'10 • SR-T-091
E60
Compressor rotor lock error
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
power supply voltage
OK?
NO
Reset the power supply and restart operation.
YES
Does the compressor start?
Does E59 occur?
NO
YES
Does it
start up normally without
recurrence of
E60.
YES
NO
Does the
compressor run without
occurrence of
E42?
NO
YES
Is the noise
or vibration of compressor
normal?
Is the
output from inverter
checker OK?
YES
YES
NO
NO
NO
Check and correct the
power supply voltage
Correct it based on the
troubleshooting of E59
Correct it based on the
troubleshooting of E42
Defective outdoor
PCB
➞
Replace.
Replace compressor.
Check compressor for
insulation, resistance.
Replace compressor if
necessary.
Defective outdoor PCB
➞
Replace.
2. Error detection method
Compressor rotor position
3. Condition of Error displayed
If it fails again to detect the
rotor position after shifting to
the compressor rotor position
detection operation, the
compressor stops.
4. Presumable cause
• Defective outdoor fan motor
• Defective outdoor PCB
• Anomalous power supply
voltage
• Improper refrigerant amount
and refrigerant circuit
• Defective compressor (motor,
bearing)
Note: Insulation resistance
• The unit is left for long period without power supply or soon after installation, migrated liquid refrigerant may dissolve in the refrigerant oil in the compressor.
In such case insulation resistance decreases upto several M
Ω
or lower. If the electric leakage breaker is activated due to low insulation resistance, check followings.
➀
Check whehter the insulation resistance can recover or not, ater 6 hours has passed since power ON.
(By energize the crankcase heater, migrated liquid refrigerant in the refrigerant oil in compressor can be evaporated)
➁
Check whether the electric leakage breake conforms to high-hermonic specifications
(As units has inverter, in order to prevent from improper operation, be sure to use high-hermonic one.)
Error code
Remote controller:
LED
Green
Red
Content
Indoor Keeps flashing Stays OFF
Содержание SRK60ZJX-S
Страница 85: ... 84 10 SR T 091 4 Ceiling cassette 4way compact type FDTC ...
Страница 89: ... 88 10 SR T 091 a PJA012D783 ...
Страница 189: ... 188 10 SR T 091 09 SRK DB 087D Service data record form 182 ...
Страница 197: ... 196 10 SR T 091 09 SRK DB 087D 11 Outdoor unit inspection points 20ZJX S 25ZJX S 35ZJX S 198 198 189 ...
Страница 267: ... 266 10 SR T 091 12 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control ...
Страница 268: ... 267 10 SR T 091 ...