16
OCH668B
Operation
PUMY-SP112VKM.TH(-BS)
PUMY-SP112VKMR1.TH(-BS)
PUMY-SP112YKM.TH(-BS)
PUMY-SP112YKMR1.TH(-BS)
PUMY-SP125VKM.TH(-BS)
PUMY-SP125VKMR1.TH(-BS)
PUMY-SP125YKM.TH(-BS)
PUMY-SP125YKMR1.TH(-BS)
PUMY-SP140VKM.TH(-BS)
PUMY-SP140VKMR1.TH(-BS)
PUMY-SP140YKM.TH(-BS)
PUMY-SP140YKMR1.TH(-BS)
Operating
conditions
Ambient
temperature
Indoor
DB/
WB
27/19°C
20°C
27/19°C
20°C
27/19°C
20°C
Outdoor
35°C
7/6°C
35°C
7/6°C
35°C
7/6°C
Indoor unit
No. of connected units
Unit
4
4
4
No. of units in operation
4
4
4
Model
—
25
×
2
+
32
×
2
25
×
1 + 32
×
3
32
×
2 + 40
×
2
Piping
Main pipe
m
5
5
5
Branch pipe
2.5
2.5
2.5
Total pipe length
15
15
15
Fan speed
—
Hi
Hi
Hi
Amount of refrigerant
kg
6.5
6.5
6.5
Outdoor unit
Electric current
A
15.69
14.88
18.78
18.38
22.27
19.62
Voltage
V
230
230
230
230
230
230
Compressor frequency
Hz
57
74
65
84
73
88
LEV opening Indoor unit
Pulse
226
396
264
335
262
358
Pressure
High pressure/Low pressure
MPaG
2.96/1.08
1.93/0.63
3.12/1.02
2.06/0.60
3.25/0.99
2.08/0.60
Temp. of
each section
Outdoor
unit
Discharge
°C
67.6
43.1
81.6
46.4
83.9
47.6
Heat exchanger outlet
48.5
2.0
49.9
1.3
51.2
-0.3
Accumulator inlet
14.8
-1.2
17.6
-2.0
15.4
-2.4
Compressor inlet
15.7
-1.6
19.6
-2.7
17.5
-2.8
Indoor unit
LEV inlet
30.6
25.2
32.7
44.6
33.7
45.0
Heat exchanger inlet
16.6
39.2
14.5
24.4
14.3
26.5
4-3. STANDARD OPERATION DATA (REFERENCE DATA)