M800S/M80 Series Connection and Setup Manual
4 General Specifications
20
IB-1501269-F
(Note 1) "Short term" means roughly within one month.
(Note 2) This value includes the maximum value of DO external load current (3.2A).
(Note 3) This value does not include DO external load current.
(Note 4) For the heating value of the I/O circuit, calculate with the number of points used.
(Note 5) For the whole NC system, consider the characteristics of the drive units when the altitude is more than 1000
meters above sea level. Refer to the manual of drive unit for details.
4.1.2 24VDC Stabilized Power Supply Selecting Conditions
Consider the following characteristics for the stabilized power supply, and select the power supply that complies with
laws, regulations, or safety standards of the country where the machine will be installed.
Item
Unit name
Remote I/O unit
Type
FCU8-DX220/
DX230/
DX231
FCU8-DX202
FCU8-DX213/
DX213-1/
DX654/
DX654-1
FCU8-DX408
FCU8-DX651
General
Specifications
Ambient
temperature
During
operation
0 to 58°C
During
storage
-20 to 60°C
Ambient
humidity
Long term
10 to 75% RH (with no dew condensation)
Short term
10 to 95% RH
(with no dew condensation)
(Note 1)
10 to 85% RH
(with no dew condensation)
(Note 1)
Vibration resistance
4.9m/s
2
or less
Shock resistance
29.4m/s
2
or less
Working atmosphere
No corrosive gases, dust or oil mist
Altitude
Operation/Storage: 1000 meters or less above sea level,
Transportation: 13000 meters or less above sea level
Power supply voltage
24VDC
Current consumption
3.5A (Note 2)
0.3A
0.3A (Note 3)
0.1A
3.7A (Note 2)
Heating value (max)
8W (Note 4)
Mass
(kg)
0.4
0.2
0.8
Outline
dimension
W×H×D
(mm)
40×175×133 40×175×119 40×175×130 40×175×109
172×100×115
Item
Specifications
Remarks
Output
Voltage
24VDC
When the stabilized power supply and 24VDC input unit are distant, select
the stabilized power supply which is possible to set output voltage 24VDC or
more allowing for the influence of voltage down by the cable.
Voltage fluctuation
±5%
Current
-
Calculate the current value as a reference of maximum current consumption
for the unit which uses the power supply.
Ripple noise
0.2V (P-P)
Output holding time
min 20ms
Output holding time is decided by loading ratio; however, the stabilized power
supply which complies with the specification on the left must be selected
during maximum loading.
Overcurrent output
shutoff function
-
Use a power supply having the overcurrent output shutoff function.
CAUTION
1. Using a stabilized power supply without overcurrent protection may cause the unit's failure due to miswiring of
24V.
Содержание M80 series
Страница 1: ......
Страница 4: ......
Страница 9: ......
Страница 21: ......
Страница 23: ......
Страница 25: ......
Страница 27: ......
Страница 29: ......
Страница 37: ......
Страница 38: ...1 IB 1501269 F 1 System Basic Configuration...
Страница 40: ...3 IB 1501269 F 2 General Connection Diagram...
Страница 44: ...7 IB 1501269 F 3 List of Configuration...
Страница 53: ...M800S M80 Series Connection and Setup Manual 3 List of Configuration 16 IB 1501269 F...
Страница 54: ...17 IB 1501269 F 4 General Specifications...
Страница 185: ...M800S M80 Series Connection and Setup Manual 4 General Specifications 148 IB 1501269 F...
Страница 186: ...149 IB 1501269 F 5 Installation...
Страница 211: ...M800S M80 Series Connection and Setup Manual 5 Installation 174 IB 1501269 F...
Страница 212: ...175 IB 1501269 F 6 Precautions for Connecting...
Страница 219: ...M800S M80 Series Connection and Setup Manual 6 Precautions for Connecting 182 IB 1501269 F...
Страница 220: ...183 IB 1501269 F 7 Connection of Control Unit...
Страница 245: ...M800S M80 Series Connection and Setup Manual 7 Connection of Control Unit 208 IB 1501269 F...
Страница 246: ...209 IB 1501269 F 8 Connection of Keyboard Unit...
