FX3G INSTALLATION MANUAL 

19

1. 

Operation with built-in RUN/STOP switch 
Operate the RUN/STOP switch on the front panel of the main unit to 
start and stop the PLC (refer to the right figure). Turn the switch to 
RUN, and the PLC will start. Turn it to STOP, and the PLC will stop.

2. 

Running and stopping with general-purpose input  
(RUN terminal) 
Operation with one switch (RUN)  
One of the input terminals X000 to X017 *1 of the main unit can 
be used as a RUN input terminal by a parameter setting (refer to 
the figure below). When the specified input terminal is turned on, 
the PLC starts. When it is turned off, the PLC is started or stopped 
depending on the state of the built-in RUN/STOP switch.

*1. X000 to X007 in 14-point type main units, and X000 to X015 in 
24-point type main units.

For details, refer to the HELP menu in GX Works2.

Operation with two switches (RUN and STOP)

The PLC can be started and stopped with individual RUN and STOP 
pushbutton switches. For this operation, a sequence program using 
M8035 to M8037 is necessary.

For details, refer to the HELP menu in GX Works2.

3. 

Starting and stopping by remote control from programming 
software

The programming software has a function to forcibly start and stop the 
PLC by remote control (remote RUN/STOP function). However, when 
power is reapplied, the remote RUN/STOP function is disabled. The 
RUN/STOP status is then determined by the RUN/STOP switch or 
RUN terminal.

For details on the start and stop procedures with remote control from 
programming software, see below.

n

 USE OF SEVERAL RUNNING/STOPPING METHODS

1. When the built-in RUN/STOP switch and the general-purpose RUN 

terminal are used

(without remote running/stopping operation from the programming 
software) The RUN/STOP status of the PLC is determined by the 
conditions shown in the following table.

Condition of 

Built-in RUN/STOP 

Switch

Condition of General-Purpose 

Input Terminal Specified as 

RUN Terminal by Parameter

Status of PLC

RUN

OFF

RUN

ON

RUN

STOP

OFF

STOP

ON

RUN

Use either built-in RUN/STOP switch or the general input specified as 
RUN terminal. (When specifying the general-purpose terminal as the 
RUN terminal, always set the built-in RUN/STOP switch to STOP.)

2. 

When the remote running/stopping operation from the 

programming software is performed

For this operation, keep both the built-in RUN/STOP switch and the 
general-purpose input RUN terminal in the STOP position. If the stop 
command is given from the programming software after the PLC is 
started by either the built-in RUN/STOP switch or the general-purpose 
input RUN terminal, the PLC will be restored to the running status by 
giving the RUN command from the programming software. This can 
also be accomplished by setting the built-in RUN/STOP switch or the 
general-purpose input RUN terminal to STOP and then to RUN.

n

 OPERATION AND TEST [POWER ON AND PLC RUNNING]

SELF-DIAGNOSTIC FUNCTION

When the PLC’s power is turned on, its self-diagnostic function starts 
automatically. If there are no problems with the hardware, parameters 
or program, the PLC will start and the RUN command (refer to Section 
14.2) is given (RUN LED is lit). If any problems are found, the “ERR” 
LED flashes or lights.

TEST FUNCTIONS

Functions of the programming tool to turn on/off the PLC devices 
and change the current values/settings are effective or ineffective 
depending on the PLC status as shown below.

X: Effective    O: Conditionally Effective  – : Ineffective

Item

In Running 

Status

In Stopped 

Status

Forcible ON/OFF *1

Devices used in program

O *1

O*1

Devices not in use

X

X

Change of current 

values of timers, 

counters, data 

registers, extension 

registers, extension 

file registers and 

file registers *4

Devices used in program

O *2, *3

X *3

Devices not in use

X *3

X *3

Change of settings 

of timers and 

counters *5

When the program memory is 

the built-in EEPROM

X

X

When the program memory is 

in the memory cassette and 

the PROTECT switch is on

When the program memory is 

in the memory cassette and 

the PROTECT switch is off

X

X

1.  Forcible ON/OFF

- The forcible ON/OFF function is effective on the input relays (X), output relays 

(Y), auxiliary relays (M), state (S), timers (T) and counters (C). On the display 

module, the function cannot be operated for the input relays (X). 

- The forcible ON/OFF function can turn on or off the devices only for one scan. 

While the PLC is running, the function is substantially effective in clearing the 

current values of the timers (T), counters (C), data registers (D), index registers 

(Z and V) and extension registers (R) and in controlling the SET/RST circuit and 

RUN/STOP switch

X000 X001 X002

0V

24V

S/S

Main unit (sink input)

RUN

General-purpose input terminal

specified as RUN input by

parameter

X000 X001 X002

0V

24V

S/S

Main unit (source input)

RUN

General-purpose input terminal

specified as RUN input by

parameter

X000 X001 X002

0V

24V

S/S

Main unit(sink input)

RUN STOP

General-purpose input terminal

specified as RUN input by

parameter

X000 X001 X002

0V

24V

S/S

Main unit(source input)

RUN STOP

General-purpose input terminal

specified as RUN input by

parameter

Содержание FX3G-14MR/ES

Страница 1: ...PROGRAMMABLE LOGIC CONTROLLER MODEL FX3G INSTALLATION MANUAL ...

Страница 2: ...S AND WIRING DIAGRAM 9 4 4 INPUT SPECIFICATIONS AND WIRING DIAGRAM 10 4 5 PULSE CATCH M8170 TO M8175 11 4 6 PULSE WIDTH PULSE PERIOD MEASUREMENT SPECIFICATIONS AND WIRING 11 4 7 HIGH SPEED COUNTERS SPECIFICATIONS AND WIRING 12 4 8 OUTPUT SPECIFICATIONS AND WIRING 13 5 PROGRAMMING USING GX WORKS2 14 5 1 SYSTEM CONFIGURATION 14 5 2 INSTALLING THE USB DRIVER 14 5 3 INSTALLING GX WORKS2 16 5 4 STARTIN...

Страница 3: ...ouch any terminal while the PLC s power is on Doing so may cause electric shock or malfunctions Before cleaning or retightening terminals externally cut off all phases of the power supply Failure to do so may cause electric shock Use the battery for memory backup correctly as described in this manual Use the battery only for the specified purpose Connect the battery correctly Do not charge disasse...

Страница 4: ...attery is used 8 Output display LEDs red When an output terminal Y000 or more is turned on the corresponding LED lights 9 Model name abbreviation The model name of the main unit is indicated Check the nameplate on the right side for the model name 10 DIN rail mounting hooks The main unit can be installed on DIN46277 rail 35mm 1 38 wide 11 The year and month of production The year and month of prod...

Страница 5: ...cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Be sure to remove the dust proof sheet from the PLC s ventilation port when installation work is completed Failure to do so may cause fire equipment failures or malfunctions Connect the extension cables peripheral device cables input output cables and battery connecting ca...

Страница 6: ...e of 1 000Vp p noise width of 1μs rise time of 1ns and period of 30 to 100Hz Dielectric Withstand Voltage 2 1 5kVAC for one minute Between each terminals 2 and ground terminal 500VAC for one minute Insulation Resistance 2 5MΩ or more by 500VDC megger Grounding Class D grounding grounding resistance 100Ω or less Common grounding with a heavy electrical system is not allowed 3 Working Atmosphere Fre...

Страница 7: ... AC power supply type has 0V and 24V terminals whereas the DC power supply type shows since the DC power supply type does not have the service power supply Do not connect with terminals Indication of Input terminal Both AC and DC power supply type have the same input terminals however the external input wiring differs from each other Indication of output terminals connected to common terminal One ...

Страница 8: ...r an abnormal voltage drop occurs the PLC stops and output is turned off When the power supply is restored it will automatically restart when the RUN input is on DANGER WIRING PRECAUTIONS Cut off all phases of the power supply externally before installation or wiring work in order to avoid damage to the product or electric shock CAUTION WIRING PRECAUTIONS Connect the AC power supply to the dedicat...

Страница 9: ... possible If it cannot be grounded independently ground it jointly as shown below Use ground wires thicker than AWG14 2 mm Position the grounding point as close to the PLC as possible to decrease the length of the ground wire 4 3 POWER SUPPLY SPECIFICATIONS AND WIRING DIAGRAM n POWER SUPPLY SPECIFICATIONS Item Specification AC Power Type DC Power Type Supply Voltage 100 to 240VAC 24VDC Allowable S...

Страница 10: ...tact input Sink input NPN open collector transistor Source input PNP open collector transistor Input Circuit Insulation Photocoupler insulation Input Operation Display LED on panel lights when photocoupler is driven INPUT CIRCUIT CONFIGURATION 1 Each value inside indicates the number of occupied points 2 Input impedance 3 The 24V and 0V terminals are located on the output terminal side n INSTRUCTI...

