8.5
display by LED readout
(1) UNDER VOLTAGE
This alarm appears if voltage under 170V lasts for longer
than 15ms.
Cause
Checkup
Remedy
Tower supply
This alarm appears when speed
Increase capacity of
capacity
is changed or load is
input power supply.
insufficient
sive.
Interval
AC power supply should be
Prolong AC power
turning
turned on in minimum 1 sec.
ply off time.
off and on
after turned off.
AC power sup-
ply short
Card SFJ-CA1
It should be checked if this
Replace the card
not in good
alarm is reproducible.
condition
Replace the card SFJ-CA1 in
use with a new card SFJ-CA1
to check if the same alarm
occurs again.
Use the previous card
CA1 again to check if the
same alarm occurs again.
IM-PW power
After making sure this alarm
/Replace the IM-PW
unit not in
is reproducible, replace the
/power unit.
good
card SFJ-CA1 in use with
tion
a new card SFJ-CA1