background image

-

 158 

-

 '10 • SCM-SM-094

PJA012D781

Installation of indoor unit (continued)

6. Make sure to install the indoor unit horizontally. Confirm the 

levelness of the indoor unit with a level gauge or transparent 

hose filled with water. Keep the height difference at both ends of 

the indoor unit within 3mm.

7. Tighten four upper nuts and fix the unit after height and levelness 

adjustment.

Caution

Do not adjust the height by adjusting upper nuts. It will cause unexpected stress on the indoor unit 

and it will lead to deformation of the unit, failure of attaching a panel, and generating noise from the 

fan.

Make sure to install the indoor unit horizontally and set the gap between the unit underside and 

the ceiling plane properly. Improper installation may cause air leakage, dew condensation, water 

leakage and noise.

Even after decorative panel attached, still the unit height can be adjusted finely. Refer to the 

installation manual for decorative panel for details.

Make sure there is no gap between decoration panel and ceiling surface, and between decoration 

panel and the indoor unit. The gap may cause air leakage, dew condensation and water leakage.

In case decorative panel is not installed at the same time, or ceiling material is installed after the 

unit installed, put the cardboard template for installation attached on the package (packing material 

of cardboard box) on the bottom of the unit in order to avoid dust coming into the indoor unit.

Refrigerant pipe

Caution

Use the new refrigerant pipe.

When re-using the existing pipe system for R22 or R407C, pay attention to the following items.

 

Change the flare nuts with the attached ones (JIS category 2), and reprocess the flare parts.

 

Do not use thin-walled pipes.

Use phosphorus deoxidized copper alloy seamless pipe (C1220T specified in JIS H3300) for 

refrigeration pipe installation.

 

In addition, make sure there is no damage both inside and outside of the pipe, and no harmful 

substances such as sulfur, oxide, dust or a contaminant stuck on the pipes. 

Do not use any refrigerant other than R410A.

Using other refrigerant except R410A (R22 etc.) may degrade inside refrigeration oil. And air getting 

into refrigeration circuit may cause over-pressure and resultant it may result in bursting, etc.

Store the copper pipes indoors and seal the both end of them until they are brazed in order to avoid 

any dust, dirt or water getting into pipe. Otherwise it will cause degradation of refrigeration oil and 

compressor breakdown, etc.

Use special tools for R410 refrigerant.

Work procedure 

1. Remove the flare nut and blind flanges on the pipe of the indoor unit.

Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving 

torque to the nut with another spanner in order to avoid unexpected stress to the copper pipe, 

and then remove them.

(Gas may come out at this time, but it is not abnormal.)

Pay attention whether the flare nut pops out. (as the indoor unit is sometimes pressured.)

2. Make a flare on liquid pipe and gas pipe, and connect the refrigeration pipes on the indoor unit.

Bend the pipe with as big radius as possible and do not bend the pipe repeatedly. In addition, do 

not twist and crush the pipes.

Do a flare connection as follows:

Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving 

torque to the nut with another spanner in order to avoid unexpected stress to the copper pipe, 

and then remove them.

When fastening the flare nut, align the refrigeration pipe with the center of flare nut, screw the 

nut for 3-4 times by hand and then tighten it by spanner with the specified torque mentioned 

in the table below. Make sure to hold the pipe on the indoor unit securely by a spanner when 

tightening the nut in order to avoid unexpected stress on the copper pipe.

3. Cover the flare connection part of the indoor unit with attached insulation material after a gas 

leakage inspection, and tighten both ends with attached straps.

Make sure to insulate both gas pipes and liquid pipes completely.

Incomplete insulation may cause dew condensation or water dropping. 

4. Refrigerant is charged in the outdoor unit.

As for the additional refrigerant charge for the indoor unit and piping, refer to the installation manual 

attached to the outdoor unit.

Pipe diameter

Tightening torque N·m

 6.35

14 to 18

 9.52

34 to 42

 12.7

49 to 61

 15.88

68 to 82

 19.05

100 to 120

Drain pipe (continued)

Work procedure

1. Make sure to insert the drain hose (the end mode of soft PVC) to the end of the step part of drain 

socket.

     Attach the hose clamp to the drain hose around 10mm from the end, and fasten the screw within 

5mm left to the nut.

Do not apply adhesives on this end.

 

Drain socket

The step part

Drain hose 

No adhesive allowed

 Drain socket

Metal plate

10mm

Hose clamp

Fasten the screw within 5 mm left to the nut.

Drain hose

2. Prepare a joint for connecting VP-20 pipe, adhere and connect the joint to the drain hose (the end 

made of rigid PVC), and adhere and connect VP-20 pipe (prepare on site).

As for drain pipe, apply VP-20 made of rigid PVC which is on the market.

Make sure that the adhesive will not get into the supplied drain hose.
It may cause the flexible part broken after the adhesive is dried up and gets rigid.

Do not bend or make an excess offset on the drain hose as shown in the picture.
Bend or excess offset will cause drain leakage.

Over 20mm

3. Make sure to make descending slope of greater than 1/100 and do not make up-down bend and/or 

trap in the midway.

Pay attention not to give stress on the pipe on the indoor unit side, and support and fix the pipe 
as close place to the unit as possible when connecting the drain pipe.

Do not set up air vent.

Supporting metal

No bump

No trap 

Not touching the water

Trapped air will 

generate noises.

Air vent

Insulation material

1.5m ~ 2m

Descending slope greater than 1/100

When sharing a drain pipe for more than one 
unit, lay the main pipe 100mm below the drain 
outlet of the unit. In addition, select VP-30 or 
bigger size for main drain pipe.

4. Insulate the drain pipe.

Be sure to insulate the drain socket and rigid PVC pipe installed indoors otherwise it may cause 
dew condensation and water leakage.

