background image

FX3G INSTALLATION MANUAL 

5

n

 WHEN THE TERMINAL BLOCK COVERS ARE OPEN

[3]

[4]
[2]

[5]

[1]

[2]

[1] Power supply terminal. Connect the power supply to the main 
unit.
[2] Terminal block mounting screws. If the main unit must be 
replaced, loosen the screws (slightly loosen the left and right screws), 
and the upper part of the terminal block can be removed.
[3] Input (X) terminals. Wire switches and sensors to the terminals.
[4] Output (Y) terminals. Wire loads (contactors, solenoid valves, etc.) 
to be driven to the terminals.
[5] Terminal cover. A protective terminal cover (refer to the following 
drawing) is fitted to the lower stage of each terminal block. The cover 
prevents fingers from touching terminals, thereby improving safety.

2. DIMENSIONS

Model Number

W: mm (inches)

W1: mm (inches) 

Direct mounting hole 

pitches

Weight: kg (lbs)

FX3G-14M_

90 (3.55")

82 (3.23")

0.50 (1.10 lbs.)

FX3G-24M_

90 (3.55")

82 (3.23")

0.55 (1.21 lbs.)

FX3G-40M_

130 (5.12")

122 (4.81")

0.70 (1.54 lbs.)

FX3G-60M_

175 (6.89")

167 (6.58")

0.85 (1.87 lbs.)

3. INSTALLATION

CAUTION:

 

INSTALLATION PRECAUTIONS

•  Use the product within the generic environment specifications 

described in Section 3.1 of this manual. Never use the product in 
areas with excessive dust, oily smoke, conductive dusts, corrosive 
gas (salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or 
impacts, or exposed to high temperature, condensation, or rain and 
wind. If the product is used in such conditions, electric shock, fire, 
malfunctions, deterioration or damage may occur.

•  Do not touch the conductive parts of the product directly to avoid 

failure or malfunctions.

•  Install the product securely using a DIN rail or mounting screws.

•  Install the product on a flat surface. If the mounting surface is 

rough, undue force will be applied to the PC board, thereby causing 
nonconformities.

•  When drilling screw holes or wiring, make sure cutting or wire debris 

does not enter the ventilation slits. Failure to do so may cause fire, 
equipment failures or malfunctions.

•  Be sure to remove the dust proof sheet from the PLC’s ventilation 

port when installation work is completed. Failure to do so may cause 
fire, equipment failures or malfunctions.

•  Connect the extension cables, peripheral device cables, input/output 

cables and battery connecting cable securely to their designated 
connectors. Unsecured connection may cause malfunctions.

•  Turn off the power before attaching or detaching the following 

devices. Failure to do so may cause device failures or malfunctions.

„

„

Battery

•  To prevent temperature rise, do not install the PLC on a floor, a 

ceiling or a vertical surface. Install it horizontally on a wall as shown 
in Section 3.2.

•  Keep a space of 50mm (1.97") or more between the unit main body 

and another device or structure (part A). Install the unit as far away 
as possible from high-voltage lines, high-voltage devices and power 
equipment.

DANGER: 

WIRING PRECAUTIONS

•  Cut off all phases of the power supply externally before installation 

or wiring work in order to avoid damage to the product or electric 
shock.

3.1  SPECIFICATIONS

n

 COMPLIANCE WITH EC DIRECTIVE (CE MARKING )

This document does not guarantee that a mechanical system including 
this product will comply with the following standards. Compliance 
to EMC directive and LVD directive of the entire mechanical system 
should be checked by the user / manufacturer. For more details please 
contact the local Mitsubishi Electric sales site.

n

 REQUIREMENT FOR COMPLIANCE WITH EMC DIRECTIVE

The following products have shown compliance through direct testing 
(of the identified standards below) and design analysis (through the 
creation of a technical construction file) to the European Directive for 
Electromagnetic Compatibility (2004/108/EC) when used as directed 
by the appropriate documentation. 

W1

W

90 (3.55")

82 (3.23")

2-

φ

4.5 mounting holes

86 (3.39")

8 (0.32")

Unit: mm(inches)

Mounting hole pitches

Содержание FX3G-14MR/ES

Страница 1: ...PROGRAMMABLE LOGIC CONTROLLER MODEL FX3G INSTALLATION MANUAL ...