Страница 11: ...ection in GX Works2 n CAUTIONS FOR PULSE WIDTH PERIOD MEASUREMENT FUNCTION 1 Non overlap of input numbers The input terminals X000 X001 X003 and X004 can be used for high speed counter input interruption pulse catch speed detection SPD instructions and general purpose input Take care not to overlap the input numbers However overlap of input numbers is allowed for input interruptions 2 When the pul...

Страница 12: ...iring apply to the cases where C251 is used When another high speed counter number is used wire the counter referring to the following diagrams It is recommended to use shielded twisted pair cables for connection cables Ground the shield of each shielded cable only on the PLC side 1 NPN open collector transistor output rotary encoder 2 PNP open collector transistor output rotary encoder The ground...

Страница 13: ...ercurrent is shut down Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation Make sure that the rush current does not exceed the current corresponding to the maximum specified resistance load 2 Lamp load Lamp loads generally generate rush current 10 to 15 times the stationary current Make sure that the rush current does not exceed the current corres...

Страница 14: ... is at least 2 times larger than the total rated fuse capacity n CONTACT PROTECTION CIRCUIT FOR INDUCTIVE LOADS When an inductive load is connected connect a diode for commutation in parallel with the load as necessary The diode for commutation must comply with the following specifications Item Guide Reverse voltage 5 to 10 times of the load voltage Forward current Load current or more n INTERLOCK...

Страница 15: ... to their installed location POINT Considerations when installing USB driver If the USB driver cannot be installed confirm the following Windows settings If Block Never install unsigned driver software is selected under Control Panel System Hardware Driver Signing the USB driver may not be installed Select Ignore Install the software anyway and don t ask for my approval or Warn Prompt me each time...

Страница 16: ...on POINT Product ID is written on the License certificate included with the product Enter the 12 digit number divided into 3 and 9 digits n OPERATING ENVIRONMENT Item Contents Personal Com puter Windows supported personal computer CPU Intel Core 2 Duo Processor 2GHz or more recommended Required Memory 1GB or more recommended Available Hard Disk Capacity When installing GX Works2 HDD available capa...

Страница 17: ... a list of functions such as function blocks used for programming Output Display compilation and check results errors and warnings Cross Reference Display cross reference results Device List Display the device list Watch 1 to 4 A screen used for monitoring and changing current device values Intelligent Function Module Monitor 1 to 10 Screens used for monitoring intelligent function modules Find Re...

Страница 18: ...unit n FOR CONTINUOUS USE OF A PERIPHERAL DEVICE SUCH AS GOT Cut off the area shown in the left figure below of the peripheral device connector cover main unit using a nipper etc and connect the peripheral device as shown in the right figure below n CONNECTION TO BUILT IN PROGRAMMING CONNECTOR USB Connect and disconnect the communication cable for the peripheral device personal computer At connect...

Страница 19: ...d is given from the programming software after the PLC is started by either the built in RUN STOP switch or the general purpose input RUN terminal the PLC will be restored to the running status by giving the RUN command from the programming software This can also be accomplished by setting the built in RUN STOP switch or the general purpose input RUN terminal to STOP and then to RUN n OPERATION AN...

Страница 20: ...INTENANCE This PLC does not incorporate consumable parts that are factors in the reduction of service life However the output relays points of contact and batteries option have a limited life expectancy n PERIODIC INSPECTION BATTERY LIFE ETC 1 BATTERY Model FX3U 32BL battery Standard life 5 years at ambient temperature of 25 C 77 F 2 OTHER DEVICES When inspecting the battery check the following po...

Страница 21: ...ply power If ERR LED goes off a watchdog timer error may have occurred Take any of the following measures Review the program The maximum value D8012 of the scan time should not exceed the setting D8000 of the watchdog timer Check that the input used for input interruption or pulse catch is not being abnormally turned on and off in one scan Check that the frequency of the pulse duty of 50 input to ...

Страница 22: ...easures When input turns on Check that the input device does not have a built in diode or parallel resistance When input does not turn on Measure the voltage between the 0V terminal or 24V terminal not connected to the S S terminal and the input terminal with a tester to confirm that the voltage is 24VDC Check the configuration of the external wiring and connected devices and the connection of the...

Страница 23: ...FX3G INSTALLATION MANUAL 23 ...

Страница 24: ...orporate Woods Parkway Vernon Hills IL 60061 Phn 847 478 2100 us MitsubishiElectric com fa en Serving the Americas AZ JY997D33401 A Effective January 2016 Specifications subject to change without notice 2016 Mitsubishi Electric Automation Inc ...

Отзывы: