Exhaust Extra High/High *
ON : Exhaust air fan Extra High fan speed
OFF: Exhaust air fan High fan speed (Factory setting)
10
Pulse input *
ON : At time of pulse signal input (Requires a pulse width of 200 ms or
greater)
OFF: At time of Level signal and Mr. Slim signal inputs (Factory setting)
2
(10) Setting of function selection switches (SW1, 2, and 5)
The associated switches are as listed below.
* This function can also be set from PZ-60DR-E. When the function has been switched from the remote con-
troller later on, the system will operate according to the setting of the remote controller.
Type
Trial operation
ON : Trial operation mode
OFF: Normal mode (Factory setting)
SW2 1
Delay setting *
Note 2
ON : Delay operation of 30 minutes
OFF: Normal (Factory setting)
SW5 1
Operation output monitor *
ON : Operation monitor output correspond to air supply fan
OFF: Operation monitor output with normal operation (Factory setting)
2
Exhaust fan stop during air
conditioner defrost *
Exhaust fan Low fan speed at
outdoor air temperature of -
15ºC or lower *
ON : Both Exhaust air fan and Supply air fan (Low fan speed) opera-
tion at outdoor air temperature of -15ºC or lower
OFF: Exhaust fan operation (Only Supply air fan stopped) (Factory set-
ting)
3
Automatic recovery after
power failure *
Note 2
ON : After the recovery, operation at the mode preceding the power
failure
OFF: Stop after the recovery (Factory setting)
4
Filter cleaning setting *
Note 2
Selection switch for accumulated running time of the filter cleaning dis-
play.
ON : 3,000 hours
OFF: No filter maintenance display (Factory setting)
5
TM3
6
,
7
output setting
ON : Operation monitor output with delay functions 2. Refer to (3)
2
Fan speed control by function setting (page 26), and (6)
1
Output terminals (page 33).
OFF: Bypass ventilation operation monitor output (Factory setting)
6
Interlock mode setting *
Note 2
Effective only at time of external control input usage.
Refer to (5)
2
Interlock mode (page 32).
7
8
Power supply/exhaust when
operation starts *
ON : Power supply exhaust mode
OFF: Normal mode (Factory setting)
3
SA fan fixed at Low speed *
ON : Low fan speed fixed
OFF: Normal mode (Factory setting)
4
EA fan fixed at Low speed *
ON : Low fan speed fixed
OFF: Normal mode (Factory setting)
5
Power supply ON/OFF *
Note 2
ON : Enable
OFF: Disable (Factory setting)
6
Bypass ventilation priority at
Automatic mode *
Temperature condition for
Night purge operation
ON : Automatic ventilation outdoor air cooling priority mode / Night
purge operation condition of outdoor air temperature is 17ºC or
higher (within 24 hours)
OFF: Automatic ventilation normal mode / Night purge operation condi-
tion of outdoor air temperature is 28ºC or higher (within 24 hours)
(Factory setting)
7
TM4
9
,
0
output setting
ON : Operation monitor output with delay function 1. Refer to (3)
2
Fan speed control by function setting (page 26), and (6)
1
Output terminals (page 33).
OFF: Operation monitor output based on SW5-2 (Factory setting)
8
Supply Extra High/High *
ON : Supply air fan Extra High fan speed
OFF: Supply air fan High fan speed (Factory setting)
9
Name
Specification
SW1
Main/Sub selection switch
Lossnay control mode (Main/Sub) switching (The factory setting is set
to “Main”.)
Содержание LGH-100RX5-E
Страница 4: ...4 2 Specifications...
Страница 5: ...5...
Страница 6: ...6...
Страница 7: ...7...
Страница 8: ...8...
Страница 9: ...Unit mm LGH 15RX5 E 3 Outside dimensions 9...
Страница 10: ...Unit mm LGH 25RX5 E 10...
Страница 11: ...Unit mm LGH 35RX5 E 11...
Страница 12: ...12 Unit mm LGH 50RX5 E...
Страница 13: ...Unit mm LGH 65RX5 E 13...
Страница 14: ...14 Unit mm LGH 80RX5 E...
Страница 15: ...Unit mm LGH 100RX5 E 15...
Страница 16: ...16 Unit mm LGH 150RX5 E...
Страница 17: ...Unit mm LGH 200RX5 E 17...
Страница 18: ...18 Unit mm PZ 60DR E Unit mm PZ 25RF8 E PZ 35RF8 E PZ 50RF8 E PZ 65RF8 E PZ 80RF8 E PZ 100RF8 E...
Страница 71: ...71 LGH 15RX5 E 8 8 8 8 8 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 4 7 8 8 10 5 1 2 2 5 7 7 2 shows accessory parts...
Страница 77: ...77 8 8 8 8 8 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 4 7 8 8 10 5 1 2 2 5 7 7 2 LGH 25RX5 E shows accessory parts...
Страница 83: ...83 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 7 8 10 5 1 2 2 5 7 7 8 4 2 8 8 8 8 8 LGH 35RX5 E shows accessory parts...
Страница 89: ...89 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 7 8 10 5 1 2 2 5 7 7 8 4 2 8 8 8 8 8 LGH 50RX5 E shows accessory parts...
Страница 95: ...95 8 8 8 8 8 2 1 13 12 14 11 10 9 3 4 5 6 7 8 5 7 7 7 8 10 13 5 1 2 2 2 5 8 4 LGH 65RX5 E shows accessory parts...
Страница 101: ...101 8 8 8 8 8 2 1 13 12 14 11 10 9 3 4 5 6 7 8 5 7 7 7 8 14 10 5 1 2 2 2 5 8 4 LGH 80RX5 E shows accessory parts...
Страница 107: ...107 2 1 13 14 11 12 10 9 3 4 5 6 7 8 5 7 8 10 14 5 1 2 2 2 5 8 7 7 4 8 8 8 8 8 LGH 100RX5 E shows accessory parts...