After drainage test implementation, cover the drain socket part with pipe cover (small size), 

then use the pipe cover (big size) to cover the pipe cover (small size), clamps and part of the 
drain hose, and fix and wrap it with tapes to wrap and make joint part gapless.

Drain up

The position for drain pipe outlet can be raised up to 600mm above the ceiling. Use elbows for 
installation to avoid obstacles inside ceiling. If the horizontal drain pipe is too long before vertical 
pipe, the backflow of water will increase when the unit is stopped, and it may cause overflow of 
water from the drain pan on the indoor unit. In order to avoid overflow, keep the horizontal pipe 
length and offset of the pipe within the limit shown in the figure below.

Drain hose

600mm or less

Joint for VP-20

(Prepare on site)

295 to 325mm

100 or less

Drain pipe (continued)

Drain test

After installation of drain pipe, make sure that drain system work in good condition and no water 
leakage from joint and drain pan. Check if the motor sound of drain pump is normal or not.

Do drain test even if installation of heating season.

For new building cases, make sure to complete the test before 
hanging the ceiling.

1. Pour water of about 1000cc into the drain pan in the indoor unit by 

pump so as not to get the electrical component wet.

2. Make sure that water is drained out properly and there is no water 

leakage from any joints of the drain pipe at the test.
Confirm that the water is properly drained out while the drain motor 
is operating. At the drain socket (transparent), it is possible to 
check if the water is drained out properly.

3. Unplug the drain plug on the indoor unit to remove remaining water 

on the drain pan after the test, and re-plug it. And insulate the drain 
pipe properly finally.

Drain pump operation 

In case electrical wiring work finished
Drain pump can be operated by remote controller (wired).
For the operation method, refer to  Operation for drain pump  in the installation manual for wiring 
work.

In case electrical wiring work not finished

 

Drain pump will run continuously when the dip switch“SW7-1” on the indoor unit PCB is turned ON, 
the Connector CNB is disconnected, and then the power supply (220-240VAC on the terminal block 
[

and

] or [ 

 and 

 ] ) is turned ON.

 

Make sure to turn OFF “SW7-1” and reconnect the Connector CNB after the test.

Attach the panel on the indoor unit after electrical wiring work.

Refer to attached manual for panel installation for details.

Drain pipe

Caution

Install the drain pipe according to the installation manual in order to drain properly.

 

Imperfection in draining may cause flood indoors and wetting the household goodsetc.

Do not put the drain pipe directly into the ditch where toxic gas such as sulfur, the other harmful and

 

inflammable gas is generated. Toxic gas would flow into the room and it would cause serious 

damage to user’s health and safety (some poisoning or deficiency of oxygen). In addition, it may 

cause corrosion of heat exchanger and bad smell.

Connect the pipe securely to avoid water leakage from the joint.

Insulate the pipe properly to avoid condensation drop.

Check if the water can flow out properly from both the drain outlet on the indoor unit and the end of 

the drain pipe after installation.

Make sure to make descending slope of greater than 1/100 and do not make up-down bend and/or 

trap in the midway. In addition, do not put air vent on the drain pipe. Check if water is drained 

out properly from the pipe during commissioning. Also, keep sufficient space for inspection and 

maintenance.

Wiring-out position and wiring connection

Electrical installation work must be performed according to the installation manual by an electrical 
installation service provider qualified by a power provider of the country, and be executed according 
to the technical standards and other regulations applicable to electrical installation in the country. 

 

Be sure to use an exclusive circuit.

Use specified cord, fasten the wiring to the terminal securely, and hold the cord securely in order 
not to apply unexpected stress on the terminal.

Do not put both power source line and signal line on the same route. It may cause 
miscommunication and malfunction.

Be sure to do D type earth work.

For the details of electrical wiring work, see attached instruction manual for electrical wiring work.

1. Remove a lid of the control box (1 screws).
2. Hold each wiring inside the unit and fasten them to terminal block securely.
3. Fix the wiring with clamp.
4. Install a lid of the control box back to original place.

Indoor unit

hose

Strap (Accessory)

Pipe cover (Accessory)

The thickness of insulation should be 20mm or more.

Pipe cover (small)

(For insulation)

(Accessory)

Unit

pipe cover (big)

(For insulation)

(Accessory)

Joint for VP-20

(Prepare on site)

Drain socket

Connect

VP-20

(Prepare on site)

Pipe cover (small)

(For insulation)

(Prepare on site)

Drain hose

(Accessory)

 Clamp

(Accessory

Descending stop greater than 1/100

As wide as possible

(about100mm)

VP-30 or bigger

Panel installation

After wiring work finished, install the panel on the indoor unit.

Refer to attached panel installation manual for details.

Accessory items

1

Hook

1 piece

For fixing temporarily

2

Chain

2 pieces

3

Bolt

4 pieces

For installing the panel

4

Screw

1 piece

For attaching a hook

5

Screw

2 pieces

For attaching a chain

Check list after installation

Check the following items after all installation work completed.

Check if

Expected trouble

Check

The indoor and outdoor units are fixed securely?

Falling, vibration, noise

Inspection for leakage is done?

Insufficient capacity

Insulation work is properly done?

Water leakage

Water is drained properly?

Water leakage

Supply voltage is same as mentioned in the model name plate? PCB burnt out, not working at all
There is mis-wiring or mis-connection of piping?

PCB burnt out, not working at all

Earth wiring is connected properly?

Electric shock

Cable size comply with specified size?

PCB burnt out, not working at all

Any obstacle blocks airflow on air inlet and outlet?