Страница 2: ...S AND WIRING DIAGRAM 9 4 4 INPUT SPECIFICATIONS AND WIRING DIAGRAM 10 4 5 PULSE CATCH M8170 TO M8175 11 4 6 PULSE WIDTH PULSE PERIOD MEASUREMENT SPECIFICATIONS AND WIRING 11 4 7 HIGH SPEED COUNTERS SPECIFICATIONS AND WIRING 12 4 8 OUTPUT SPECIFICATIONS AND WIRING 13 5 PROGRAMMING USING GX WORKS2 14 5 1 SYSTEM CONFIGURATION 14 5 2 INSTALLING THE USB DRIVER 14 5 3 INSTALLING GX WORKS2 16 5 4 STARTIN...

Страница 3: ...ouch any terminal while the PLC s power is on Doing so may cause electric shock or malfunctions Before cleaning or retightening terminals externally cut off all phases of the power supply Failure to do so may cause electric shock Use the battery for memory backup correctly as described in this manual Use the battery only for the specified purpose Connect the battery correctly Do not charge disasse...

Страница 4: ...attery is used 8 Output display LEDs red When an output terminal Y000 or more is turned on the corresponding LED lights 9 Model name abbreviation The model name of the main unit is indicated Check the nameplate on the right side for the model name 10 DIN rail mounting hooks The main unit can be installed on DIN46277 rail 35mm 1 38 wide 11 The year and month of production The year and month of prod...

Страница 5: ...cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Be sure to remove the dust proof sheet from the PLC s ventilation port when installation work is completed Failure to do so may cause fire equipment failures or malfunctions Connect the extension cables peripheral device cables input output cables and battery connecting ca...

Страница 6: ...e of 1 000Vp p noise width of 1μs rise time of 1ns and period of 30 to 100Hz Dielectric Withstand Voltage 2 1 5kVAC for one minute Between each terminals 2 and ground terminal 500VAC for one minute Insulation Resistance 2 5MΩ or more by 500VDC megger Grounding Class D grounding grounding resistance 100Ω or less Common grounding with a heavy electrical system is not allowed 3 Working Atmosphere Fre...

Страница 7: ... AC power supply type has 0V and 24V terminals whereas the DC power supply type shows since the DC power supply type does not have the service power supply Do not connect with terminals Indication of Input terminal Both AC and DC power supply type have the same input terminals however the external input wiring differs from each other Indication of output terminals connected to common terminal One ...

Страница 8: ...r an abnormal voltage drop occurs the PLC stops and output is turned off When the power supply is restored it will automatically restart when the RUN input is on DANGER WIRING PRECAUTIONS Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the product or electric shock CAUTION WIRING PRECAUTIONS Connect the AC power supply to the dedicat...

Страница 9: ... possible If it cannot be grounded independently ground it jointly as shown below Use ground wires thicker than AWG14 2 mm Position the grounding point as close to the PLC as possible to decrease the length of the ground wire 4 3 POWER SUPPLY SPECIFICATIONS AND WIRING DIAGRAM n POWER SUPPLY SPECIFICATIONS Item Specification AC Power Type DC Power Type Supply Voltage 100 to 240VAC 24VDC Allowable S...

Страница 10: ...tact input Sink input NPN open collector transistor Source input PNP open collector transistor Input Circuit Insulation Photocoupler insulation Input Operation Display LED on panel lights when photocoupler is driven INPUT CIRCUIT CONFIGURATION 1 Each value inside indicates the number of occupied points 2 Input impedance 3 The 24V and 0V terminals are located on the output terminal side n INSTRUCTI...

Страница 11: ...ection in GX Works2 n CAUTIONS FOR PULSE WIDTH PERIOD MEASUREMENT FUNCTION 1 Non overlap of input numbers The input terminals X000 X001 X003 and X004 can be used for high speed counter input interruption pulse catch speed detection SPD instructions and general purpose input Take care not to overlap the input numbers However overlap of input numbers is allowed for input interruptions 2 When the pul...

