—58—

8

When the main power
supply is turned on, the
remote controller display
will indicate and Lossnay
will start.

«

When using PZ-60DR-E, “RECOVERY SET-
TING” is set to “on” or “AUTo” with the function
selection of the remote controller. 

«

When not using PZ-60DR-E, the function
selection switch (SW2-6 or SW5-4) on the
Lossnay circuit board is set to ON.

«

When using PZ-41SLB-E, the main power sup-
ply was turned off during operation.

«

Check the power supply
ON/OFF/AUTO setting with the
PZ-60DR-E function selection.
(Refer to page 41)

«

Check the function selection
switch (SW2-6 or SW5-4). (Refer
to page 38)

«

When using PZ-41SLB-E, the
operation prior to switching off the
power will return when the main
power supply is turned on. Switch
off the main power supply approx-
imately 10 seconds after Lossnay
stop with the remote controller.

7

No.

The ventilation mode
cannot be switched with
the remote controller.

«

The bypass ventilation switching external input
(CN16) is set to ON.

«

Check the bypass ventilation
switching input (CN16).
(Refer to page 35)

9

There is no power failure
automatic return.

«

When using PZ-60DR-E, “RECOVERY SET-
TING” is set to “oFF” with the function selection
of the remote controller.

«

When not using PZ-60DR-E, the function
selection switch (SW5-4) on the Lossnay cir-
cuit board is set to ON.

«

Check the power supply ON/OFF/AUTO
setting with the PZ-60DR-E function
selection. (Refer to page 41)

«

Check the function selection
switch (SW5-4) on the Lossnay
circuit board. (Refer to page 38)

12

When PZ-60DR-E is
used, Lossnay does not
operate in accordance
with the timer setting.

«

When a different timer has been set with each
remote controller in a two remote controller
system, the resultant operation will not be in
accordance with the setting.

«

Perform the timer setting with
one remote controller only, and
use the other remote controller
as “( 

Timer off indicator)”.

Error

Cause

Action

10

The fan does not stop
even though the remote
controller is set to stop.

«

Operation monitor with delay function is set to
ON. (Function selection switch SW2-8 or SW5-
6 is set to ON)

«

Check the function selection
switch (SW2-8 or SW5-6).
(Refer to page 38)

Note: When two remote controllers are used, the combination of the PZ-60DR-E and PZ-41SLB-E cannot be used. 

13

“CLEANING” “FILTER” /
“CLEANING” “CORE” (PZ-
60DR-E), or “FILTER” (PZ-
41SLB-E) continues to
blink and the display can-
not be reset.

«

The display is reset incorrectly.

«

The remote controller has broken down.

«

During Lossnay operation, press
the “FILTER” button two times
(within 3 seconds).

«

Replace the remote controller.

11

When using PZ-60DR-E,
Lossnay starts or stops
operating, or the fan
speed changes, by itself.

«

Timer function has been set with PZ-60DR-E. 

«

“NIGHT PURGE” is set to “on” with PZ-60DR-E.

«

Check the timer function setting
with PZ-60DR-E.

«

Check the night purge setting of
PZ-60DR-E. If enabled, this is
not an error. (Refer to page 41)

Checklist for PZ-52SF-E (Table 3-2)

1

No.

Nothing displays on the
LCD.

«

Transmission cable is connected to the wrong
terminal block.

«

There is no power supply unit (for Lossnay only systems).

«

The power supply unit is not turned on.

«

Transmission cable is not securely connected.

«

Wiring length of the transmission cable from the
power supply unit or the outdoor unit is longer
than specified (maximum extension 200 m).

«

Check the transmission cable
connection (TB5 

A

B

for M-

NET transmission cables).

«

Install the power supply unit.

«

Check the power to the power supply unit.

«

Check the transmission cable connection.

«

Check the length of the trans-
mission cable wiring. (See the
technical manual for details
about the regulations.)

