background image

FX3G INSTALLATION MANUAL 

9

4.1  WIRING

n

 CABLE END TREATMENT AND TIGHTENING TORQUE

•  For the terminals of FX3G series PLC, M3 screws are used.  

The electric wire ends should be treated as shown below.

•  Tighten the screws to a torque of 0.5 to 0.8 N•m.

•  Do not tighten terminal screws with a torque exceeding the 

regulation torque.

•  Failure to do so may cause equipment failures or malfunctions.

n

 WHEN ONE WIRE IS CONNECTED TO ONE TERMINAL

Terminal Manufacturer

Type No.

Certification

Pressure 

Bonding Tool

JAPAN SOLDERLESS 

TERMINAL MFG CO 

LTD (JST)

FV1.25-B3A

UL Listed

YA-1(JST)

FV2-MS3

n

 WHEN TWO WIRES ARE CONNECTED TO ONE TERMINAL

Terminal Manufacturer

Type No.

Certification

Pressure 

Bonding Tool

JAPAN SOLDERLESS 

TERMINAL MFG CO 

LTD (JST)

FV1.25-B3A

UL Listed

YA-1(JST)

n

 REMOVAL AND INSTALLATION OF QUICK-RELEASE  

    TERMINAL BLOCK
REMOVAL
 Unscrew the terminal block mounting screw [both right and 
left screws] evenly, and remove the terminal block. 
INSTALLATION Place the terminal block in the specified position, and 
tighten the terminal block mounting screw evenly [both right and left 
screws]. Tightening torque 0.4 to 0.5 N • m 
Do not tighten the terminal block mounting screws with a torque 
exceeding the regulation torque. 
Failure to do so may cause equipment failures or malfunctions.

* Pay attention so that the center of the terminal block is not lifted.

4.2  GROUNDING

Ground the PLC as stated below.

•  Perform class D grounding. (Grounding resistance: 100 Ω or less)

•  Ground the PLC independently if possible.

If it cannot be grounded independently, ground it jointly as shown 
below.

•  Use ground wires thicker than AWG14 (2 mm²).

•  Position the grounding point as close to the PLC as possible to 

decrease the length of the ground wire.

4.3  POWER SUPPLY SPECIFICATIONS AND  
       WIRING DIAGRAM

n

 POWER SUPPLY SPECIFICATIONS

Item

Specification
AC Power Type

DC Power Type

Supply Voltage

100 to 240VAC

24VDC

Allowable Supply Voltage 

Range

85 to 264VAC

20.4 to 28.8VDC

Rated Frequency

50/60Hz

-

Allowable Instantaneous 

Power Failure Time

Operation can be 

continued upon 

occurrence of 

instantaneous power 

failure for 10 ms or less.

Operation can be 

continued upon 

occurrence of 

instantaneous power 

failure for 5 ms or less.

Power Fuse

FX3G-14M_

FX3G-24M_

250V 1A

125V 2.5A

FX3G-40M_

FX3G-60M_

250V 3.15A

125V 3.15A

Rush Current Main unit

30A max. 5ms or 

less/100 VAC 50A max. 

5ms or less/200 VAC

30A max. 1ms or less/ 

24 VDC

Power 

Consumption 

*1

FX3G-14M_

31W

19W

FX3G-24M_

32W

21W

FX3G-40M_

37W

25W

FX3G-60M_

40W

29W

24VDC 

Service 

Power Supply

Main Unit

400mA

-

*1 This item shows values when all 24V DC service power supplies are used in the 

maximum configuration connectable to the main unit or input/output extension units 

(The DC power type main unit does not have a 24V DC service power supply.)

φ

3.2 (0.13")

6.2 mm (0.24")

or less

Terminal
screw

Solderless
terminal

6.2 mm (0.24")

or less

φ

3.2 (0.13")

Terminal

6.3 mm(0.25")
or more

6.3 mm(0.25")
or more

6.2 mm (0.24")

or less

6.2 mm (0.24")

or less

φ

3.2 (0.13")

φ

3.2 (0.13")

Terminal

Terminal
screw

Solderless
terminal

PLC

PLC

PLC

Other

equipment

Shared grounding

(Good condition)

Common grounding

(Not allowed)

Independent grounding

(Best condition)

Other

equipment

Other

equipment

Содержание FX3G-14MR/ES

Страница 1: ...PROGRAMMABLE LOGIC CONTROLLER MODEL FX3G INSTALLATION MANUAL ...

Страница 2: ...S AND WIRING DIAGRAM 9 4 4 INPUT SPECIFICATIONS AND WIRING DIAGRAM 10 4 5 PULSE CATCH M8170 TO M8175 11 4 6 PULSE WIDTH PULSE PERIOD MEASUREMENT SPECIFICATIONS AND WIRING 11 4 7 HIGH SPEED COUNTERS SPECIFICATIONS AND WIRING 12 4 8 OUTPUT SPECIFICATIONS AND WIRING 13 5 PROGRAMMING USING GX WORKS2 14 5 1 SYSTEM CONFIGURATION 14 5 2 INSTALLING THE USB DRIVER 14 5 3 INSTALLING GX WORKS2 16 5 4 STARTIN...

Страница 3: ...ouch any terminal while the PLC s power is on Doing so may cause electric shock or malfunctions Before cleaning or retightening terminals externally cut off all phases of the power supply Failure to do so may cause electric shock Use the battery for memory backup correctly as described in this manual Use the battery only for the specified purpose Connect the battery correctly Do not charge disasse...

Страница 4: ...attery is used 8 Output display LEDs red When an output terminal Y000 or more is turned on the corresponding LED lights 9 Model name abbreviation The model name of the main unit is indicated Check the nameplate on the right side for the model name 10 DIN rail mounting hooks The main unit can be installed on DIN46277 rail 35mm 1 38 wide 11 The year and month of production The year and month of prod...

Страница 5: ...cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Be sure to remove the dust proof sheet from the PLC s ventilation port when installation work is completed Failure to do so may cause fire equipment failures or malfunctions Connect the extension cables peripheral device cables input output cables and battery connecting ca...

Страница 6: ...e of 1 000Vp p noise width of 1μs rise time of 1ns and period of 30 to 100Hz Dielectric Withstand Voltage 2 1 5kVAC for one minute Between each terminals 2 and ground terminal 500VAC for one minute Insulation Resistance 2 5MΩ or more by 500VDC megger Grounding Class D grounding grounding resistance 100Ω or less Common grounding with a heavy electrical system is not allowed 3 Working Atmosphere Fre...

Страница 7: ... AC power supply type has 0V and 24V terminals whereas the DC power supply type shows since the DC power supply type does not have the service power supply Do not connect with terminals Indication of Input terminal Both AC and DC power supply type have the same input terminals however the external input wiring differs from each other Indication of output terminals connected to common terminal One ...

Страница 8: ...r an abnormal voltage drop occurs the PLC stops and output is turned off When the power supply is restored it will automatically restart when the RUN input is on DANGER WIRING PRECAUTIONS Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the product or electric shock CAUTION WIRING PRECAUTIONS Connect the AC power supply to the dedicat...

Страница 9: ... possible If it cannot be grounded independently ground it jointly as shown below Use ground wires thicker than AWG14 2 mm Position the grounding point as close to the PLC as possible to decrease the length of the ground wire 4 3 POWER SUPPLY SPECIFICATIONS AND WIRING DIAGRAM n POWER SUPPLY SPECIFICATIONS Item Specification AC Power Type DC Power Type Supply Voltage 100 to 240VAC 24VDC Allowable S...

Страница 10: ...tact input Sink input NPN open collector transistor Source input PNP open collector transistor Input Circuit Insulation Photocoupler insulation Input Operation Display LED on panel lights when photocoupler is driven INPUT CIRCUIT CONFIGURATION 1 Each value inside indicates the number of occupied points 2 Input impedance 3 The 24V and 0V terminals are located on the output terminal side n INSTRUCTI...

Страница 11: ...ection in GX Works2 n CAUTIONS FOR PULSE WIDTH PERIOD MEASUREMENT FUNCTION 1 Non overlap of input numbers The input terminals X000 X001 X003 and X004 can be used for high speed counter input interruption pulse catch speed detection SPD instructions and general purpose input Take care not to overlap the input numbers However overlap of input numbers is allowed for input interruptions 2 When the pul...

Страница 12: ...iring apply to the cases where C251 is used When another high speed counter number is used wire the counter referring to the following diagrams It is recommended to use shielded twisted pair cables for connection cables Ground the shield of each shielded cable only on the PLC side 1 NPN open collector transistor output rotary encoder 2 PNP open collector transistor output rotary encoder The ground...

Страница 13: ...ercurrent is shut down Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load 2 Lamp load Lamp loads generally generate rush current 10 to 15 times the stationary current Make sure that the rush current does not exceed the current corres...

Страница 14: ... is at least 2 times larger than the total rated fuse capacity n CONTACT PROTECTION CIRCUIT FOR INDUCTIVE LOADS When an inductive load is connected connect a diode for commutation in parallel with the load as necessary The diode for commutation must comply with the following specifications Item Guide Reverse voltage 5 to 10 times of the load voltage Forward current Load current or more n INTERLOCK...

Страница 15: ... to their installed location POINT Considerations when installing USB driver If the USB driver cannot be installed confirm the following Windows settings If Block Never install unsigned driver software is selected under Control Panel System Hardware Driver Signing the USB driver may not be installed Select Ignore Install the software anyway and don t ask for my approval or Warn Prompt me each time...

Страница 16: ...on POINT Product ID is written on the License certificate included with the product Enter the 12 digit number divided into 3 and 9 digits n OPERATING ENVIRONMENT Item Contents Personal Com puter Windows supported personal computer CPU Intel Core 2 Duo Processor 2GHz or more recommended Required Memory 1GB or more recommended Available Hard Disk Capacity When installing GX Works2 HDD available capa...

Страница 17: ... a list of functions such as function blocks used for programming Output Display compilation and check results errors and warnings Cross Reference Display cross reference results Device List Display the device list Watch 1 to 4 A screen used for monitoring and changing current device values Intelligent Function Module Monitor 1 to 10 Screens used for monitoring intelligent function modules Find Re...

Страница 18: ...unit n FOR CONTINUOUS USE OF A PERIPHERAL DEVICE SUCH AS GOT Cut off the area shown in the left figure below of the peripheral device connector cover main unit using a nipper etc and connect the peripheral device as shown in the right figure below n CONNECTION TO BUILT IN PROGRAMMING CONNECTOR USB Connect and disconnect the communication cable for the peripheral device personal computer At connect...

Страница 19: ...d is given from the programming software after the PLC is started by either the built in RUN STOP switch or the general purpose input RUN terminal the PLC will be restored to the running status by giving the RUN command from the programming software This can also be accomplished by setting the built in RUN STOP switch or the general purpose input RUN terminal to STOP and then to RUN n OPERATION AN...

Страница 20: ...INTENANCE This PLC does not incorporate consumable parts that are factors in the reduction of service life However the output relays points of contact and batteries option have a limited life expectancy n PERIODIC INSPECTION BATTERY LIFE ETC 1 BATTERY Model FX3U 32BL battery Standard life 5 years at ambient temperature of 25 C 77 F 2 OTHER DEVICES When inspecting the battery check the following po...

Страница 21: ...ply power If ERR LED goes off a watchdog timer error may have occurred Take any of the following measures Review the program The maximum value D8012 of the scan time should not exceed the setting D8000 of the watchdog timer Check that the input used for input interruption or pulse catch is not being abnormally turned on and off in one scan Check that the frequency of the pulse duty of 50 input to ...

Страница 22: ...easures When input turns on Check that the input device does not have a built in diode or parallel resistance When input does not turn on Measure the voltage between the 0V terminal or 24V terminal not connected to the S S terminal and the input terminal with a tester to confirm that the voltage is 24VDC Check the configuration of the external wiring and connected devices and the connection of the...

Страница 23: ...FX3G INSTALLATION MANUAL 23 ...

Страница 24: ...orporate Woods Parkway Vernon Hills IL 60061 Phn 847 478 2100 us MitsubishiElectric com fa en Serving the Americas AZ JY997D33401 A Effective January 2016 Specifications subject to change without notice 2016 Mitsubishi Electric Automation Inc ...

Отзывы: