118
OCH668B
No.
SW1
setting
Display
mode
Display
on
the
LED1,
2
(display
data)
Notes
12345678
1
2
3
4
5
6
7
8
52
00101
100
Outdoor LEV
-A
opening
pulse
0–2000
(pulse)
Display
of
opening
pulse
of
outdoor LEV
53
10101
100
Outdoor
LEV
-A
opening
pulse
abnormality
delay
54
01
101
100
Outdoor
LEV
-A
opening
pulse
abnormality
55
11
101
100
Outdoor LEV
-B
opening
pulse
56
0001
1100
Outdoor
LEV
-B
opening
pulse
abnormality
delay
57
1001
1100
Outdoor
LEV
-B
opening
pulse
abnormality
58
0101
1100
63LS
(Low
pressure)
−99.9–999.9
(kgf/cm²)
Display
of
data
from
sensor
and thermistor
59
1101
1100
63LS abnormality delay
−99.9–999.9
(kgf/cm²)
60
001
11
100
63 LS abnormality
61
101
11
100
TH2
(HIC
pipe)
−99.9–999.9
(
:
)
62
011111
00
TH2(HIC) abnormality delay
−99.9–999.9
(
:
)
63
111111
00
TH2 (HIC) abnormality
64
00000010
Operational
frequency
0–255
(Hz)
Display
of
actual
operating
frequency
65
10000010
Target
frequency
0–255
(Hz)
Display
of
target
frequency
66
01000010
Outdoor fan control
step
number
0–15
Display
of
number
of
outdoor
fan
control
steps
(target)
69
10100010
IC1
LEV
Opening
pulse
0–2000
(pulse)
Display
of
opening
pulse
of
indoor LEV
70
01
100010
IC2
LEV
Opening
pulse
71
11
100010
IC3
LEV
Opening
pulse
72
00010010
IC4
LEV
Opening
pulse
73
10010010
IC5
LEV
Opening
pulse
74
01010010
High
pressure
sensor
(Pd)
−99.9–999.9
(kgf/cm²)
Display
detected
data
of
outdoor unit sensors and thermistors
75
11010010
TH4(Compressor)(Td)
data
−99.9–999.9
(
:
)
76
001
10010
TH6(Suction
pipe)
(ET)
data
77
101
10010
TH7(Ambient) data
78
01
110010
TH3(Outdoor
liquid
pipe)
data
80
00001010
TH8(Heat sink) data
81
10001010
IC1 TH23
(Gas)
−99.9–999.9
(
:
)
(When
indoor
unit
is
not
connected,
it
is
displayed
as
0.)
Display
detected
data
of
indoor unit thermistor
82
01001010
IC2 TH23
(Gas)
83
11001010
IC3 TH23
(Gas)
84
00101010
IC4 TH23
(Gas)
85
10101010
IC5 TH23
(Gas)