Error

Cause

Action

Содержание LGH-100RX5-E

Страница 1: ...HANDBOOK Model LGH 15RX5 E LGH 25RX5 E LGH 35RX5 E LGH 50RX5 E LGH 65RX5 E LGH 80RX5 E LGH 100RX5 E Nameplate LGH 150RX5 E LGH 200RX5 E Nameplate Model PZ 60DR E Model PZ 25RF8 E PZ 35RF8 E PZ 50RF8...

Страница 2: ...5 Basic circuit diagram 21 6 Fundamentals of operation 22 44 7 Troubleshooting 45 65 8 Disassembly and assembly 66 68 9 Parts catalog 69 123 LGH 15RX5 E 70 75 LGH 25RX5 E 76 81 LGH 35RX5 E 82 87 LGH 5...

Страница 3: ...struction Electric shock If you must inspect the circuitry while the power is on do not touch the live parts Failure to heed this warning may result in elec tric shock Caution for electric shock Modif...

Страница 4: ...4 2 Specifications...

Страница 5: ...5...

Страница 6: ...6...

Страница 7: ...7...

Страница 8: ...8...

Страница 9: ...Unit mm LGH 15RX5 E 3 Outside dimensions 9...

Страница 10: ...Unit mm LGH 25RX5 E 10...

Страница 11: ...Unit mm LGH 35RX5 E 11...

Страница 12: ...12 Unit mm LGH 50RX5 E...

Страница 13: ...Unit mm LGH 65RX5 E 13...

Страница 14: ...14 Unit mm LGH 80RX5 E...

Страница 15: ...Unit mm LGH 100RX5 E 15...

Страница 16: ...16 Unit mm LGH 150RX5 E...

Страница 17: ...Unit mm LGH 200RX5 E 17...

Страница 18: ...18 Unit mm PZ 60DR E Unit mm PZ 25RF8 E PZ 35RF8 E PZ 50RF8 E PZ 65RF8 E PZ 80RF8 E PZ 100RF8 E...

Страница 19: ...trical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obtaining...

Страница 20: ...al electrical regulations Always use double insulated PVC cable for the transmission cables Wiring work must be performed by qualified professionals All supply circuits must be disconnected before obt...

Страница 21: ...ventilation When SW5 6 is ON During operation and when the outdoor air temperature is 5 C to 15 C 0 While stopped or when the outdoor air temperature is 15 C TM3 6 7 Thermistor RA OA CN5 LED 2 Red Wh...

Страница 22: ...e controller PZ 60DR E or PZ 41SLB E One remote controller oper ates one Lossnay unit Two remote controllers oper ate one Lossnay unit Last touch priority operation PZ 60DR E and PZ 41SLB E cannot be...

Страница 23: ...rom an air conditioner remote con troller Having PZ 60DR E or PZ 52SF E last touch priority operation is permitted with the air conditioner remote controller and the Lossnay remote controller 1 PZ 41S...

Страница 24: ...troller MA remote controller PAR 20 21MAA Wireless remote controller PAR FA FL 31MA Compact remote controller PAC YT51CRA Compact remote controller PAC SE51CRA ME remote controller PAR F27MEA PAR 21MA...

Страница 25: ...lection is not available from the K control remote controller Extra Low fan speed selection is not available from the A control and K control remote controllers System interlocked with Mr Slim None Fi...

Страница 26: ...ance is adjusted to suit the usage environment or the place of installation Multi venti lation mode Power supply exhaust when operation starts ON Refer to page 41 During the first 30 minutes of operat...

Страница 27: ...Ventilation mode control Lossnay heat exchange ventilation or bypass normal ventilation is achieved by switching the air duct inside the Lossnay unit with a damper 1 Ventilation mode There are 3 contr...

Страница 28: ...em interlocked with City Multi indoor units Up to two of the Lossnay remote controllers PZ 60DR E PZ 41SLB E and PZ 52SF E can be used in the same group but they cannot be used together with a differe...

Страница 29: ...ture map Ventilation mode switching of Lossnay ventilation Bypass ventilation in the automatic ventilation mode is in accordance with the following map a Systems interlocked with Mr Slim and City Mult...

Страница 30: ...tained Lossnay ventilation area Bypass ventilation area Undetermined area Bypass Ventilation Bypass Ventilation Undetermined area b When there is no interlocking with Mr Slim and City Multi indoor uni...

Страница 31: ...te controller or ME remote con troller and the ventilation setting The City Multi indoor unit operation mode target tempera ture and other internal information can also be brought in Systems interlock...

Страница 32: ...he pulse signal is input Stopping is by remote controller ON interlock Lossnay will start with the start signal of the external device Stopping is by remote controller Interlock mode setting on SW5 7...

Страница 33: ...s a common terminal with bypass operation monitor operation monitor with delay function 2 output 7 2 Terminal 7 of TM3 is a common terminal with malfunction monitor output 7 3 The operation monitor ca...

Страница 34: ...rd and input the signal uncharged a contact from a CO2 sensor to the brown and red lines When the contacts in the diagram below are ON closed the system will switch to High Extra High fan speed regard...

Страница 35: ...s within the same group When not using PZ 60DR E input bypass ventilation switching into each Lossnay unit The setting is applied only to the Lossnay units that have received input Operation Multiple...

Страница 36: ...accumulated heat and there by reduce the air conditioning load the next morning If Night purge is enabled per the Installation Manual 5 Function Selection 5 8 night purge operation will be performed...

Страница 37: ...satisfied Night Purge mode is active no operation 1 00 A M Outdoor temperature 17 C 28 C or more within 24 hours Temperature monitoring operation 5 minutes Night Purge operation Bypass ventilation 55...

Страница 38: ...lter cleaning dis play ON 3 000 hours OFF No filter maintenance display Factory setting 5 TM3 6 7 output setting ON Operation monitor output with delay functions 2 Refer to 3 2 Fan speed control by fu...

Страница 39: ...in In systems with multiple Lossnay units be sure that one unit is set to Main and that all the others are set to Sub When interlocked with an external device be sure to connect the external device to...

Страница 40: ...tion lock Factory setting no2 All button lock oFF Stops operation by pressing the ON OFF button during operation Factory setting on Extra Low fan speed operation by pressing the ON OFF button during o...

Страница 41: ...H L Fixed at Low fan speed Multiple ventilation mode L Do not execute power supply exhaust when operation starts Factory setting oFF Execute power supply exhaust when opera tion starts 30 minutes on I...

Страница 42: ...the ventilation mode will not be possible during night purge operation Bypass ventilation fixed 11 Refer to 4 5 Automatic ventilation algorithm temperature map 12 External input priority will not be p...

Страница 43: ...witch condition of the Main Lossnay Example 001 will be displayed when the address is number 01 Lossnay address switch condition Self diagnosis Error history Error history clear Returns all of the rem...

Страница 44: ...truction by Lossnay remote controller or external device Extra Low fan speed operation when using PZ 60DR E other than the LGH 150 and 200 types High Extra High fan speed Low fan speed High Extra High...

Страница 45: ...eshooting 4 Check the checklist for the remote controllers Table 3 1 to 3 2 Check the Lossnay checklist Table 4 Yes No No This is normal No No Yes Yes Yes 45 7 Troubleshooting I Work precautions When...

Страница 46: ...41SLB E TM4 1 2 M NET control TAB5 A B 7 Is the wiring length of the transmission cable within the regulations Basic system PZ 60DR E PZ 41SLB E Total extension within 500 m M NET control Maximum ext...

Страница 47: ...ith level signal pulse signal output devices and Mr Slim units 8 Do the external signals meet specifications Level signal Charged 12 V DC 24 V DC uncharged a contact Pulse signal Charged 12 V DC 24 V...

Страница 48: ...r supply fan operation monitor mal function monitor bypass operation monitor and operation monitor with delay function 8 When using the operation monitor is the setting of the output signal cor rect W...

