219
-
'10 • SR-T-091
INSPECT I/U
INSPECT I/U
(When 1 or 2 remote controllers are connected)
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Are 2 units
of remote controller
connected?
Is it set
at the slave remote
controller?
⑴,
⑵
Note (1) Use SW1 to set at
master or slave.
Note (2)
“Slave” is displayed
on the remote
controller LCD.
⑵
Does it
become normal?
Do more than
one indoor units have the
same address?
Are remote
controller wires laid
along high voltage
wires?
Does DM
start 60 seconds later
automatically.
Disconnect the connecting
wire
�
between the indoor
and outdoor unit.
Power supply reset
NO
YES
YES
NO
NO
NO
NO
NO
YES
YES
YES
Set one remote controller
for “Master” and the other
for “Slave”
Set SW1 on remote
controller PCB at “Master”.
Set address again. (SW2 on
indoor control PCB)
Separate remote controller
wires from high voltage
wires.
Defective indoor control
PCB
➞
Replace.
Defective remote controller
➞
Change.
2. Error detection method
Communication between indoor
unit and remote controller
is disabled for more than 30
minutes after the power on.
3. Condition of Error displayed
Same as above
4. Presumable cause
• Improper setting
• Surrounding environment
• Defective remote controller
communication circuit
• Faulty indoor control PCB
Note:
If any error is detected 30 minutes after displaying “
WAIT
” on the remote controller, the display changes to
“INSPECT I/U”.
Error code
Remote controller:
LED
Green
Red
Indoor
Content
Содержание SRK60ZJX-S
Страница 85: ... 84 10 SR T 091 4 Ceiling cassette 4way compact type FDTC ...
Страница 89: ... 88 10 SR T 091 a PJA012D783 ...
Страница 189: ... 188 10 SR T 091 09 SRK DB 087D Service data record form 182 ...
Страница 197: ... 196 10 SR T 091 09 SRK DB 087D 11 Outdoor unit inspection points 20ZJX S 25ZJX S 35ZJX S 198 198 189 ...
Страница 267: ... 266 10 SR T 091 12 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...