Insufficient capacity

Drain plug

Power source side terminal block

Earth

Wiring between indoor

and outdoor unit

Signal side terminal block

Remote controller line

Wiring clamp

Single split (PAC) series

VRF (KX) series

Power source side terminal block

Earth

Indoor power source line

Signal side terminal block

Signal line (shielded cord)

Remote controller line

Wiring clamp

Earth (signal line)

6

6

6

6

PJA012D786

See next page

Содержание SRR60ZJ-S

Страница 1: ...M45ZJ S SCM50ZJ S SCM60ZJ S SCM71ZJ S SCM80ZJ S INDOOR UNIT Wall mounted type SRK20ZJX S SRK25ZJX S SRK35ZJX S SRK50ZJX S SRK60ZJX S SRK20ZJ S SRK25ZJ S SRK35ZJ S SRK50ZJ S Floor standing type SRF25ZJ...

Страница 2: ...control function by remote controller 5 Flap and louver control 10 4 Custom cord switching procedure 9 3 Auto restart function 2 Unit ON OFF button 8 5 1 Remote controller Option parts 19 3 Operation...

Страница 3: ...2 7 Heating low outdoor temperature protective control 36 9 Crankcase heater 37 10 Inching prevention 8 Freezing cycle system protective control 36 36 1 Frost prevention control 33 2 Cooling overload...

Страница 4: ...series 63 5 1 Installation of outdoor unit 127 5 2 Installation of indoor unit 139 11 Outdoor unit inspection points 59 76 2 Troubleshooting 58 10 How to make sure of wireless remote controller 1 List...

Страница 5: ...FDTC Ceiling cassette 4 way compact type JX S Example Outdoor unit SCM 60 Z Series code Inverter type Product capacity Model name Outdoor unit J S Capacity Model Floor standing type SRF Outdoor unit t...

Страница 6: ...ER ECONOMY mode HI POWER ECONO button These buttons set the indoor temperature These buttons are used for setting the current time and timer function as well TEMPERATURE button This button selects ON...

Страница 7: ...be used for turning on off the unit when remote controller is not available Remote controller signal receiver RUN HOT KEEP light green blue Illuminates during operation green except ECONO operation bl...

Страница 8: ...ZJX S Unit display section AIR SELECTION button AIR OUTLET SELECTION light green Illuminates during upper air outlet operation TIMER light yellow Illuminates during TIMER operation This button can be...

Страница 9: ...en the remote controller batteries become weak or if the remote controller is lost or malfunctioning this button may be used to turn the unit on and off a Operation Push the button once to place the u...

Страница 10: ...sabled See the diagram at right ModelSRK20 60ZJX S Model SRK20 50ZJ S SRF25 50ZJX S SRR25 60ZJ S Jumper wire J170 Jumper wire JA1 4 Custom cord switching procedure If two wireless remote controller ar...

Страница 11: ...75 Swing Flap stopped Approx 45 Approx 60 Approx 60 Angle of Flap from Horizontal Mode SRK20 60ZJX S COOL DRY FAN Remote controller display HEAT Approx 10 Approx 25 Approx 25 Approx 40 Approx 40 Appro...

Страница 12: ...ries Control the flap by AIRFLOW UP DOWN button on the wireless remote controller a Flap Each time when you press the AIRFLOW UP DOWN button the mode changes as follows b Swing 1 Swing flap Flap moves...

Страница 13: ...the start or until indoor temperature is close to reaching the setting point And then the air outlet will change to both outlets in order to spread comfort air to every corner 2 HEAT operation a In c...

Страница 14: ...lowing Fixed Operation mode Indoor temp Setting temp 2 C Setting temp Indoor temp 2 C At heating At cooling Air flow direction contorol 2 C Setting temp Indoor temp 5 C 2 C Indoor temp Setting temp 5...

Страница 15: ...installation location while the installation location setting display illuminates Airflow range Airflow range Airflow range Left End Installation Center Installation Right End Installation Center Ins...

Страница 16: ...stop 2 Inciuding the Fan operation according to the mismatch of operation modes 1 Control A a If the float switch detects any anomalous draining condition the unit stops with the anomalous stop and t...

Страница 17: ...alid Operation is displayed but it does not mean a failure Cover AIR CON No button Display the indoor unit number connected to this remote controller CHECK button This button is used at servicing TEST...

Страница 18: ...when this is pressed once again it stops operating Used to swing the louver Every time this button is pressed displays switch as below Sets room temperature by pressing or button Sets time when settin...

Страница 19: ...Operation mode Airflow volume mode Room temperature setting Louver auto swing stop However the stop position 4 position is cancelled so that it returns to Position 1 Remote controller function items w...

Страница 20: ...Outdoor unit fan Indoor unit fan Louver motor Drain pump 3 2 2 Thermostat ON Thermostat OFF 2 2 Note 1 Operation Stop Turned ON OFF by the control other than the room temperature control 2 ON during...

Страница 21: ...er ON This is not displayed under the Remote mode 2 If this display is not shown under the Center Remote mode check if the indoor unit power switch is turned on or not f Hot start Cold draft preventio...

Страница 22: ...ensor is effective i Filter sign As the operation time Total ON time of ON OFF switch accumulates to 180 hours 1 FILTER CLEANING is displayed on the remote controller This is displayed when the unit i...

Страница 23: ...change of operation mode If the thermostat is turned OFF during the forced operation control of heating compressor the louver position with the auto swing is returned to the level position Note 1 The...

Страница 24: ...oling operation SRC40 60 FDC100 140 Model Symbol A 4 4 1 1 1 0 1 0 2 5 2 5 B C D 2 Selection of indoor fan speed If it enters the frost prevention control during cooling operation excluding dehumidify...

Страница 25: ...ing procedure Signal wiring between indoor and outdoor units should be made on each unit same as the normal wiring For the group control lay connect with sires wiring between rooms using terminal bloc...

Страница 26: ...l and start stop operation of the unit from the wired remote controller becomes not available 2 In case that Operation permission prohibition mode setting is Valid and External input setting is Pulse...

Страница 27: ...T 6 input Unit A Unit B Note The latest operation has priority It is available to operate stop by remote controller or center controller b In case of Pulse input setting Local setting It is effective...

Страница 28: ...sampling present number of revolutions of indoor unit fan speed is reduced by 10min 1 3 End conditions Indoor fan speed is reduced to the setting airflow volume when the compressor OFF is established...

Страница 29: ...S 1 5 7 6 kW SCM71ZJ S 1 5 9 1 kW SCM80ZJ S 1 5 9 5 kW 3 Hot keep operation If the hot keep operation is selected during the heating operation the indoor fan is controlled based on the temperature of...

Страница 30: ...n 20 20 15 10 5 0 5 10 15 10 5 0 Outdoor air temperature Outdoor heat exchanger temperature Defrost operation start Defrost operation start temperature b h 2 2 h 20 3 Max 12 minutes and 50 seconds Hea...

Страница 31: ...nit fan Compressor Outdoor unit fan Electronic expansion valve ON According to command speed According to outdoor unit speed According to decision speed 0 All indoor units OFF According to stop mode A...

Страница 32: ...SRK SRR series b 1 2 3 c d 27 5 25 5 18 0 18 30 2 SRK 20 50ZJ S series a Determination of operation mode Heating Dehumidifying Cooling Indoor air temperature C Outdoor air temperature C Signals of wir...

Страница 33: ...an start and stop the operation When the jumper wire J3 is released Permission Prohibition mode When Cnt input is set to ON the operation mode is changed to permission and if input is set to OFF the o...

Страница 34: ...ol s indoor unit settings Input signal to CnT becomes valid at OFF ON only and the motion of air conditioner ON OFF is inverted CnT Input Unit CASE A Unit CASE B OFF OFF ON ON OFF ON OFF ON ON OFF OFF...

Страница 35: ...speed is set to B or D rps and even if the speed becomes lower than B or D rps the speed is kept to B or D rps However when the thermo becomes OFF the speed is reduced to 0 rps The upper limit of com...

Страница 36: ...ly 2 Contents of control Compressor stop 3 Release condition When the indoor heat exchanger temperature Th2 has become lower than the release tempera ture b Outdoor unit side 1 Start condition When th...

Страница 37: ...tdoor air temperature Th2 is 10 C or lower after the compressor stops 8 Freezing cycle system protective control a Starting condition This control starts when the following conditions are met 1 When i...

Страница 38: ...when it exceeds the control value 1 Switching with jumper wire Jumper wire J2 Short circuit At shipping from factory Short circuit Jumper wire J1 Short circuit At shipping from factory Current safe C...

Страница 39: ...20 rps 60 rps SCM60ZJ S 20 rps 60 rps SCM80ZJ S 20 rps 60 rps SCM71ZJ S a The fan operates as follows according to the compressor command speed Except during defrost Cooling Heating Compressor speed r...

Страница 40: ...ut 85 or less Outdoor fan speed 6th speed 5th speed More than 31 but 66 or less 4th speed 3rd speed Less than 31 More than 46 66 or more but 66 or less 6th speed 5th speed More than 31 but 46 or less...

Страница 41: ...ondition When the outdoor air temperature Th2 has risen higher than 13 C for 30 seconds continuously while the compressor is operating b Contents of control The outdoor unit fan tap is brought down by...

Страница 42: ...H I 8 7 5 4 405 1 7 55 7 056 8 05 5 50 1 0 7 7 4 5 7 55 7 1 7 4 H 1 8 50 J1 1 G07 G 4G 5H 3 Troubleshooting procedure If the air conditioner does not run at all 8 0 7 5 0 0 5 1 5 5 44 0 65 1 8 34 1056...

Страница 43: ...42 10 SCM SM 094 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 43 44 50 44 50...

Страница 44: ...pole positions cannot be correctly detected when the compressor starts The air conditioner stops Defective compressor Open phase on compressor Defective outdoor PCB Service valve is closed Refrigeran...

Страница 45: ...indoor unit Data are recorded for up to 5 previous occurrences Data which are older than the 5th previous occurrence are erased In addition data on the temperature of each sensor room temperature indo...

Страница 46: ...6 865 4 6 45 A 11 1 8 B F65 4 5 1 14 1 5 5 1 14 1 4 6 11 1 8 D45 865 4 8 6 45 F65 4 5 6 8 1 4 Q 4 1 5 5 1 14 1 4 6 11 1 8 D45 865 4 8 6 45 F65 4 5 1 1 1 6 2 1 4 6 4 6 11 1 8 D45 865 4 8 6 45 F65 4 5...

Страница 47: ...n for the stop stop code 2 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 3 times previous when the air conditioner was stopp...

Страница 48: ...ght 1 s digit Stop coad or Error coad Error content Cause Occurrence conditions Error display Auto recovery OFF 3 time flash 5 time flash 6 time flash 8 time flash 4 time flash 2 times 2 times 3 times...

Страница 49: ...Display pattern when in service mode Operation switching when there is an abnormal stop 0 1 2 4 3 AUTO DRY COOL FAN HEAT C N5 6 678 8 A TIMER light Fan speed switching Display pattern when in service...

Страница 50: ...34 44 54 64 74 84 94 55 45 35 25 15 5 5 15 25 35 45 55 65 75 85 95 56 46 36 26 16 6 6 16 26 36 46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28 38 48 58 68 78 8...

Страница 51: ...0 10 30 50 70 90 110 130 150 52 32 12 12 32 52 72 92 112 132 54 34 14 14 34 54 74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 78 98 118 138 No does not sound 0 12 3 456 7 1284 9 7 2 2...