Страница 49: ...gth of the trans mission cable wiring Using suitable cables wire the transmission cables so that they are separated from one another Use the same type of remote controller 3 Interlock operation with e...

Страница 50: ...an address corresponding to interlock operation Check the length of the trans mission cable wiring See the technical manual for details about the regulations Change to the PZ 60DR E or PZ 52SF E remo...

Страница 51: ...2SF E goes blank and the system does not start The restricted number of connected PZ 52SF E units have been exceeded The length of the transmission cable wiring is longer than specified longer than ma...

Страница 52: ...ot been performed by PZ 52SF E Lossnay address setting SA1 SA2 is wrong Lossnay address setting SA1 SA2 was changed The transmission cable power supply restric tions have been exceeded Group setting h...

Страница 53: ...wer supply cable Check the transmission cable connection Check the length of the transmission cable wiring Error Cause Action RC6608 SRC 6608 Communica tion error between remote con trollers when two...

Страница 54: ...nger than specified longer than 500 m Turn off the main power and set the Main Sub selection switch SW1 Set the first unit to Main and the second and following units to Sub Using suitable cables wire...

Страница 55: ...e external devices When external devices are not con nected check the TM3 6 7 output setting switch SW5 6 Refer to page 38 3602 3 blinks Damper related error Damper board operation is not cor rect Con...

Страница 56: ...o Sub Using suitable cables wire the transmission cables so that they are separated from one another Wire the transmission cable at least 5 cm away from the power supply cable Check the transmission c...

Страница 57: ...cal switching CN32 is set to Remote Check the setting of the MELANS Check the interlock mode set ting Refer to page 32 Check the remote local switching CN32 Refer to page 35 6 Cannot switch fan speed...

Страница 58: ...n will not be in accordance with the setting Perform the timer setting with one remote controller only and use the other remote controller as Timer off indicator Error Cause Action 10 The fan does not...

Страница 59: ...E or MELANS Power is not supplied to Lossnay Power that does not follow specifications is used Transmission cable to the Lossnay is not con nected Transmission cable is connected to the wrong terminal...

Страница 60: ...device Uncharged a contact Longer than 500 m Mr Slim signal Longer than 500 m The Delay operation is set with the function selection of PZ 60DR E or PZ 41SLB E or the function selection switch SW5 1 o...

Страница 61: ...ing for air conditioner defrost ing with the PZ 60DR E function selection or the function selec tion switch SW5 3 Refer to page 38 and 42 7 Fan speed will not change High Low Extra Low fan speed switc...

Страница 62: ...ion monitor out put setting with the PZ 60DR E function selection or the function selection switch SW5 2 on the Lossnay circuit board Refer to page 38 and 41 11 Night purge operation does not work eve...

Страница 63: ...mal dis play of PZ 60DR E or when returning to the normal display from the function selection mode or the maintenance mode Button operations may not be accepted immediately depending on commu nication...

Страница 64: ...following circum stances The night purge conditions have not been satisfied Lossnay has been started or stopped during the display of Night purge Night purge operation will not be performed when CENT...

Страница 65: ...3 1 20 32 8 5 16 5 10 8 8 25 5 0 40 3 0 19 31 2 4 15 7 11 8 5 26 4 8 41 2 8 18 29 8 3 15 1 12 8 1 27 4 7 42 2 7 17 28 4 2 14 5 13 7 8 28 4 5 43 2 7 16 27 1 1 13 8 14 7 6 29 4 3 44 2 6 15 25 8 0 13 3 1...

Страница 66: ...ns according to the instructions described in the troubleshooting When servicing always keep proper footing When servicing make sure that the power cord is pulled out of the outlet or the power supply...

Страница 67: ...Unscrew the fixing screws two special screws 4 x 22 5 indicated by 67 4 Slide the connector covers with the connector toward the Lossnay core side and then take them off from the unit 5 Remove the co...

Страница 68: ...di cated by for the motor fix plate SA side Remove the EA side motor in the same way Separator Instructions When reassembling the unit assemble it in the reverse order of disassembly Always make sure...