Страница 248: ...211 IB 1501269 F 9 Connection of Operation Panel I O Unit...
Страница 262: ...225 IB 1501269 F 10 Connection of Remote I O Unit...
Страница 289: ...M800S M80 Series Connection and Setup Manual 10 Connection of Remote I O Unit 252 IB 1501269 F...
Страница 290: ...253 IB 1501269 F 11 Connection of Manual Pulse Generator...
Страница 294: ...257 IB 1501269 F 12 Connection of Synchronous Feed Encoder...
Страница 296: ...259 IB 1501269 F 13 Connection of MITSUBISHI CNC Machine Operation Panel...
Страница 307: ...M800S M80 Series Connection and Setup Manual 13 Connection of MITSUBISHI CNC Machine Operation Panel 270 IB 1501269 F...
Страница 308: ...271 IB 1501269 F 14 Connection of Handy Terminal...
Страница 310: ...273 IB 1501269 F 15 Cable...
Страница 349: ...M800S M80 Series Connection and Setup Manual 15 Cable 312 IB 1501269 F...
Страница 350: ...313 IB 1501269 F 16 Setup Outline...
Страница 354: ...317 IB 1501269 F 17 Setting the Hardware...
Страница 383: ...M800S M80 Series Connection and Setup Manual 17 Setting the Hardware 346 IB 1501269 F...
Страница 384: ...347 IB 1501269 F 18 Setting Up with M80 M800S SETUP INSTALLER...
Страница 392: ...355 IB 1501269 F 19 Setting the Parameters and Date Time...
Страница 398: ...361 IB 1501269 F 20 PLC Program Writing...
Страница 410: ...373 IB 1501269 F 21 Confirming the Basic Operation...
Страница 415: ...M800S M80 Series Connection and Setup Manual 21 Confirming the Basic Operation 378 IB 1501269 F...
Страница 416: ...379 IB 1501269 F 22 Setting the Position Detection System...
Страница 439: ...M800S M80 Series Connection and Setup Manual 22 Setting the Position Detection System 402 IB 1501269 F...
Страница 440: ...403 IB 1501269 F 23 Setting the Tool Entry Prohibited Range...
Страница 453: ...M800S M80 Series Connection and Setup Manual 23 Setting the Tool Entry Prohibited Range 416 IB 1501269 F...
Страница 454: ...417 IB 1501269 F 24 Confirming the Spindle Operation...
Страница 457: ...M800S M80 Series Connection and Setup Manual 24 Confirming the Spindle Operation 420 IB 1501269 F...
Страница 458: ...421 IB 1501269 F 25 Setting the Handy Terminal...
Страница 464: ...427 IB 1501269 F 26 Setting the Deceleration Check...
Страница 474: ...437 IB 1501269 F 27 Adjust S analog Screen...
Страница 479: ...M800S M80 Series Connection and Setup Manual 27 Adjust S analog Screen 442 IB 1501269 F...
Страница 480: ...443 IB 1501269 F 28 Device Open Parameter Screen...
Страница 486: ...449 IB 1501269 F 29 SRAM Open Parameter Screen...
Страница 492: ...455 IB 1501269 F 30 Data Backup and Restoration...
Страница 498: ...461 IB 1501269 F 31 Appx 1 Setting the System Lock...
Страница 502: ...465 IB 1501269 F 32 Appx 2 Protection Setting...
Страница 510: ...473 IB 1501269 F 33 Appx 3 Displaying Original Logo On Standard Screen...
Страница 512: ...475 IB 1501269 F 34 Appx 4 EMC Installation Guidelines...
Страница 523: ...M800S M80 Series Connection and Setup Manual 34 Appx 4 EMC Installation Guidelines 486 IB 1501269 F...
Страница 524: ...487 IB 1501269 F 35 Appx 5 Restrictions for Lithium Batteries...
Страница 531: ...M800S M80 Series Connection and Setup Manual 35 Appx 5 Restrictions for Lithium Batteries 494 IB 1501269 F...
Страница 532: ...495 IB 1501269 F 36 Appx 6 Precautions for Compliance to UL c UL Standards...
Страница 538: ......
Страница 542: ......