница 134: ...133 10 SCM SM 094...
Страница 135: ...134 10 SCM SM 094...
Страница 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Страница 153: ...152 10 SCM SM 094...
Страница 154: ...153 10 SCM SM 094...
Страница 155: ...154 10 SCM SM 094...
Страница 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Страница 160: ...159 10 SCM SM 094 PJA012D783...