57
Notes
· High voltage is applied to the connecter (CNF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNF1, 2) for the motor with the power supply on.
(It causes trouble of the outdoor controller circuit
board and fan motor.)
Self check
Symptom : The outdoor fan cannot rotate.
1
2
Power supply check(Remove the connector (CNF1, 2))
Measure the voltage in the outdoor controller circuit
board.
TEST POINT
1
: V
DC
(between 1 (+) and 4 (
−
) of the fan connector): V
DC
280–340 V DC (When PFC stops), 380 V DC (When PFC is operating)
TEST POINT
2
: V
CC
(between 5 (+) and 4 (
−
) of the fan connector): V
CC
15 V DC
No
No
No
Wiring contact check
Contact of fan motor connector (CNF1, 2)
Fuse check
Check F5 on outdoor
controller board.
Recover wiring.
Replace the outdoor controller circuit board.
Replace the fan motor.
Replace the outdoor controller circuit board (C.B)
and fan motor (MF1, 2).
Replace the outdoor
controller circuit board.
Replace the fan motor.
Is the voltage normal?
Is there contact failure?
Yes
Yes
No
Did the F5 open?
No
Yes
Check the operation of fan.
END
Yes
OK
Check the operation.
END
OK
FAN MOTOR (MF1)
Inverter
driver
Ground
<- power supply (inverter drive)
<- power supply (gate drive)
-> rotation signal
<- control voltage
7
6
5
4
-
-
1
3
-
1
CNF1
CNDC
F5
15 V DC
0-6.5 V DC
0-15 V DC pulse
C5E
Motor
TESTS POINT
①
V
A36/A42 only
DC
TESTS POINT
②
Vcc
CHECK POINT
+
280-380 V DC
TESTS POINT
③
Vsp
PC5D
C5B
TESTS POINT
④
V
FG
C5D
TESTS POINT
③
Vsp
TESTS POINT
④
V
FG
TESTS POINT
②
Vcc
CHECK POINT
FAN MOTOR (MF2)
Inverter
driver
Ground
<- power supply (inverter drive)
<- power supply (gate drive)
-> rotation signal
<- control voltage
7
6
5
4
-
-
1
CNF2
0-6.5 V DC
0-15 V DC pulse
Motor
TESTS POINT
①
V
DC
TESTS POINT
③
Vsp
PC5C
C5A
TESTS POINT
④
V
FG
TESTS POINT
③
Vsp
TESTS POINT
④
V
FG
TESTS POINT
②
Vcc
CHECK POINT
3
-
1
CNDC
Outdoor controller circuit board
Power circuit board
· The inverter control P.C. board is built in the fan motor of this outdoor unit.
· When F5 that is on controller board is opened, change the fan motor and outdoor controller board at the same time (F5 is
impossible to change).
· It is abnormal when the abnormality is detected from either both fan motors or only one side.
10-6-5. Check method of DC fan motor (fan motor/outdoor controller circuit board)
OCH636A