Страница 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...

Страница 53: ...10 40 50 60 70 0 10 Discharge pipe sensor temperature characteristics Indoor fan motor error Broken sensor wire connector poor connection 0 0 20 40 60 80 100 120 135 20 40 60 80 100 120 140 160 180 T...

Страница 54: ...Current cut Compressor lock Compressor wiring short circuit Compressor output is open phase Outdoor PCB is faulty Service valve is closed EEV is faulty Compressor faulty Current safe stop Overload ope...

Страница 55: ...094 09 SRK DB 087D Over heat of compressor Gas shortage defective discharge pipe sensor Error of signal transmission Wiring error including power cable defective indoor outdoor PCB 52 main indoor indo...

Страница 56: ...tor error Defective fan motor connector poor connection defective outdoor PCB Power supply reset Is it normalized Malfunction by temporary noise Replace fan motor If the error persists after replacing...

Страница 57: ...r unit Defective compressor defective outdoor PCB Sensor Operation mode Phenomenon Shortcircuit Disconnected wire Room temperature sensor Cooling Heating Heat exchanger sensor Cooling Heating Humidity...

Страница 58: ...15 A YES YES YES NO NO NO b Indoor unit fan motor check procedure 1 Indoor PCB output check 2 Fan motor resistance check FMI DC15V Indoor PCB DC 308 336V DC several V 4 6 V CNU GND Blue Yellow White...

Страница 59: ...m burns wiring mistakes etc If no problems are found check the output of the power transistor 2 Output inspection procedure Disconnect the terminals for the compresseor If an output such as the one sh...

Страница 60: ...of resistance value of sensor Remove the connector and check the resistance value See the section of sensor characteristics on page 52 Power source and serial signal inspection to AC 220 230 240V to N...

Страница 61: ...inspection to AC 220 230 240V to Normal if the voltage oscillates between DC 0 and approx 20V UNIT A UNIT B UNIT C Power supply 1 Phase 220 240V 50Hz Inspection of electronic expansion valve See page...

Страница 62: ...rmal if the voltage oscillates between DC 0 and approx 20V UNIT A UNIT B UNIT C UNIT D Power supply 1 Phase 220 240V 50Hz Inspection of electronic expansion valve See page 62 Color Marks Mark Color BK...

Страница 63: ...ansion valve as a separate unit Measuring point Resistance when normal b Outdoor unit fan motor check procedure 2 Fan motor resistance check Measuring point Resistance when normal Measuring point Resi...

Страница 64: ...hanger tempera ture thermistor Defective indoor heat exchanger temperature thermistor defective element broken wire short circuit Poor contact of temperature thermistor connector Replacement repair of...

Страница 65: ...air of temperature sensor 104 Outdoor main PCB Defective outdoor main PCB Defective temperature sensor input circuit Replacement of PCB Stays OFF Keeps flashing 1 time flash Outdoor main PCB compresso...

Страница 66: ...with one remote controller Whenever excessively connected indoor units is detected after power ON Return air temperature thermistor anomaly 50 C or lower is detected for 5 seconds continuously within...

Страница 67: ...ger remote controller switch and fuse Note 1 With regard to parts of high voltage circuits and refrigeration cycle judge it according to ordinary inspection methods b Instruction of how to replace ind...

Страница 68: ...CB Parts mounting are different by the kind of PCB ON OFF Part number SW2 Blue Address setting SW5 Master Slave setting SW7 Function setting CNT Blue External switch CNJ White Louver motor CNN Yellow...

Страница 69: ...ing connector color should match with the color of connector of the PCB Note 2 6 Let the wiring red and blue pass beneath the yellow green wiring and bind together with band 7 Screw back the terminal...

Страница 70: ...l mode Valid Reserved keep OFF Test run Drain motor Normal Test run Valid Invalid Normal Model selection As per model See table 1 Remarks Address No setting at plural indoor units control by 1 R C 0 F...

Страница 71: ...press the button which allows you to go back to the indoor unit selection screen Pressing the button will stop displaying data Pressing the RESET button during remote control unit operation will undo...

Страница 72: ...ctively b Operation for judgment 1 Power ON and start check operation on cooling or heating mode 2 Check ON OFF status of 6 LED s on the checker 3 Judge the PCB by ON OFF status of 6 LED s on the chec...

Страница 73: ...nspection to AC 220 230 240V to Normal if the voltage oscillates between DC 0 and approx 20V Color Marks Mark Color BK BR Black Brown RD Y G Red Yellow Green WH White OR Orange EEV S BK WH RD V W U FM...

Страница 74: ...voltage oscillates between DC 0 and approx 20V UNIT A UNIT B UNIT C Power supply 1 Phase 220 240V 50Hz EEV S BK WH RD V W U FMo CM R CNTH CNFAN S 2 BK WH WH S 1 CNSUB CNMAIN SIN RIN BK WH SO RO 250V...

Страница 75: ...d approx 20V UNIT A UNIT B UNIT C UNIT D Power supply 1 Phase 220 240V 50Hz Color Marks Mark Color BK BR Black BL Blue BR Brown Brown RD Y G Red Yellow Green WH White OR Orange YE Yellow EEV S BK WH R...

Страница 76: ...rature thermistor anomaly 92 16 E7 Return air temperature thermistor anomaly 93 17 E8 Heating overload operation 94 18 E9 Drain trouble 95 19 E10 Excessive number of connected indoor units more than 1...

Страница 77: ...mpressor or other respective parts NO YES YES NO YES YES YES NO NO Is the compressor operating NO YES NO Note 1 Outdoor 35 C Indoor 27 C 1 WAIT It is normal This unit is designed to start in the soft...

Страница 78: ...s phenomenon NO YES YES NO YES YES YES NO NO Is the compressor operating NO YES NO Note 1 Outdoor 7 C Indoor 20 C 1 WAIT It is normal This unit is designed to start in the soft start mode by detecting...

Страница 79: ...power supply the insulation resistance may drop to a few M because of refrigerant migrated in the compressor When the earth breaker is activated at lower insulation resistance check the following poin...

Страница 80: ...nto the gap if necessary Prevent the vibration from transmitting to wall and etc by fixing pipes on the wall or wrapping rubber cushion around the pipe which goes through the hole in the wall or apply...

Страница 81: ...side of piping of air conditioner It is likely to occur particularly during cooling or defrosting in the heating mode It is normal The noise vibration occurs when the refrigerant starts or stops flowi...

Страница 82: ...n of air nitrogen etc In such occasion it is necessary to recover refrigerant vacuum dry and recharge refrigerant Since there could be many causes of noise vibration the above do not cover all In such...

Страница 83: ...locked Check at the indoor unit side LM louver motor Is the louver operable with the remote controller YES NO Does the louver operate at the power on YES NO YES NO Operate after waiting for more than...

Страница 84: ...LM etc OK NO NO 1 Note 1 for GND Is DC5V detected between of CNW2 NO Is AC220 240V for 1 phase unit detected between 1 and 2 on the terminal block of outdoor unit YES YES YES YES Is JX1 open Defective...

Страница 85: ...broken or short circuited Is DC180V between of CNW2 Disconnect remote controller wires NO Is DC15V or higher detected between X Y of indoor unit terminal block YES YES YES YES NO NO NO Correct Replace...

Страница 86: ...he connecting wire between the indoor and outdoor unit Power supply reset NO YES YES NO NO NO NO NO YES YES YES Set one remote controller for Master and the other for Slave Set SW1 on remote controlle...

Страница 87: ...on with remote controller 3 Condition of Error displayed Same as above 4 Presumable cause Improper setting Surrounding environment Defective remote controller communication circuit Faulty indoor cont...

Страница 88: ...t terminal block YES NO Is approx DC20V detected between on the indoor unit terminal block NO YES WAIT See next page Defective outdoor sub PCB Replace Defective indoor control PCB Replace Replace indo...

Страница 89: ...eplacing the power supply fuse Diagnosis Countermeasure Replace the outdoor sub PCB YES YES NO YES Replace the outdoor main PCB NO Replace the reactor NO Isn t there a short circuit between phases of...

Страница 90: ...emote controller side after disconnecting the remote controller Are wires connected properly between the indoor and the outdoor units Is approx DC20V detected between on the outdoor unit terminal bloc...

Страница 91: ...en after 3 minutes Power reset NO WAIT Malfunction by noise Check peripheral environment Defective indoor control PCB Replace Defective remote controller Replace 2 Error detection method When normal c...

Страница 92: ...ection looseness on the outdoor unit terminal block Power reset Note 2 Check for faulty connection or breakage of signal wires between indoor outdoor units YES NO YES NO Repair signal wires Repair sig...

Страница 93: ...indoor heat exchanger temperature thermistor Replace Defective indoor control PCB Replace Defective indoor unit heat exchanger temperature thermistor input circuit 2 Error detection method Anomalousl...

Страница 94: ...rect Connect connector Defective return air temperature thermistor Replace Defective indoor control PCB Replace Defective return air temperature thermistor input circuit 2 Error detection method Anoma...

Страница 95: ...Note 2 For characteristics of indoor heat exchanger temperature thermistor see the error display E6 YES NO YES NO Error stop Reset Indoor heat exchanger temperature C 56 63 Wash Defective indoor heat...

Страница 96: ...Is the drain pipe slop OK NO YES NO Defective indoor control PCB Replace Defective indoor control PCB Replace Check optional equipment Correct setting to Humidifier DM interlock Defective indoor power...

Страница 97: ...del 5 Troubleshooting All models Diagnosis Countermeasure Aren t more than 17 indoor units connected to one remote controller NO YES Defective remote controller Replace Reduce to 16 or less units 2 Er...

Страница 98: ...otor Check power voltage Replace faulty fan motor and power PCB Replace fan motor If the error persists after replacing the fan motor replace the indoor control PCB Malfunction by temporary noise 2 Er...

Страница 99: ...oor control PCB ON E19 occurs when the power ON NO YES Defective indoor control PCB Defective SW7 Replace Turn SW7 1 on the indoor control PCB OFF and reset the power 2 Error detection method After in...

Страница 100: ...er 3 minutes delay the compressor starts again automatically but if this error occurs again within 60 minutes after the initial detection 4 Presumable cause Faulty connection of remote controller temp...

Страница 101: ...unit side Isn t the air circulation of outdoor unit short circuited Are installation spaces adequate Isn t there any fouling or clogging on heater exchanger Control operation check Defective outdoor...

Страница 102: ...39 YES NO NO Replace discharge pipe temperature sensor Insufficient refrigerant amount Recharge refrigerant by weighing proper amount on a scale Control operation check Defective outdoor main PCB Repl...

Страница 103: ...uit Correct connector Defective outdoor heat exchanger temperature sensor Replace Defective outdoor main PCB Replace Defective outdoor heat exchanger temperature sensor input circuit 2 Error detection...

Страница 104: ...rect connector Defective outdoor air temperature sensor Replace Defective outdoor main PCB Replace Defective outdoor air temperature sensor input circuit 2 Error detection method Detection of anomalou...

Страница 105: ...perature C Broken wire Shot circuit Correct connector Defective discharge pipe temperature sensor Replace Defective outdoor main PCB Replace Defective temperature sensor input circuit 2 Error detectio...

Страница 106: ...NO NO NO Check power supply Open the valves Check refrigerant amount and refregerant circuit In case of transitional increase of high pressure and or test run several times restarting may recover it b...

