MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER
Details on the operation data including each thermistor temperature and error history can be confirmed with the remote controller.
F1
F2
F3
F4
Check menu
Cursor
Service menu:
Error history
Refrigerant volume check
Refrigerant leak check
Smooth maintenance
Request code
Select "Request code" with the F1 or F2 button, and press the
button.
Select "Check" with the F1 or F2 button, and press the
button.
2
Set the Refrigerant address and Request code.
Select the item to be changed with the F1 or F2 button.
Select the required setting with the F3 or F4 button.
■<Ref.address>setting [ 0 ] – [ 15 ]
■<Request code>setting
Press the
button, Data will be collected and displayed.
F1
F2
F3
F4
Request code
Request:
Request:
Request code
Ref.address
Request code
Cursor
− +
Ref.address
Request code
Cursor
− +
Request code: 004
Discharge temperature: 69˚C
1
Select "Service" from the Main menu, and press the
button.
13-1. HOW TO "MONITOR THE OPERATION DATA"
13-1-1. PAR-3xMAA ("x" represents 0 or later)
OCH636A