Check code
Abnormal points and detection methods
Causes and checkpoints
When a connected indoor unit is incompatible, a check code <7101> is
displayed.
The model name of connected indoor unit (model code)
is read as incompatible.
The connectable indoor units are:
· SP112 to SP140 model: P10 to P140 model (code 2 to 28)
· When connecting via branch box: P15 to P100 model
(code 4 to 20)
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
7101
(EF)
Capacity code error
Yes
No
Is it set properly?
Set the switch properly.
The model code of the connected indoor
unit can be displayed by an operation of
SW1 on the outdoor unit.
Check the model selection switch (SW4
on the indoor controller board) of the
connected indoor unit.
94
95
OCH668G