Страница 12: ...iring apply to the cases where C251 is used When another high speed counter number is used wire the counter referring to the following diagrams It is recommended to use shielded twisted pair cables for connection cables Ground the shield of each shielded cable only on the PLC side 1 NPN open collector transistor output rotary encoder 2 PNP open collector transistor output rotary encoder The ground...

Страница 13: ...ercurrent is shut down Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load 2 Lamp load Lamp loads generally generate rush current 10 to 15 times the stationary current Make sure that the rush current does not exceed the current corres...

Страница 14: ... is at least 2 times larger than the total rated fuse capacity n CONTACT PROTECTION CIRCUIT FOR INDUCTIVE LOADS When an inductive load is connected connect a diode for commutation in parallel with the load as necessary The diode for commutation must comply with the following specifications Item Guide Reverse voltage 5 to 10 times of the load voltage Forward current Load current or more n INTERLOCK...

Страница 15: ... to their installed location POINT Considerations when installing USB driver If the USB driver cannot be installed confirm the following Windows settings If Block Never install unsigned driver software is selected under Control Panel System Hardware Driver Signing the USB driver may not be installed Select Ignore Install the software anyway and don t ask for my approval or Warn Prompt me each time...

Страница 16: ...on POINT Product ID is written on the License certificate included with the product Enter the 12 digit number divided into 3 and 9 digits n OPERATING ENVIRONMENT Item Contents Personal Com puter Windows supported personal computer CPU Intel Core 2 Duo Processor 2GHz or more recommended Required Memory 1GB or more recommended Available Hard Disk Capacity When installing GX Works2 HDD available capa...

Страница 17: ... a list of functions such as function blocks used for programming Output Display compilation and check results errors and warnings Cross Reference Display cross reference results Device List Display the device list Watch 1 to 4 A screen used for monitoring and changing current device values Intelligent Function Module Monitor 1 to 10 Screens used for monitoring intelligent function modules Find Re...

Страница 18: ...unit n FOR CONTINUOUS USE OF A PERIPHERAL DEVICE SUCH AS GOT Cut off the area shown in the left figure below of the peripheral device connector cover main unit using a nipper etc and connect the peripheral device as shown in the right figure below n CONNECTION TO BUILT IN PROGRAMMING CONNECTOR USB Connect and disconnect the communication cable for the peripheral device personal computer At connect...

Страница 19: ...d is given from the programming software after the PLC is started by either the built in RUN STOP switch or the general purpose input RUN terminal the PLC will be restored to the running status by giving the RUN command from the programming software This can also be accomplished by setting the built in RUN STOP switch or the general purpose input RUN terminal to STOP and then to RUN n OPERATION AN...

Страница 20: ...INTENANCE This PLC does not incorporate consumable parts that are factors in the reduction of service life However the output relays points of contact and batteries option have a limited life expectancy n PERIODIC INSPECTION BATTERY LIFE ETC 1 BATTERY Model FX3U 32BL battery Standard life 5 years at ambient temperature of 25 C 77 F 2 OTHER DEVICES When inspecting the battery check the following po...

Страница 21: ...ply power If ERR LED goes off a watchdog timer error may have occurred Take any of the following measures Review the program The maximum value D8012 of the scan time should not exceed the setting D8000 of the watchdog timer Check that the input used for input interruption or pulse catch is not being abnormally turned on and off in one scan Check that the frequency of the pulse duty of 50 input to ...

Страница 22: ...easures When input turns on Check that the input device does not have a built in diode or parallel resistance When input does not turn on Measure the voltage between the 0V terminal or 24V terminal not connected to the S S terminal and the input terminal with a tester to confirm that the voltage is 24VDC Check the configuration of the external wiring and connected devices and the connection of the...

Страница 23: ...FX3G INSTALLATION MANUAL 23 ...

Страница 24: ...orporate Woods Parkway Vernon Hills IL 60061 Phn 847 478 2100 us MitsubishiElectric com fa en Serving the Americas AZ JY997D33401 A Effective January 2016 Specifications subject to change without notice 2016 Mitsubishi Electric Automation Inc ...

Отзывы: