82
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Discharge superheat on error
occurring
SHd
32 to 360
Cooling = TH4−TH6
Heating = TH4−TH5
32 to 360 [0 to 182˚C]
(When the temperature is 100˚F or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 150˚F;
0.5 s 0.5 s 2 s
50
1
˚F
[
:
]
1
ON
2 3 4 5 6
Sub cool on error occurring. SC
32 to 266
Cooling = TH6-TH3
Heating = TH5-TH2
32 to 266 [0 to 130˚C]
(When the temperature is 100˚F or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 115˚F;
0.5 s 0.5 s 2 s
15
1
˚F
[
:
]
1
ON
2 3 4 5 6
Thermostat-on time until error
stops
0 to 999
0 to 999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 s 0.5 s 2 s
15
4
Minute
1
ON
2 3 4 5 6
Pipe temperature/Suction (TH32)
−58 to 194
−58 to194 [−50 to 90
:
]
(When the coil thermistor detects 0˚F or below, “–”
and temperature are displayed by turns.)
(Example) When -10˚F;
0.5 s 0.5 s 2 s
10
˚F
[
:
]
1
ON
2 3 4 5 6
Indoor pipe temperature/Liquid
(TH2 (3))
Indoor 3
−38 to 190
−38 to 190 [−39 to 88°C]
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
˚F
[
:
]
1
ON
2 3 4 5 6
Indoor pipe temperature/Cond./
Eva. (TH5 (3)) Indoor 3
−38 to 190
−38 to 190 [−39 to 88°C]
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
When there is no indoor unit, “00” is displayed.
˚F
[
:
]
1
ON
2 3 4 5 6
Indoor pipe temperature/Liquid
(TH2 (4)) Indoor 4
−38 to 190
−38 to 190 [−39 to 88°C]
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
˚F
[
:
]
OCH636A