Страница 107: ...the filter clogged At heating does the indoor fan motor run Are the service valves fully opened Is the filter clogged Is there any liquid flooding Is the superheat within normal range Is the low press...

Страница 108: ...en the main PCB and the outdoor sub PCB connected properly Is normal state restored YES NO NO NO Correct connector Check why power is not supplied to outdoor sub PCB Connect communication wire securel...

Страница 109: ...for foreign matter like dust fouling etc YES Is voltage within the specified range NO Restore normal condition Restore normal condition Remove foreign matter like dust fouling etc Defective outdoor su...

Страница 110: ...n by temporary noise 2 Error detection method Detected by rotation speed of outdoor fan motor 3 Condition of Error displayed When actual rotation speed of outdoor fan motor drops to 75min 1 or lower f...

Страница 111: ...is Countermeasure 2 Error detection method 3 Condition of Error displayed 4 Presumable cause Note If the power transistor primary current exceeds the setting value for 3 seconds the compressor stops P...

Страница 112: ...rect connector Defective suction pipe temperature sensor Replace Defective outdoor sub PCB Replace Defective suction pipe temperature sensor input circuit 2 Error detection method Detection of anomalo...

Страница 113: ...place Charge refrigerant Defective indoor control PCB Replace Defective indoor heat exchanger return air temperature thermistor input circuits 2 Error detection method Judge insufficient refrigerant a...

Страница 114: ...or under Same as above Excessive refrigerant amount Indoor outdoor unit installation spaces Faulty compressor Defective outdor air temp sensor Defective outdoor main PCB Diagnosis Countermeasure 2 Err...

Страница 115: ...Defective outdoor main PCB Replace Repalce compressor 2 Error detection method If it fails to change over to the rotor detection operation of compressor motor 3 Condition of Error displayed If compres...

Страница 116: ...ompressor rotor position 3 Condition of Error displayed If it fails again to detect the rotor position after shifting to the compressor rotor position detection operation the compressor stops 4 Presum...

Страница 117: ...lash Over heat of compressor 6Time flash Error of signal transmission 7Time flash Lock of compressor 8Time flash Sensor error Except discharge pipe sensor Four sec light and Discharge pipe sensor erro...

Страница 118: ...sensor Outdoor air temp sensor Discharge pipe temp sensor CM Th1 Connector 20S 4 Way valve coil Suction pipe temp sensor Th4 FMo Fan motor Terminal block TB1 TB2 outdoor unit HEATER Crank case heater...

Страница 119: ...is produced in the control box don t touch electrical parts in the control box for 5 minutes after cutting power supply CNA CN20S EEV A EEV B EEV C EEV D R Compressor motor Electric expansion valve c...

Страница 120: ...5 IM RD WH RD WH BK BL Y Y G BK t Th2 1 Th2 2 Th3 LM1 LM2 SM1 SM2 FMI DS t t TO OUTDOOR UNIT HEAT EXCHANGER 1 2 N 3 POWER WIRES SIGNAL WIRE 1 2 N 3 Power source 1 phase 220 240 V 50Hz T Color Marks B...

Страница 121: ...UNIT BK WH RD Y G HEAT EXCHANGER 2 N 3 Y G HD ONLY t o 2 t o R AMP 2 HEAT EXCHANGER 5 FMI SMI LM1 LM2 F Va ThI Th2 Th3 T DS Blue Black BK Red BL RD White WH Yellow Green Y G Color Mark Heat exch sens...

Страница 122: ...l block T Damper motor DM1 SM1 2 1 2 Damper arm motor Description Item Varistor Va DM2 250V F G 3 15A S N Va CNU CNS INTERFACE KIT SC BIKN E CNG CNE DISPLAY WIRELESS RECEIVER J CNF U M HEAT 1 3 4 5 6...

Страница 123: ...G 1 2 N 3 WH BK Y G RD S N J RD BK WH BOX CONTROL U 8 2 2 2 RD CNW M F 250V 0 16A RD OR 5 1 WH WH BK 2 BK 10 BK L CNS FM DM Th1 Th2 Th3 t TO OUTDOOR UNIT POWER WIRES SIGNAL WIRE 1 2 N 3 Power source...

Страница 124: ...6 7 8 9 BK BK BK BK 10 BK 11 BK 12 BK 13 BK 14 BK 15 BK 16 BK 17 BK BK 18 BK 19 BK 20 BK 1 2 3 4 5 BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 I FS LM1...

Страница 125: ...or Th1 Heat exchanger Heat exchanger Liquid line Gas line 6 35 6 35 9 52 9 52 Strainer Compressor 4 way valve Service valve Liquid Capillary tube Capillary tube Electric expansion valve EEVA EEVB Cool...

Страница 126: ...Sensor Th2 Accumlator Sensor Th4 Service valve Liquid Electronic expansion valve Compressor 4way valve Discharge Suction Sensor Th1 Heat exchanger Cooling cycle Heating cycle 9 52 or 12 7 9 52 or 12...

Страница 127: ...sor EEVA EEVD EEVC EEVB Strainer Discharge Suction Sensor Th3 Receiver Sensor Th4 Service valve Liquid Electronic expansion valve Compressor Oil separator 4way valve Sensor Heat exchanger Th2 Sensor T...

Страница 128: ...water Be sure to switch off the power supply in the event of installation inspection or servicing If the power supply is not shut off there is a risk of electric shocks unit failure or personal injur...

Страница 129: ...ned specifically for R410A Gauge for projection adjustment Used when flare is made by using conventional flare tool 9 10 11 12 13 14 15 16 Plus headed driver Knife Saw Tape measure Hammer Spanner wren...