Страница 69: ...screw PTT screw PT screw SET screw SQ SET screw P SET screw PMT screw HS SET screw P R W screw P C W screw P R C W screw R W screw PW PP screw SW PW PP screw Description Cross recess flat head machin...

Страница 70: ...50 541 380 4 6 Cover R50 541 717 2 7 Flange Y50 115 619 4 8 PTT screw 4 8 H00 000 487 46 9 Maint cover R50 541 487 1 10 Filter X50 039 717 4 11 Lossnay core R50 541 718 2 With filter stoppers 12 Core...

Страница 71: ...71 LGH 15RX5 E 8 8 8 8 8 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 4 7 8 8 10 5 1 2 2 5 7 7 2 shows accessory parts...

Страница 72: ...te R50 214 708 4 27 PTT screw 4 10 H00 000 332 13 28 Motor fix plate R50 541 712 2 29 Cord clamper D43 008 223 2 30 Motor Y50 115 453 1 31 PTT screw 4 6 H00 312 007 16 32 Cord bush M45 649 226 2 33 Co...

Страница 73: ...73 21 22 23 24 25 26 27 28 29 30 31 34 33 32 35 27 32 31 26 27 27 26 29 28 26 24 23 22 21 31 31 27 36 36 31 LGH 15RX5 E...

Страница 74: ...440VAC 55 PPT screw 3 8 H00 003 005 1 56 Circuit board Y50 115 171 1 LG X3 E 57 Lock washer 4 H00 013 076 2 58 Transformer Y50 115 216 1 AC230V 59 PT screw 4 8 BS H00 011 008 1 60 Cord band M45 017 2...

Страница 75: ...75 42 48 43 41 50 51 49 52 53 54 55 56 57 58 59 60 61 62 63 68 69 70 71 72 64 65 66 67 44 46 45 47 70 54 64 57 31 45 8 8 8 8 8 8 8 8 8 8 8 8 8 shows accessory parts LGH 15RX5 E...

Страница 76: ...50 541 380 4 6 Cover R50 541 717 2 7 Flange Y50 075 609 4 8 PTT screw 4 8 H00 000 487 46 9 Maint cover R50 541 487 1 10 Filter X50 039 717 4 11 Lossnay core R50 541 718 2 With filter stoppers 12 Core...

Страница 77: ...77 8 8 8 8 8 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 4 7 8 8 10 5 1 2 2 5 7 7 2 LGH 25RX5 E shows accessory parts...

Страница 78: ...te R50 214 708 4 27 PTT screw 4 10 H00 000 332 13 28 Motor fix plate R50 541 712 2 29 Cord clamper D43 008 223 2 30 Motor Y50 115 455 1 31 PTT screw 4 6 H00 312 007 14 32 Cord bush M45 649 226 2 33 Co...

Страница 79: ...79 21 22 23 24 25 26 27 28 29 30 31 34 33 32 35 27 32 31 26 27 27 26 29 28 26 24 23 22 21 31 31 27 36 36 31 LGH 25RX5 E...

Страница 80: ...440VAC 55 PPT screw 3 8 H00 003 005 1 56 Circuit board Y50 115 171 1 LG X3 E 57 Lock washer 4 H00 013 076 2 58 Transformer Y50 115 216 1 AC230V 59 PT screw 4 8 BS H00 011 008 1 60 Cord band M45 017 2...

Страница 81: ...81 42 48 43 41 50 51 49 52 53 54 55 56 57 58 59 60 61 62 63 68 69 70 71 72 64 65 66 67 44 46 45 47 70 54 64 57 31 45 8 8 8 8 8 8 8 8 8 8 8 8 8 LGH 25RX5 E shows accessory parts...

Страница 82: ...50 541 380 4 6 Cover R50 541 717 2 7 Flange Y50 075 609 4 8 PTT screw 4 8 H00 000 487 48 9 Maint cover R50 542 486 1 10 Filter Y50 116 717 4 11 Lossnay core R50 542 710 2 With filter stoppers 12 Core...

Страница 83: ...83 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 7 8 10 5 1 2 2 5 7 7 8 4 2 8 8 8 8 8 LGH 35RX5 E shows accessory parts...

Страница 84: ...ate Y50 116 712 2 28 PTT screw 5 10 H00 189 007 8 29 Cord clamper D43 008 223 2 30 Cord bush M45 649 226 4 31 Connector cover Y50 115 709 2 32 PTT screw 4 6 H00 312 007 15 33 Connector plate Y50 115 7...

Страница 85: ...85 21 22 23 24 25 26 27 28 29 29 27 26 24 23 22 21 36 37 25 34 31 32 30 33 30 31 30 32 8 8 30 33 28 38 35 36 37 38 35 LGH 35RX5 E...

Страница 86: ...k washer 4 H00 013 076 2 53 Transformer Y50 115 216 1 AC230V 54 PT screw 4 8 BS H00 011 008 1 55 TB fix plate Y50 115 712 1 56 Cord band K83 170 228 2 White 57 PCB fix plate R50 546 705 1 58 Bush R50...

Страница 87: ...87 42 41 44 43 46 47 45 48 49 50 51 57 56 58 65 62 64 63 67 66 8 8 8 8 8 8 8 66 62 8 8 8 8 34 8 32 52 53 54 59 60 61 55 59 52 8 LGH 35RX5 E shows accessory parts...

Страница 88: ...50 541 380 4 6 Cover R50 542 706 2 7 Flange R50 429 609 4 8 PTT screw 4 8 H00 000 487 48 9 Maint cover R50 542 486 1 10 Filter R50 521 717 4 11 Lossnay core R50 542 711 2 With filter stoppers 12 Core...

Страница 89: ...89 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 7 8 10 5 1 2 2 5 7 7 8 4 2 8 8 8 8 8 LGH 50RX5 E shows accessory parts...

Страница 90: ...ate Y50 116 712 2 28 PTT screw 5 10 H00 189 007 8 29 Cord clamper D43 008 223 2 30 Cord bush M45 649 226 4 31 Connector cover Y50 115 709 2 32 PTT screw 4 6 H00 312 007 15 33 Connector plate Y50 115 7...

Страница 91: ...91 21 22 23 24 25 26 27 28 29 29 27 26 24 23 22 21 36 37 25 34 31 32 30 33 30 31 30 32 8 8 30 33 28 38 35 36 37 38 35 LGH 50RX5 E...

Страница 92: ...k washer 4 H00 013 076 2 53 Transformer Y50 115 216 1 AC230V 54 PT screw 4 8 BS H00 011 008 1 55 TB fix plate Y50 115 712 1 56 Cord band K83 170 228 2 White 57 PCB fix plate R50 546 705 1 58 Bush R50...

Страница 93: ...93 42 41 44 43 46 47 45 48 49 50 51 57 56 58 65 62 64 63 67 66 8 8 8 8 8 8 8 66 62 8 8 8 8 34 8 32 52 53 54 59 60 61 55 59 52 8 LGH 50RX5 E shows accessory parts...

Страница 94: ...50 543 380 4 6 Cover R50 542 706 2 7 Flange R50 429 609 4 8 PTT screw 4 8 H00 000 487 55 9 Maint cover R50 543 486 1 10 Filter R50 524 717 4 11 Lossnay core R50 543 710 2 With filter stoppers 12 Core...

Страница 95: ...95 8 8 8 8 8 2 1 13 12 14 11 10 9 3 4 5 6 7 8 5 7 7 7 8 10 13 5 1 2 2 2 5 8 4 LGH 65RX5 E shows accessory parts...

Страница 96: ...sher 6 M34 043 080 8 28 Key Y50 033 104 2 5 5 11 5 29 Motor Y50 117 453 2 30 Motor fix plate R50 543 712 2 31 PTT screw 5 10 H00 189 007 16 32 Nut 6 H00 061 050 8 33 Cord bush M45 649 226 4 34 Connect...

Страница 97: ...97 31 31 25 24 23 22 21 31 30 29 31 37 28 31 34 33 33 36 26 27 33 31 32 21 22 23 24 25 27 26 28 29 30 31 32 35 34 33 36 38 38 37 LGH 65RX5 E...

Страница 98: ...k washer 4 H00 013 076 2 63 Transformer Y50 115 216 1 AC230V 64 PT screw 4 8 BS H00 011 008 1 65 TB fix plate Y50 115 712 1 66 Cord band K83 170 228 2 White 67 PCB fix plate R50 546 705 1 68 Bush R50...

Страница 99: ...99 51 52 54 53 56 57 55 58 59 60 61 67 68 75 72 74 73 77 76 8 8 8 8 8 8 8 8 76 72 8 8 8 8 35 8 62 63 64 66 69 70 71 65 69 62 8 LGH 65RX5 E shows accessory parts...

Страница 100: ...50 095 380 4 6 Cover R50 543 704 2 7 Flange Y50 021 609 4 8 PTT screw 4 8 H00 000 487 54 9 Maint cover R50 543 487 1 10 Filter R50 529 717 4 11 Lossnay core R50 543 711 2 With filter stoppers 12 Core...

Страница 101: ...101 8 8 8 8 8 2 1 13 12 14 11 10 9 3 4 5 6 7 8 5 7 7 7 8 14 10 5 1 2 2 2 5 8 4 LGH 80RX5 E shows accessory parts...

Страница 102: ...otor Y50 117 454 2 29 Motor fix plate Y50 117 712 2 30 PTT screw 5 10 H00 189 007 16 31 Spl washer 6 M34 043 080 8 32 PT screw 6 20 H00 157 008 8 33 Cord bush M45 649 226 4 34 Connector cover Y50 115...

Страница 103: ...103 30 30 25 24 23 22 21 30 30 32 29 28 30 37 30 27 34 33 33 36 26 33 30 31 21 22 23 24 25 26 27 28 29 30 31 32 39 35 34 33 36 38 38 37 LGH 80RX5 E...

Страница 104: ...washer 4 H00 013 076 2 63 Transformer Y50 115 216 1 AC230V 64 PT screw 4 8 BS H00 011 008 1 65 TB fix plate Y50 115 712 1 66 Cord band K83 170 228 2 White 67 PCB fix plate R50 546 705 1 68 Bush R50 4...

Страница 105: ...105 51 52 54 53 56 57 55 58 59 60 61 67 68 75 72 74 73 77 76 8 8 8 8 8 8 8 8 76 72 8 8 8 8 35 8 62 63 64 66 69 70 71 65 8 62 69 LGH 80RX5 E shows accessory parts...

Страница 106: ...50 095 380 4 6 Cover R50 543 704 2 7 Flange Y50 021 609 4 8 PTT screw 4 8 H00 000 487 54 9 Maint cover R50 543 487 1 10 Filter R50 522 717 4 11 Lossnay core R50 544 710 2 With filter stoppers 12 Core...

Страница 107: ...107 2 1 13 14 11 12 10 9 3 4 5 6 7 8 5 7 8 10 14 5 1 2 2 2 5 8 7 7 4 8 8 8 8 8 LGH 100RX5 E shows accessory parts...

Страница 108: ...Motor Y50 118 451 2 29 Motor fix plate Y50 117 712 2 30 PTT screw 5 10 H00 189 007 16 31 Spl washer 6 M34 043 080 8 32 PT screw 6 20 H00 157 008 8 33 Cord bush M45 649 226 4 34 Connector cover Y50 115...

Страница 109: ...109 30 30 25 24 23 22 21 30 30 32 30 29 28 27 30 34 37 33 33 36 26 33 30 31 21 22 23 24 25 26 27 28 29 30 39 31 32 35 34 33 36 38 37 38 LGH 100RX5 E...

Страница 110: ...76 2 63 Transformer Y50 115 216 1 AC230V 64 PT screw 4 8 BS H00 011 008 1 65 TB fix plate Y50 115 712 1 66 Cord band K83 170 228 2 White 67 PCB fix plate R50 546 705 1 68 Bush R50 476 225 1 69 PP scre...

Страница 111: ...to the new capacitors 2 No 78 during production so there are two types of the capacitors on the market Check the production number production year and month shown on the nameplate and choose the appli...

Страница 112: ...7 99 6 Flange R50 545 704 2 7 Hinge R50 466 344 2 8 Hanger R50 111 381 8 9 PT screw 6 12 H00 000 244 40 10 Filter R50 529 717 8 11 Lossnay core R50 543 711 4 With filter stoppers 12 Core guide R R50 5...

Страница 113: ...113 8 8 8 8 8 8 2 1 3 4 11 10 12 13 15 14 6 8 7 9 5 3 3 3 2 10 8 8 8 9 8 8 13 15 14 15 15 5 6 5 9 5 5 LGH 150RX5 E shows accessory parts...

Страница 114: ...otor Y50 117 454 4 29 Motor fix plate Y50 117 712 4 30 PTT screw 5 10 H00 189 007 32 31 Spl washer 6 M34 043 080 16 32 PT screw 6 20 H00 157 008 16 33 Cord bush M45 649 226 8 34 Connector cover Y50 11...

Страница 115: ...115 30 30 25 24 23 22 21 30 29 28 30 30 37 30 27 34 33 33 36 26 33 30 31 32 21 22 23 24 25 26 27 28 29 39 30 31 32 35 34 33 36 37 38 38 LGH 150RX5 E...

Страница 116: ...d band K83 170 228 3 White 67 PPT screw 3 6 H00 000 384 12 68 Relay Y50 009 268 6 LY 2F 69 Circuit board Y50 115 171 1 LG X3 E 70 PCB case D40 169 382 1 71 PP screw 4 8 H00 000 003 6 72 Transformer Y5...

Страница 117: ...117 51 52 53 55 54 66 75 76 85 81 82 73 56 59 60 61 68 67 72 71 70 69 62 63 64 65 57 58 35 71 71 71 82 52 55 5 5 64 64 5 64 5 5 5 52 74 80 79 78 77 83 84 LGH 150RX5 E shows accessory parts...

Страница 118: ...7 99 6 Flange R50 545 704 2 7 Hinge R50 466 344 2 8 Hanger R50 111 381 8 9 PT screw 6 12 H00 000 244 40 10 Filter R50 522 717 8 11 Lossnay core R50 544 710 4 With filter stoppers 12 Core guide R R50 5...

Страница 119: ...119 8 8 8 8 8 8 2 1 3 4 11 10 12 13 15 14 6 8 7 9 5 3 3 3 2 10 8 8 8 9 8 8 13 15 14 15 15 5 6 5 9 5 5 LGH 200RX5 E shows accessory parts...

Страница 120: ...otor Y50 118 451 4 29 Motor fix plate Y50 117 712 4 30 PTT screw 5 10 H00 189 007 32 31 Spl washer 6 M34 043 080 16 32 PT screw 6 20 H00 157 008 16 33 Cord bush M45 649 226 8 34 Connector cover Y50 11...

Страница 121: ...121 30 30 25 24 23 22 21 30 29 28 30 30 37 30 27 34 33 33 36 26 33 30 31 32 21 22 23 24 25 26 27 28 29 39 30 31 32 35 34 33 36 37 38 38 LGH 200RX5 E...

Страница 122: ...384 12 67 Relay Y50 009 268 6 LY 2F 68 Control base Y50 118 708 1 69 Support plate Y50 118 710 1 70 Circuit board Y50 115 171 1 LG X3 E 71 PCB case D40 169 382 1 72 PP screw 4 8 H00 000 003 6 73 Tran...

Страница 123: ...1 No 64 were changed to the new capacitors 2 No 86 during production so there are two types of the capacitors on the market Check the production number production year and month shown on the nameplat...

Отзывы: