17
OCH668G
Model name
PUMY-SP112VKM(-BS)
PUMY-SP112VKM-ET(-BS)
PUMY-SP112VKM-ER(-BS)
PUMY-SP112YKM(-BS)
PUMY-SP112YKM-ET(-BS)
PUMY-SP112YKM-ER(-BS)
PUMY-SP125VKM(-BS)
PUMY-SP125VKM-ET(-BS)
PUMY-SP125VKM-ER(-BS)
PUMY-SP25YKM(-BS)
PUMY-SP125YKM-ET(-BS)
PUMY-SP125YKM-ER(-BS)
PUMY-SP140VKM(-BS)
PUMY-SP140VKM-ET(-BS)
PUMY-SP140VKM-ER(-BS)
PUMY-SP140YKM(-BS)
PUMY-SP140YKM-ET(-BS)
PUMY-SP140YKM-ER(-BS)
Operating
conditions
Ambient
temperature
Indoor
D.B./
W.B.
27/19°C
20°C
27/19°C
20°C
27/19°C
20°C
Outdoor
35°C
7/6°C
35°C
7/6°C
35°C
7/6°C
Indoor
unit
No. of connected units
Unit
4
4
4
No. of units in opera
-
tion
4
4
4
Capacity × Qty.
—
Type 25×2 + Type 32×2
Type 25×1 + Type 32×3
Type 32×2 + Type 40×2
Piping
Main pipe
m
5
5
5
Branch pipe
2.5
2.5
2.5
Total pipe length
15
15
15
Fan speed
—
Hi
Hi
Hi
Amount of refrigerant
kg
6.5
6.5
6.5
Outdoor
unit
Electric current
A
11.65/3.99
11.28/3.86
14.74/5.05
14.78/5.06
17.95/6.15
15.74/5.39
Voltage
V
230/400
230/400
230/400
230/400
230/400
230/400
Compressor frequency
Hz
57
74
65
84
73
88
LEV
opening
Indoor unit
Pulse
226
396
264
335
262
358
Pressure
High pressure/Low pressure
MPaG
2.96/1.08
1.93/0.63
3.12/1.02
2.06/0.60
3.25/0.99
2.08/0.60
Temp. of
each
section
Outdoor
unit
Discharge
°C
67.6
43.1
81.6
46.4
83.9
47.6
Heat exchanger outlet
48.5
2.0
49.9
1.3
51.2
-0.3
Accumulator inlet
14.8
-1.2
17.6
-2.0
15.4
-2.4
Compressor inlet
15.7
-1.6
19.6
-2.7
17.5
-2.8
Indoor
unit
LEV inlet
30.6
25.2
32.7
24.4
33.7
26.5
Heat exchanger inlet
16.6
39.2
14.5
44.6
14.3
45.0
4-3. STANDARD OPERATION DATA (REFERENCE DATA)