14
OCH668G
4-2. CORRECTION BY TEMPERATURE
15
16
17
18
19
20
21
22
23
24
0.4
0.6
0.8
1.0
1.2
Ratio of cooling capacity
Indoor Temperature [°CW.B.]
15.0
16.0
18.0
19.0
20.0
22.0
24.0
0.777
0.832
0.944
1.000
1.030
1.091
1.151
Ratio of cooling capacity
Outdoor Temperature [°C D.B.]
Indoor Temperature
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
19°C W.B
The outdoor units have varied capacity at different designing temperature. Using the nominal cooling capacity value and the
ratio below, the capacity can be observed at various temperature.
Figure
7 Indoor unit temperature correction
To be used to correct indoor unit capacity only
Figure 8 Outdoor unit temperature correction
To be used to correct outdoor unit capacity only
<Cooling>