128
-
'10 • SR-T-091
(6) 3D auto operation
Control the flap and louver by 3D AUTO button on the wireless remote controller.
Air flow selection and air flow direction are automatically controlled, allowing the entire indoor to efficiently conditioned.
(a)
During Cooling and Heating (Including auto cooling and heating)
1)
Air flow selection is determined according to indoor temperature and setting temperature.
2)
Air flow direction is controlled according to the indoor temperature and setting temperature.
a) When 3D auto operation starts
b) When Indoor temp. – Setting temp. is
<=
5ºC during cooling and when Setting temp. – Indoor temp. is
<=
5ºC during
heating, the system switches to the following air flow direction control. After the louver swings left and right sym
-
metrically for 3 cycles, control is switched to the control in c).
c) After the flap swings for 5 cycles, control is switched to the control in d).
d) For 5 minutes, the following air flow direction control is carried out.
e) After 5 minutes have passed, the air flow direction is determined according to the indoor temperature and setting
temperature.
(b)
During DRY Operation (including auto DRY operation)
At cooling
Air flow selection
Operation mode
AUTO
HI
MED
LO
At heating
Indoor temp. – Setting temp. >5°C
Indoor temp. – Setting temp. 5°C
Setting temp. – Indoor temp. >5°C
Setting temp. – Indoor temp. 5°C
HIGH POWER
AUTO
HI
MED
LO
HIGH POWER
AUTO
<
=
<
=
Flap
Louver
Cooling
Up/down Swing
Heating
Wide (fixed)
Center (fixed)
Flap
Louver
Cooling
Heating
Left/right Swing
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Flap
Louver
Cooling
Up/down Swing
Heating
Center (Fixed)
Wide (Fixed)
Flap
Louver
Cooling
Heating
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Operation mode
Indoor temp. – Setting temp. 2°C
Setting temp. – Indoor temp. 2°C
At heating
At cooling
Air flow direction contorol
2°C < Setting temp. – Indoor temp. 5°C
2°C < Indoor temp. – Setting temp. 5°C
Indoor temp. – Setting temp. > 5°C
Setting temp. – Indoor temp. > 5°C
The control in 4) continues.
Control returns to the control in 2).
Control returns to the control in 1).
The control in 4) continues.
Control returns to the control in 2).
Control returns to the control in 1).
<
=
<
=
<
=
<
=
Wide (Fixed)
Flap
Air flow selection
Louver
According to DRY operation.
Horizontal blowing (Fixed)
Содержание SRK60ZJX-S
Страница 85: ... 84 10 SR T 091 4 Ceiling cassette 4way compact type FDTC ...
Страница 89: ... 88 10 SR T 091 a PJA012D783 ...
Страница 189: ... 188 10 SR T 091 09 SRK DB 087D Service data record form 182 ...
Страница 197: ... 196 10 SR T 091 09 SRK DB 087D 11 Outdoor unit inspection points 20ZJX S 25ZJX S 35ZJX S 198 198 189 ...
Страница 267: ... 266 10 SR T 091 12 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...
Страница 268: ... 267 10 SR T 091 ...