'10 • SR-T-091
A
RWB000Z053
Model
Item
SRF35ZJX-S
Indoor unit
SRF35ZJX-S
Outdoor unit
SRC35ZJX-S
Cooling capacity (1)
W
3500 (900 (Min.)~4100 (Max.))
Heating capacity (1)
W
4500 (900 (Min.)~5100 (Max.))
Power supply
1 Phase, 220~240 V, 50Hz
Operation
data (1)
Power
consumption
Cooling
kW
0.890 (0.19~1.26)
Heating
1.124 (0.23~1.43)
Running
current
Cooling
A
4.1 / 3.9 / 3.7 (220/ 230/ 240 V)
Heating
5.2 / 4.9 / 4.7 (220/ 230/ 240 V)
Inrush current
5.2 / 4.9 / 4.7 (220/ 230/ 240 V)
COP
Cooling
3.93
Heating
4.00
Noise
level
Cooling
Sound level
dB(A)
Hi : 41 Me : 34 Lo : 28
50
Power level
dB
52
63
Heating
Sound level
dB(A)
Hi : 41 Me : 36 Lo : 31
50
Power level
dB
52
62
Exterior dimensions (Height x Width x Depth)
mm
600 x 860 x 238
595 x 780 x 290
Exterior appearance
( Munsell color )
Fine snow
( 8.0Y 9.3/0.1 ) near equivalent
Stucco white
( 4.2Y 7.5/1.1 ) near equivalent
Net weight
kg
19
38
Refrigerant
equipment
Compressor type & Q'ty
—
RM-B5077MDE1 (Rotary type) x 1
Motor (Starting method)
kW
—
0.90 (Line starting)
Refrigerant oil
0.35 (DIAMOND FREEZE MA68)
Refrigerant (3)
kg
R410A 1.2 (Pre-Charged up to the piping length of 15m)
Heat exchanger
Louver fins & inner grooved tubing
M fins & inner grooved tubing
Refrigerant control
Capillary tubes + Electronic expansion valve
Deice control
Microcomputer control
Air handling
equipment
Fan type & Q'ty
Turbo fan x 1
Propeller fan x 1
Motor
W
40
24
Air flow
Cooling
CMM
Hi : 9.2 Me : 7.8 Lo : 6.4
32.5
Heating
Hi : 10.7 Me : 8.3 Lo : 7.4
29.5
Fresh air intake
Impossible
—
Air filter, Quality / Quantity
Polypropylene net (washable) x 1
—
Shock & vibration absorber
—
Cushion rubber (for compressor)
Electric heater
—
—
Operation
control
Operation switch
Wireless-Remote control
—
Room temperature control
Microcomputer thermostat
—
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
AIR OUTLET SELECTION : Green, ECONO : Green
Safety devices
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection (High pressure control), Cooling overload protection
Installation
data
Refrigerant piping size (O.D)
mm
Liquid line :
φ
6.35 (1/4") Gas line :
φ
9.52 (3/8")
Connecting method
Flare connecting
Attached length of piping
m
—
—
Insulation for piping
Necessary (Both sides), independent
Refrigerant line (one way) length
m
Max. 15
Vertical height difference between
outdoor unit and indoor unit
Max. 10 (Outdoor unit is higher)
Max.10 (Outdoor unit is lower)
Drain hose
Connectable (VP16)
—
Power cable
—
Recommended breaker size
A
16
Connection wiring
Size x Core number
1.5mm
2
x 4 cores (Including earth cable)
Connecting method
Terminal block (Screw fixing type)
Accessories (included)
Mounting kit, Clean filter (Natural enzyme filter x 1, Photocatalytic washable deodorizing filter x 1)
Optional parts
Interface kit (SC-BIKN-E)
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1, JIS C 9612
Heating
20˚C
—
7˚C
6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) The operation data are applied to the 220/230/240V districts respectively.
(4) The refrigerant quantity to be charged includes the refrigerant in 15m connecting piping.
(Purging is not required even for the short piping.)
The pipe length is 7.5m.
Adapted to
RoHS
directive
Содержание SRK60ZJX-S
Страница 85: ... 84 10 SR T 091 4 Ceiling cassette 4way compact type FDTC ...
Страница 89: ... 88 10 SR T 091 a PJA012D783 ...
Страница 189: ... 188 10 SR T 091 09 SRK DB 087D Service data record form 182 ...
Страница 197: ... 196 10 SR T 091 09 SRK DB 087D 11 Outdoor unit inspection points 20ZJX S 25ZJX S 35ZJX S 198 198 189 ...
Страница 267: ... 266 10 SR T 091 12 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...
Страница 268: ... 267 10 SR T 091 ...