Страница 130: ...REFRIGERANT PIPINGS 3 Copper pipe diameter Clutch typr flare tool for R410A Conventional R22 flare tool Clutch type Wing nut type Measurement B mm 6 35 0 0 0 5 1 0 1 5 1 5 2 0 9 52 0 0 0 5 1 0 1 5 1 5...

Страница 131: ...n and before turning on the power Conduct a test run again and ensure that the unit operates properly At the same time explain to the customer how to use the unit and how to take care of the unit foll...

Страница 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...

Страница 133: ...132 10 SCM SM 094...

Страница 134: ...133 10 SCM SM 094...

Страница 135: ...134 10 SCM SM 094...

Страница 136: ...g operation valves before compressor stopping air can be sucked which can cause burst or personal injury due to anomalously high pressure in the refrigerant circuit Only use prescribed optional parts...

Страница 137: ...ng and miscellaneous small parts Indoor unit installation manual Necessary tools for the installation work Wrench key Hexagon 4m m Vacuum pump Vacuum pump adapter Anti reverse flow type Designed speci...

Страница 138: ...rom the aring block will vary depending on the type of a are tool in use If a conventional are tool is used please use a copper pipe gauge or a similar instrument to check protrusion so that you can k...

Страница 139: ...failures therefore it shall never be done City water pipe Town gas pipe TV antenna lightning conductor telephoneline etc Check the following points again after completion of the installation and befor...

Страница 140: ...ange the wiring in the control box so that it cannot be pushed up further into the box Install the service panel correctly Incorrect installation may result in overheating and fire Be sure to switch o...

Страница 141: ...he flare nut by torque wrench with specified method If the flare nut were tightened with excess torque this may cause burst and refrigerant leakage after a long period The electrical installation must...

Страница 142: ...for heat insulation Position it so that the slit area faces upward 9 5 A J 1G G J 1G G J 1G G 2 A H 9 5 A C 1 A 9 A C B 9 2 C 5 9 A A 2 3 8 A B A A B A A A 3 3 3 A 3 0 A A A 9 C A 5 A 2 1 2 4 0 0 002...

Страница 143: ...t insulation Position it so that the slit area faces upward 9 5 A J 1G G J 1G G J 1G G 9 A C A A A A A B A C C C A A 9 0 5 A C A A C 5 C 21 2 9 2 A H 9 5 A C 1 A 9 A C B 9 2 C 5 9 A A 2 3 8 A B A A B...

Страница 144: ...r any powder is floating Locations where any substances that can affect the unit such as sulphide gas chloride gas acid and alkaline can occur Vehicles and ships Locations where cosmetic or special sp...

Страница 145: ...outlet air of the unit Locations where vibration can be amplified due to insufficient strength of structure Locations where the infrared receiver is exposed to the direct sunlight or the strong light...

Страница 146: ...protrusion from the flaring block will vary depending on the type of a flare tool in use If a conventional flare tool is used please use a copper pipe gauge or a similar instrument to check protrusion...

Страница 147: ...nventional flare tool Please note that measurement B protrusion from the flaring block will vary depending on the type of a flare tool in use If a conventional flare tool is used please use a copper p...

Страница 148: ...n the event of installation inspection or servicing If the power supply is not shut off there is a risk of electric shocks unit failure or personal injury due to the unexpected start of fan CAUTION Us...

Страница 149: ...ower before starting electrical work Failure to shut off the power can cause electric shocks unit failure or incorrect function of equipment Be sure to use the cables conformed to safety standard and...

Страница 150: ...3 4 0 6 2 3 3 1 5 1 1 1 1 3 1 3 1 4 3 3 3 43 1 4 3 6 3 0 0 2 1 1 5 1 3 4 3 D 6 3 04 0 6 A 3 1 2 3 2 15 0 13 43 1 4 3 G K4 2 A 2 3 K4 5 5 6 3 7 61 8 C 2 2 4 8 0 3 2 5 5 A 118 43 0 1 3 1 3 0 1 341 2 6 0...

Страница 151: ...1 0 0 2 5 24 3 2 6 1 7 A 3 6 1 B 13 6 1 43 1 3 0 1 1 3 0 0 1 2 2 1 6 A 0 A 5 1 3 73 1 1 0 13 6 3 43 1 3 0 2 0 3 0 0 2 3 6 3 3 3 412 3 1 43 3 3 3 0 0 3 3 2 7 3 6 1 0 0 2 3 3 6 6 3 02 33 1 5 3 1 3 1 A...

Страница 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...

Страница 153: ...152 10 SCM SM 094...

Страница 154: ...153 10 SCM SM 094...

Страница 155: ...154 10 SCM SM 094...

Страница 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...

Страница 157: ...e installation If suspension bolt becomes longer do reinforcement of earthquake resistant For grid ceiling When suspension bolt length is over 500mm or the gap between the ceiling and roof is over 700...

Страница 158: ...thin 5mm left to the nut Do not apply adhesives on this end Drain socket The step part Drain hose No adhesive allowed Drain socket Metal plate 10mm Hose clamp Fasten the screw within 5 mm left to the...

Страница 159: ...provider of the country and be executed according to the technical standards and other regulations applicable to electrical installation in the country Be sure to use an exclusive circuit Use specifi...

Страница 160: ...159 10 SCM SM 094 PJA012D783...

Страница 161: ...M 094 Note This function is not able to be set with wireless remote controller or simple remote control RCH H3 For setting the swing range of other louvers return to 1 and proceed same procedure respe...

Страница 162: ...ng Refrigeration Systems Headquarters 16 5 2 chome Kounan Minato ku Tokyo 108 8215 Japan Fax 03 6716 5926 Copyright MITSUBISHI HEAVY INDUSTRIES LTD Because of our policy of continuous improvement we r...

Отзывы: