4
Unit
Electronic weighing scale
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) If moisture or foreign matter might have entered the refrigerant piping during service, ensure to remove them.
[2] Additional refrigerant charge
When charging directly from cylinder
(1) Check that cylinder for R410A on the market is a syphon type.
(2) Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
No.
Tool name
Specifications
1
Gauge manifold
· Only for R410A
· Use the existing fitting specifications.
· Use high-tension side pressure of 768.7 PSIG [5.3 MPa.G] or over.
2
Charge hose
· Only for R410A
· Use pressure performance of 738.2 PSIG [5.09 MPa.G] or over.
3
Electronic weighing scale
—
4
Gas leak detector
· Use the detector for R134a, R407C or R410A
5
Adaptor for reverse flow check
· Attach on vacuum pump.
6
Refrigerant charge base
—
7
Refrigerant cylinder
· Only for R410A ·Top of cylinder (Pink)
· Cylinder with syphon
8
Refrigerant recovery equipment
—
Although "-BS" model has been designed to be resistant to salt damage, observe the following precautions to maintain the
performance of the unit.
(1) Avoid installing the unit in a location where it will be exposed directly to seawater or sea breeze.
(2) If the cover panel may become covered with salt, be sure to install the unit in a location where the salt will be washed away
by rainwater. (If a sunshade is installed, rainwater may not clean the panel.)
(3) To ensure that water does not collect in the base of the outdoor unit, make sure that the base is level, not at angle. Water
collecting in the base of the outdoor unit could cause rust.
(4) If the unit is installed in a coastal area, clean the unit with water regularly to remove any salt build-up.
(5) If the unit is damaged during installation or maintenance, be sure to repair it.
(6) Be sure to check the condition of the unit regularly.
(7) Be sure to install the unit in a location with good drainage.
2-3. PRECAUTIONS FOR SALT PROOF TYPE "-BS" MODEL
OCH636A
Содержание PUY-A12NKA7
Страница 119: ...119 OCH636A ...