−9−

−8−

 

6 . Power on and initial setting

Set the main and sub R/C units according to the display at the power on.

 Main/Sub setting not performed => (1)

 Main/Sub setting performed 

=> (2)

 

When the main and sub are not yet set,

 

①⇒②

 Main/sub input screen is displayed.

 When tapping the               or               button, initial setting starts. 
If any wrong button has been tapped by mistake, the setting can be changed after the end of the initializing operation. (10.  R/C function 
setting

)

 When using two eco touch remote controllers for one IU or one group, if the first one is set for the              , the second is set for the 
              automatically.

Main

Sub

Main

Sub

Caution

When only one unit of R/C is 
used, tap the               button.
In the state of initial setting, if 
either one of buttons ([Main]/[Sub]) 
is not tapped, it keeps the screen 
unchanged.

Main

 

 

        The screen changes to 

③⇒④⇒⑤

.

 

 

        The screen changes to 

①⇒⑧⇒⑤

.

Main

Sub

Start screen

Version :
Program ID :

Main/sub set input

Select main or sub remote control.

Main

Sub

The red LED will blink 
if communication is not 
established in ten minutes.

TOP screen

Menu

Direction

Cooling

16

14 (Mon)

F1: High power

F2: Energy-saving

Timer

Now stopping.

Set temp

IU search on

Searching IU

IU info acquisition on

Loading IU settings.

Will finish 1230 seconds later.

(2)

 When the main and sub are set

Yes

  

The screen changes to 

⑧⇒⑤

.

No

  

The screen changes to 

.

If the screen is not tapped for more than 15 
seconds, the  Yes  (Continue) is selected 

and the display changes to the screen of 

.

Initialize set on

R/C is initializing.

Set continue acknowledge

Do you want to save up the previous

settings of R/C before power ON?

Yes

No

Yes

  

The screen changes to 

①⇒②

.

No

  

The screen changes to 

.

After the initializing, it returns to the default 
state.

Yes

  

The screen changes to 

①⇒②

.

No

  

The screen changes to 

.

After the initializing, it returns to the default 
state.

Initialize acknowledge

Do you want to restore default

R/C setting?

Yes

No

Содержание eco touch RC-EXC3

Страница 1: ...文 Quick reference ENGLISH eco touch 触摸线控器 RC EXC3 使用向 手册 PJZ012A133 201612 感谢您使用eco touch触摸线控器 本用户说明记载了安全注意事项 为了正确使用请在使用前务必详细阅读该说明 阅读完毕后 请将本手册置于可以随时取阅的地方 方便使用人查阅 使用人变更时请将本说明一并交接给新使用人 请客户不要自行安装 重装设备 将无法保证安全和使用功能 A ...

Страница 2: ......

Страница 3: ...an one remote control are used 8 6 Power on and initial setting 9 7 Menu items 10 8 Installation settings and test run 11 9 R C function settings 13 10 IU settings 15 11 Service Maintenance 18 For the operation part of this Quick reference refer to page 20 Refer to the Installation manual on the following web site for details http www mhi mth co jp en products detail air conditioner_users_manual h...

Страница 4: ...e it could result in electric shocks break down or malfunction Do not modify the unit It could cause electric shocks fire or break down Be sure to turn OFF the power circuit breaker before repairing inspecting the unit Repairing inspecting the unit with the power circuit breaker turned ON could cause electric shocks or injury Please read this manual carefully before starting installation work to i...

Страница 5: ...shocks fire or break down Use the specified cables for wiring and connect them securely with care to protect electronic parts from external forces Improper connections or fixing could cause heat generation fire etc Seal the inlet hole for remote control cable with putty If dew water insect etc enters through the hole it could cause electric shocks fire or break down If dew or water enters the unit ...

Страница 6: ...rature may not be detected using the temperature sensor of the remote controller Where the average room temperature cannot be detected Place near the equipment to generate heat Place affected by outside air in opening closing the door Place exposed to direct sunlight or wind from air conditioner Where the difference between wall and room temperature is large 4 When you are using the automatic gril...

Страница 7: ...the R C case is 0 5 mm2 Connect them to wires of larger size near the outside of R C When wires are connected take measures to prevent water etc from entering inside 200 m 0 5 mm2 x 2 core 300m 0 75 mm2 x 2 core 400m 1 25 mm2 x 2 core 600m 2 0 mm2 x 2 core Secure the installation space shown in the figure For the installation method embedding wiring or exposing wiring can be selected For the wirin...

Страница 8: ...wed from front 37 23 23 固定穴 18 3 83 5 120 19 120 37 23 23 19 120 Fixing holes 83 5 120 18 3 PCB side Viewed from rear 8 50 200 壁 電線管 ロ ッ クナッ ト スイ ッ チ ボ ッ クス パテで シール する こ と リ モコ ン配線 下ケース配線穴 ブッ シング センサー USB 端子 Wall Conduit Sensor USB port Terminal block Locknut Bushing Switch box Seal with putty R C cable When wires are passed through the bottom case fix the bottom case at 2 places on the switch box...

Страница 9: ... not to pinch the sheath Tighten by hand 0 7 N m or less the wire connection If the wire is connected using an electric driver it may cause failure or deformation In case of exposing wiring When the wiring is taken out from the upper center or upper left of R C Cut out the thin wall sections on the cases for the size of wire Fix the bottom R C case on a flat surface with two wood screws In case of...

Страница 10: ...lation setting Auto restart Auto temp setting Auto fan speed IU settings Service Maintenance IU address Next service date Operation data Error display Error history Display erase anomaly data Reset periodical check Saving IU settings Special settings Erase IU address CPU reset Restore of default setting Touch panel calibration Indoor unit capacity display Indoor unit R C Main R C Sub R C cable No ...

Страница 11: ...Main Sub Start screen Version Program ID Main sub set input Select main or sub remote control Main Sub The red LED will blink if communication is not established in ten minutes TOP screen Menu Direction Cooling 16 14 Mon F1 High power F2 Energy saving Timer Now stopping Set temp IU search on Searching IU IU info acquisition on Loading IU settings Will finish 1230 seconds later 2 When the main and ...

Страница 12: ...al External input 2 Refer to Installation manual External input 2 signal Refer to Installation manual Heating thermo OFF temp adjustment 15 Return temperature adjustment 15 Fan control in cooling thermo OFF 15 Fan control in heating thermo OFF 16 Anti frost temp Refer to Installation manual Anti frost control Refer to Installation manual Drain pump operation 16 Keep fan operating after cooling is ...

Страница 13: ...ion Company information 5 6 Company information Company Phone No Back Select the item Enter the company name using up to 26 one byte characters and then tap the Set button You can enter alphanumeric Japanese Kana Kanji Cyrillic or Chinese characters Enter the Company Company Back Set 漢字 Number Alphabet カナ Next Delete Input the name tap Set 汉字 TOP screen Menu Service setting Installation settings S...

Страница 14: ...rared sensor control power saving and auto off will not be performed The infrared motion sensor cannot be enabled for the indoor unit older than FDT VG or FDT KX ZE1 When the infrared motion sensor setting is tapped Invalid request will be displayed In IU rotation function the timer to changeover the operation of 2 indoor units is set The timer can be set within the range of 10 to 990 hours in inc...

Страница 15: ...unction settings Service password R C function settings menu 3 R C function settings Ventilation setting Auto restart Auto temp setting Back Select the item Previous Auto fan speed 16 18 19 17 You can change IU main unit return air temperature sensor to the R C side Disable The Indoor temp display changes to the temperature measured by the sensor at the main unit Enable The Indoor temp display cha...

Страница 16: ...y after operating the R C switch Left right flap control Left right flap control Back Select the item Fixed position stop Stop at any position If the unit stops during operation Enable It returns to the state before the power failure as soon as the power supply is restored After the end of the primary control at the power on Disable It stops after the restoration of power supply Auto restart Auto ...

Страница 17: ...ontrol pressure adjust Auto operation mode Thermo rule setting Next Back Select the item Previous 18 19 23 21 20 TOP screen Menu Service setting IU settings Service password IU setting menu 5 IU setting menu 5 IU settings Auto fan speed control IU overload alarm External output setting Back Select the item Previous 25 26 IU select 2 IU select Menu Back Select an IU address All units Previous Stand...

Страница 18: ...n operating after cooling is stopped Keep fan operating after cooling is stopped No setting Setting 1 Setting 2 Setting 3 Back Select the item Keep fan operating after heating is stopped Keep fan operating after heating is stopped No setting Setting 1 Setting 2 Setting 3 Back Select the item Select the fan control after the residual fan operation following stop and thermo OFF in heating mode Stop ...

Страница 19: ...ap is changed in the range of Powerful high High Medium Low Set the room temperature control thermostat ON OFF switching method and condition Standard The thermostat judges based on the indoor temperature and set temperature Outdoor temp basis The thermostat judges based on the outdoor temperature and the cooling and heating offset values The room temperature setting will be disabled Standard Outd...

Страница 20: ... Next service date Next service date Back Set the date Set No setting yy mm dd Service message Usage time 1 years 9 months Next check 10 2020 Company Phone No TOP screen Menu Service setting Service Maintenance Service password Service Maintenance 1 Service Maintenance IU address Next service date Operation data Error display Saving IU settings 次ペー ジ Back Select the item 3 5 9 14 7 Next Service Ma...

Страница 21: ... data The IU setting data saved in the R C are transferred to an indoor unit Reset periodical check Reset periodical check Back Yes If yes tap Yes Do you want to reset the periodical check Saving IU settings Back Save IU settings Automatic saving Transfer the saved data Saving IU settings Select the item Erase IU address Memory of the IU address for multi KX unit is erased CPU reset Microcomputers...

Страница 22: ...5 4 Menu operations 28 5 Settings and operations 29 Energy saving setting 29 Grille Up and Down 32 Individual flap control 34 Anti draft setting 35 Ventilation operation 35 Initial settings 36 Timer 38 Weekly timer 40 Registering favorite setting 41 Favorite setting operation 42 Silent mode control 42 Select the language 42 6 Maintenance and After sale service 43 Filter sign reset 43 Maintenance o...

Страница 23: ...mented only by qualified specialists WARNING Consult your dealer or a professional contractor to install the unit Improper installation made on your own may cause electric shocks fire or dropping of the unit Consult your dealer when moving disassembling or repairing the unit Never modify the unit Improper handling may result in injury electric shocks fire etc Avoid using combustible substances hair...

Страница 24: ... by yourself It could destruct the environment Ask your dealer when it is necessary to dispose the remote control Note The remote control should not be installed where it is exposed to direct sunlight or the ambient temperatures become higher than 40 C or lower than 0 C It could cause deformation discoloration or break down Do not use benzene paint thinner wipes etc to clean the remote control It ...

Страница 25: ... is displayed when one of following settings is going on When the demand control is effective When setting is made from the sub R C When the central control Optional is running When Operation for Grille Up Down is enabled During the ventilation operation When filter sign is up When the Permission Prohibition setting is made When the peak cut timer is set When the weekly timer is set When the perio...

Страница 26: ...ed sensor motion sensor control 31 Filter sign reset 43 Grille Up Down 32 Initial settings 36 Clock setting 36 Date time display 36 Summer time 36 Contrast 37 Backlight 37 Controller sound 37 Operation lamp luminance 37 Administrator settings Refer to user s manual Permission Prohibition setting Refer to user s manual Outdoor unit silent mode timer Refer to user s manual Setting temp range Refer t...

Страница 27: ...lid request may be displayed when a button is pushed This is not a fault but it is because the button operation is set to the Disable The unit starts to operate initially with the following settings after the power on These settings can be changed as desired Central control OFF Operation mode With auto mode Auto cooling Without auto mode Cooling Set temp 23 0 C Fan speed 3 speed Flap direction Whe...

Страница 28: ... or SC SL4 Also note that 3D auto flow operation will not be disabled when you change the flap direction from the SC SL2 SC SL3 or SC SL4 during a 3D auto flow operation 1 Tap the Change flap direction button on the TOP screen When an FDK with a left right flap is not connected 2 When one or more FDKs with a left right flap are connected 3 Change flap direction Ind flap Control Auto swing Back Out...

Страница 29: ...ower is displayed on the R C screen and C is displayed on the Set temp button during the high power operation Set temp and change fan speed operations are disabled during high power operation 2 High power operation is terminated when you perform one of the following When you terminate through a Run Stop operation When you change the operation mode When15 minutes have elapsed since the high power o...

Страница 30: ...he Next button is tapped next main menu screen is displayed 3 When the Back button is tapped the display returns to the TOP screen 4 When the Set button is displayed on the setting screen for each item tapping this button confirms the setting If you tap Back without tapping the Set button the settings made will not be applied and the display returns to the original screen Menu Direction Cooling 16...

Страница 31: ...em Sleep timer Peak cut timer Automatic temp set back Infrared sensor control Energy saving setting Administrator password Sleep timer Stops operation when the amount of time set has elapsed since the start of each operation 1 Tap the Menu button on the TOP screen and select Energy saving setting Sleep timer The Sleep timer screen is displayed 2 Select a desired time with buttons Setting range 30 ...

Страница 32: ... End time AM Peak cut timer Set Back State Disable Select the item Mon No 1 Change Start time End time 1 3 7 00 AM 8 00 AM 2 Select a line tap Change Change Mon Peak cut timer State Enable Disable Disable Disable Start time End time Enter Back 2 1 7 00 PM 7 00 AM 8 00 PM 8 00 AM 9 Set the peak cut Set the peak cut with the buttons The peak cut can be set at 0 40 60 or 80 The lower the peak cut is ...

Страница 33: ...n and contents of the current settings are displayed Enable disable power control Enable disable auto off After you set each item tap the Set button The display returns to the Energy saving setting menu screen When auto off is enabled The unit will enter the Operation wait state when an hour has elapsed since the last time a human presence was detected and will be in Complete stop state after anot...

Страница 34: ...s not indicate a failure this message is displayed because the automatic grille up and down panel is not used If you press the Run Stop switch in the middle of an operation the Grille Up and Down mode will terminate and the display returns to the original display Advice CAUTION Before you perform any operation make sure that the suction grille motion range is free of persons and objects Contact wi...

Страница 35: ...n descending motion and you operate the unit from another R C set as main sub or from an option such as the central console the unit will start operation R C display will remain the same During heating operation selecting Grille Up and Down may cause the IU fan to continue rotating for approximately 40 seconds Length Back Set descending length with button Set When the R C is set as the sub R C IU ...

Страница 36: ...he upper lower flap 4 When you select the left right flap 8 4 Select one of the upper limit positions from 1 to 6 for the flap motion range After you select the range tap the Set button Individual flap control Select flap Bat set Back Flap is in operation Individual flap control Select flap Back Flap Swing range Back Select the upper limit No tap Set Set Upper limit setting 配管側 ドレンホース側 制 御 箱 ルーバ F...

Страница 37: ...lect the blow outlet number to set anti draft The flap at blow outlet No will keep moving while the blow outlet selection screen is displayed Select the flap based on this figure When you have selected the blow outlet the flap with the number you selected will move The figure displayed on the screen shows the installed unit viewed from the floor side You can set all blow outlets at once by tapping...

Страница 38: ... the hour minute with the buttons on the clock setting screen Tap the Set button after the setting To change dd mm yy tap the Date button Clock setting Date Back Set the time Set PM 1 Tap the Menu button on the TOP screen and select User setting Initial settings Date time display 2 The Clock setting screen is displayed Tap OFF ON for the Date and time Tap OFF ON for A day of the week Tap Display m...

Страница 39: ...ns for the backlight lighting and the lighting Period 5 90 sec at 5 sec intervals ON The Backlight lights when the LCD is tapped If no operation is made for the set time it turns off automatically OFF The backlight does not light even if the LCD is tapped Backlight You can turn ON OFF the backlight and set the lighting period 1 Tap the Menu button on the TOP screen and select User setting Initial ...

Страница 40: ...N Clock Weekly If a prohibited combination setting is made a message The combination can t be accepted is displayed for 3 seconds Priority order of the timer settings is as follows Set OFF timer by hour clock weekly OFF timer Sleep timer Set ON timer by hour clock weekly ON timer On the TOP screen the timer is displayed from the earliest one out of OFF time of the sleep timer ON time and OFF time ...

Страница 41: ...et A C will stop at the set hours later Cancel Set ON timer by clock Starts the operation of the unit at the set clock time 1 Tap the Menu button on the TOP screen and select Useful functions Timer Set ON timer by clock 2 The Set OFF timer by hour setting screen is displayed Select a desired time to start operation 5 min intervals with the buttons 3 When operating conditions at the start of operat...

Страница 42: ...ay are displayed 5 4 For the holiday setting tap the block under the day to switch between the holiday setting and Blank reset Timer does not operate on the day set as holiday Two or more holidays can be set To enable the timer on the day set as holiday it is necessary to reset the holiday setting When tapping All Disable button the timer does not operate on all days of the week When the timer is ...

Страница 43: ...etting and move to a day of the week selection screen 3 13 Display the group setting acknowledge screen Tap the Yes button and save the setting The display changes to a day of the week setting check screen after saving 3 When making the setting after changing a day of the week repeat the setting from the step 3 Weekly timer No setting Back Select the fan speed Auto Weekly timer Yes Back Do you wan...

Страница 44: ...g silent mode control Outdoor unit silent mode control ON will be displayed on the message display 3 When you press the F1 F2 switch during silent mode control the display changes to the administrator password input screen After you enter the password the silent mode control will terminate Silent mode control will not be disabled even if you press the Run Stop switch Terminate the control with the...

Страница 45: ...screen for the Filter sign reset screen is displayed Tap the Yes button If you do not want to reset tap the Back button Filter sign reset Reset Back Select the item Setting next cleaning date Filter sign reset Do you want to reset the filter sign Back Select the item Yes 4 The Setting next cleaning date screen is displayed Select a desired date with the buttons and tap the Set button The message o...

Страница 46: ...r sale service Normal display Error display Back Menu Select the item Back Next Contact Error display Code E07 E08 E09 E40 R C Normal IU 000 IU000 001 IU001 002 IU002 003 IU003 OU 00 Select the item Contact company Back Company MHI Phone No 000 000 0000 F1 High power Timer Cooling 6 57PM Wed Set temp Menu Direction Prot stp ON E09 Touch here for contact History can be checked from Menu F2 Energy s...

Страница 47: ......

Страница 48: ...INDUSTRIES THERMAL SYSTEM LTD 三菱重工业 上海 有限公司 16 5 Konan 2 chome Minato ku Tokyo 108 8215 Japan http www mhi mth co jp 中国上海市延安西路2299号 上海世贸商城2903 2906室 邮编 200336 Tel 86 21 6236 3030 Fax 86 21 6236 0502 http www mhi ac com ...

Отзывы: