190
-
'10 • SR-T-091
'09•SRK-DB-087D
Current cut
Compressor lock, Compressor wiring short circuit, Compressor output is open phase,
Outdoor PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
*
*
Current safe stop
Overload operation, compressor
lock, overcharge
198
195
SRC20 ~ 35 : 1.703Ω (U-V, V-W, U-W) or more at 20ºC
SRC50ZJ-S : 1.417Ω (U-V), 1.392Ω (V-W), 1.435Ω (U-W) or more at 20ºC
SRC50, 60ZIX-S : 0.953Ω (U-V, V-W, U-W) or more at 20ºC
'09•SRK-DB-087D
Over heat of compressor
Gas shortage, defective discharge
pipe sensor
Error of signal transmission
Wiring error including power cable, defective indoor/
outdoor PCB
② ③
② ③
① ②
189)