Check code
Abnormal points and detection methods
Causes and checkpoints
Abnormal if 2 or more units with the same address are existing.
There are 2 units or more with the same address
in their controller among outdoor unit, indoor unit,
Fresh Master, Lossnay or remote controller
Noise interference on indoor/outdoor connectors
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
6600
(A0)
Duplex address error
No
Yes
Yes
No
Is there any unit with the same
address?
Does it operate normally?
Correct the address, and turn the power
OFF of indoor/outdoor unit, Fresh Master
or Lossnay simultaneously for 2 minutes or
more, then turn the power back ON.
Malfunction of sending/receiving circuit on
indoor/outdoor unit is suspected.
There is no abnormality on the AC unit.
It might be caused by an external noise, so
check the transmission line to remove the
factor(s).
Search for a unit with the same address as
the source of abnormality.
Turn the power back ON.