238
-
'10 • SR-T-091
E39
Discharge pipe
temperature sensor anomaly
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
discharge pipe
temperature sensor
connector connected
properly?
YES
Are the
characteristics
of discharge pipe
temperature
sensor
OK?
NO
For the characteristics of discharge pipe
temperature sensor, see the following graph.
YES
140
120
100
80
60
40
20
0
0
100
50
[T 90
°C
]
NO
Temperature-resistance characteristics
Temperature sensor resistance (k
Ω
)
Temperature (°C)
(Broken wire)
(Shot circuit)
Correct connector.
Defective discharge pipe
temperature sensor
➞
Replace.
Defective outdoor
PCB
➞
Replace.
(Defective temperature
sensor input circuit)
2. Error detection method
Detection of anomalously low
temperature (resistance) on
the discharge pipe temperature
sensor
3. Condition of Error displayed
When the temperature sensor
detects -25 °C or lower for 5
seconds continuously within
10 minutes to 10 minutes 20
seconds after the compressor
ON, the compressor stops. After
3-minutes delay, the compressor
starts again automatically, but
if this anomalous temperature
is detected 3 times within 40
minutes.
4. Presumable cause
• Defective outdoor PCB
• Broken sensor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
Error code
Remote controller:
LED
Green
Red
Indoor
Content
Содержание SRK60ZJX-S
Страница 85: ... 84 10 SR T 091 4 Ceiling cassette 4way compact type FDTC ...
Страница 89: ... 88 10 SR T 091 a PJA012D783 ...
Страница 189: ... 188 10 SR T 091 09 SRK DB 087D Service data record form 182 ...
Страница 197: ... 196 10 SR T 091 09 SRK DB 087D 11 Outdoor unit inspection points 20ZJX S 25ZJX S 35ZJX S 198 198 189 ...
Страница 267: ... 266 10 SR T 091 12 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...
Страница 268: ... 267 10 SR T 091 ...