Outdoor power circuit board
PUZ-A36NKA7
PUZ-A42NKA7
PUZ-A36NKA7-BS
PUZ-A42NKA7-BS
PUY-A36NKA7
PUY-A42NKA7
PUY-A36NKA7-BS
PUY-A42NKA7-BS
CN6
Thermistor
CN4
Connect to the outdoor
controller circuit board
(CN4)
NI, LI
Voltage of 230 V AC is input
(Connected to the terminal block
(TB1))
EI,E2,E3,E4
Connected to
the ground
CNDC
280–380 V DC (
1
+,
3
–
)
connect to the outdoor
controller circuit board
(CNDC)
TB1A, TB2A, TB3A, TB1B,
TB2B, TB3B
Connected to DCL
CNAC1, CNAC2
230 V AC
Connected to the outdoor
controller circuit board
(CNAC)
CN2
Connect to the outdoor controller circuit board (CN2)
1
–
5
: Transmitting signal to outdoor controller
circuit board (0–5 V DC)
2
–
5
: Zero cross signal
(0–5 V DC)
3
,
4
: 16 V DC
6
–
5
: 16 V DC
7
–
5
: 16 V DC
P3
U
V
W
N3
P2
L1
L2
L3
N2
S
R
P1
N1
Brief Check of POWER MODULE
Usually, they are in a state of being short-circuited if they are broken.
Measure the resistance in the following points (connectors, etc.). If they are short-
circuited, it means that they are broken.
1. Check POWER MODULE
1
Check of DIODE circuit
R – P1 S – P1 R – N1 S – N1
2
Check of IGBT circuit
P2 – L1 P2 – L2 P2 –
L3
N2 – L1 N2 – L2 N2 –
L3
3
Check of INVERTER circuit
P3
–
U , P3
–
V , P3
–
W , N3
–
U , N3
–
V , N3
–
W
Note: The marks
R
,
S
,
L1
,
L2
, L3 ,
P1
,
N1
, U , V and W
show in the diagram are not actually printed on the board.
OCH636A