SPECIFICATIONS
Model
PUMY-SP112VKM(R1).TH(-BS)
PUMY-SP125VKM(R1).TH(-BS)
PUMY-SP140VKM(R1).TH(-BS)
Power source
1-phase 220-230-240 V, 50 Hz; 1-phase 220 V, 60 Hz
220
230
240
220
230
240
220
230
240
50/60
50
50
50/60
50
50
50/60
50
50
Cooling capacity
(Nominal)
kW
*1
12.5
14.0
15.5
kcal/h
*1
10,750
12,040
13,330
BTU/h
*1
42,650
47,768
52,886
Power input
kW
3.10
3.84
4.70
Current input
A
14.38
13.75
13.18
17.81
17.04
16.33
21.80
20.85
19.98
COP
kW/kW
4.03
3.65
3.30
Temp. range of cooling Indoor temp. W.B.
15 to 24°C
Outdoor temp.
D.B.
-5 to 52°C
*3,*4
Heating capacity
(Nominal)
kW
*2
14.0
16.0
16.5
kcal/h
*2
12,040
13,760
14,190
BTU/h
*2
47,768
54,592
56,298
Power input
kW
3.17
3.90
4.02
Current input
A
14.70
14.06
13.48
18.09
17.30
16.58
18.65
17.83
17.09
COP
kW/kW
4.42
4.10
4.10
Temp. range of heating Indoor temp.
D.B.
15 to 27°C
Outdoor temp. W.B.
-20 to 15°C
Indoor unit
connectable
Total capacity
50 to 130% of outdoor unit capacity
Model/
Quantity
City multi
15-140/9
15-140/10
15-140/12
Branch box
15-100/8
15-100/8
15-100/8
"Mixed
system"
Branch box
1 unit
City multi
15-140/5
15-140/5
15-140/5
Branch
box
15-100/5
15-100/5
15-100/5
Branch box
2 units
City multi
15-140/3 or 2
*7
15-140/3
15-140/3
Branch
box
15-100/7 or 8
*7
15-100/8
15-100/8
Sound pressure level
(measured in anechoic room)
dB <A>
52/54
53/56
54/56
Power pressure level
(measured in anechoic room)
dB <A>
72/74
73/76
74/76
Refrigerant piping
diameter
Liquid pipe
mm (inch)
9.52 (3/8)
Gas pipe
mm (inch)
15.88 (5/8)
FAN
*2
Type × Quantity
Propeller Fan × 1
Air flow rate
m³/min
77
83
83
L/s
1283
1383
1383
cfm
2719
2931
2931
Control, Driving mechanism
DC control
Motor output kW
0.20 × 1
External static press.
0
Compressor
Type × Quantity
Twin rotary hermetic compressor × 1
Manufacturer
Mitsubishi Electric Corporation
Starting method
Inverter
Capacity control %
Cooling 26 to 100
Heating 20 to 100
Cooling 24 to 100
Heating 18 to 100
Cooling 21 to 100
Heating 17 to 100
Motor output kW
3.1
3.5
3.7
Case heater
kW
0
Lubricant
FV50S (1.4litter)
External finish
Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
External dimension H × W × D
mm
981 × 1,050 × 330(+40)
inch
38-5/8 × 41-3/8 × 13 (+1-37/64)
Protection devices
High pressure protection
High pressure Switch
Inverter circuit (COMP./FAN)
Overcurrent detection, Overheat detection(Heat sink thermistor)
Compressor
Compressor thermistor, Overcurrent detection
Fan motor
Overheating, Voltage protection
Refrigerant
Type × original charge
R410A 3.5 kg
Control
Electronic expansion valve
Net weight
kg (lb)
93 (205)
*8
Heat exchanger
Cross Fin and Copper tube
HIC circuit (HIC: Heat Inter-Changer)
HIC circuit
Defrosting method
Reversed refrigerant circuit
Drawing
External
RK01B171
Wiring
BH79J995
Standard attachment Document
Installation Manual
Accessory
Grounded lead wire × 2
Optional parts
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Remarks
*1 Nominal cooling conditions
*2 Nominal heating conditions
Unit converter
Indoor:
Outdoor:
Pipe length:
Level difference:
27°C D.B./19°C W.B. [81°F D.B/66°F W.B.]
35°C D.B. [95°F D.B.]
7.5 m [24-9/16 ft]
0 m [0 ft]
20°C D.B. [68°F D.B.]
7°C DB/6°C W.B. [45°F D.B./43°F W.B.]
7.5 m [24-9/16 ft]
0 m [0 ft]
kcal/h = kW × 860
BTU/h = kW × 3,412
cfm = m³/min × 35.31
lb = kg/0.4536
Above specification data is
subject to rounding variation.
*3 10 to 52°C(D.B)
:, when connecting following models: PKFY-P15/20/25VBM, PFFY-P20/25/32VLE(R)M, PFFY-P20/25/32VKM, and
M series , S series , and P series type indoor unit with branch box , M series type indoor unit with connection kit.
*4
−15 to 52
°C(D.B)
:, when using an optional air protect guide [PAC-SH95AG-E]. However, this condition does not apply to the indoor unit listed
in *3.
*5
Up to P100 when connecting via branch box.
*6
Up to 11 units when connecting via 2 branch boxes.
*7
When connecting 7 indoor units via branch box, connectable citymulti indoor units are 3; connecting 8 indoor units via branch box, connectable citymulti indoor units are 2.
*8
94 (207), for PUMY-SP112/125/140VKM(R1).TH-BS.
Notes :1. Nominal conditions *1, *2 are subject to ISO 15042.