Pattern 2. Outdoor cooling priority mode
When the outdoor temperature is lower than the indoor temperature, this mode actively takes in the out-
door air for cooling.
When PZ-60DR-E is used, operation will be at the setting of automatic ventilation adjustment pattern “2”
of the remote controller function selection. When PZ-60DR-E is not used, operation will be at the ON set-
ting of function selection switch (SW2-7) on the Lossnay circuit board.
0
5
10
15
20
25
30
35
40
0
5
10
15
20
25
30
35
40
Indoor temperature
ºC
Bypass ventilation
Prohibition temperature 8ºC 19ºC
Lossnay
Ventilation
0
5
10
15
20
25
30
35
40
0
5
10
15
20
25
30
35
40
Indoor temperature
ºC
Lossnay
Ventilation
19ºC
When an outdoor temperature of 17ºC has not
been detected within 24 hours
When an outdoor temperature of 17ºC has been
detected within 24 hours
Bypass ventilation
Prohibition temperature 8ºC
Outdoor temperature ºC
Outdoor temperature ºC
Undetermined area
When operation starts under this condition, Lossnay ventilation will be activated.
When this condition is reached after operation starts, the current ventilation mode is maintained.
Lossnay ventilation area
Bypass ventilation area
Undetermined area
Bypass
Ventilation
Bypass
Ventilation
Undetermined area
b. When there is no interlocking with Mr. Slim and City Multi indoor units
Pattern 1. Normal ventilation mode
When PZ-60DR-E is used, operation will be at the setting of automatic ventilation adjustment pattern “1”
of the remote controller function selection. When PZ-60DR-E is not used, operation will be at the OFF
setting of function selection switch (SW2-7) on the Lossnay circuit board.
When an outdoor temperature of 28ºC has not
been detected within 24 hours
0
5
10
15
20
25
30
35
40
0
5
10
15
20
25
30
35
40
Indoor temperature ºC
24ºC
Lossnay
Ventilation
When an outdoor temperature of 28ºC has been
detected within 24 hours
0
5
10
15
20
25
30
35
40
0
5
10
15
20
25
30
35
40
Indoor temperature ºC
Lossnay
Ventilation
24ºC
Bypass ventilation
Prohibition temperature 8ºC
Bypass ventilation
Prohibition temperature 8ºC
Outdoor temperature ºC
Outdoor temperature ºC
Undetermined area
When operation starts under this condition, Lossnay ventilation will be activated.
When this condition is reached after operation starts, the current ventilation mode is maintained.
Lossnay ventilation area
Bypass ventilation area
Undetermined area
Bypass
Ventilation
Undetermined area
Bypass
Ventilation
Содержание LGH-100RX5-E
Страница 4: ...4 2 Specifications...
Страница 5: ...5...
Страница 6: ...6...
Страница 7: ...7...
Страница 8: ...8...
Страница 9: ...Unit mm LGH 15RX5 E 3 Outside dimensions 9...
Страница 10: ...Unit mm LGH 25RX5 E 10...
Страница 11: ...Unit mm LGH 35RX5 E 11...
Страница 12: ...12 Unit mm LGH 50RX5 E...
Страница 13: ...Unit mm LGH 65RX5 E 13...
Страница 14: ...14 Unit mm LGH 80RX5 E...
Страница 15: ...Unit mm LGH 100RX5 E 15...
Страница 16: ...16 Unit mm LGH 150RX5 E...
Страница 17: ...Unit mm LGH 200RX5 E 17...
Страница 18: ...18 Unit mm PZ 60DR E Unit mm PZ 25RF8 E PZ 35RF8 E PZ 50RF8 E PZ 65RF8 E PZ 80RF8 E PZ 100RF8 E...
Страница 71: ...71 LGH 15RX5 E 8 8 8 8 8 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 4 7 8 8 10 5 1 2 2 5 7 7 2 shows accessory parts...
Страница 77: ...77 8 8 8 8 8 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 4 7 8 8 10 5 1 2 2 5 7 7 2 LGH 25RX5 E shows accessory parts...
Страница 83: ...83 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 7 8 10 5 1 2 2 5 7 7 8 4 2 8 8 8 8 8 LGH 35RX5 E shows accessory parts...
Страница 89: ...89 2 1 12 13 14 11 10 9 3 4 5 6 7 8 5 7 8 10 5 1 2 2 5 7 7 8 4 2 8 8 8 8 8 LGH 50RX5 E shows accessory parts...
Страница 95: ...95 8 8 8 8 8 2 1 13 12 14 11 10 9 3 4 5 6 7 8 5 7 7 7 8 10 13 5 1 2 2 2 5 8 4 LGH 65RX5 E shows accessory parts...
Страница 101: ...101 8 8 8 8 8 2 1 13 12 14 11 10 9 3 4 5 6 7 8 5 7 7 7 8 14 10 5 1 2 2 2 5 8 4 LGH 80RX5 E shows accessory parts...
Страница 107: ...107 2 1 13 14 11 12 10 9 3 4 5 6 7 8 5 7 8 10 14 5 1 2 2 2 5 8 7 7 4 8 8 8 8 8 LGH 100RX5 E shows accessory parts...