44
OCH668G
F. Example of a system using Branch Box, A-Control indoor unit, and
CITY MULTI series indoor unit.
Examples
of
Transmission
Cable
Wiring
Wiring Method
Address Settings
a. Always use shielded wire when making connections between the outdoor unit (OC) and the Branch Box or CITY
MULTI series indoor unit (M-IC), as well for all OC-OC wiring intervals.
b. Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3)
of each outdoor unit (OC) to terminals M1 and M2 on the terminal S on the transmission cable terminal block (TB5)
of the Branch Box or CITY MULTI series indoor unit (M-IC).
c. Connect terminals 1 and 2 on the transmission cable terminal block (TB5/TB15) of the A-control indoor unit (A-IC) or
CITY MULTI series indoor unit (M-IC), to the terminal block on the MA remote controller (MA-RC).
d. Connect together terminals M1, M2 and terminal S on the terminal block for centralized control (TB7) for the outdoor
unit (OC).
e. DO NOT change the jumper connector CN41 on MULTI controller board.
f. The earth processing of S terminal for the centralized control terminal block (TB7) is unnecessary. Connect the termi
-
nal S on the power supply unit to the earth.
g. Set the address setting switch as follows.
Unit
Range
Setting Method
M-IC
01 to 50
-
A-IC
01 to 50
According to the set address of connected Branch Box, set the A-IC addresses
sequentially by SW1, SW11, SW12 on Branch Box.
(For example, when the Branch Box address is set to 01, set the A-IC
addresses to 01, 02, 03, 04 and 05.)
Branch Box
01 to 50
Use a number within the range 1-50, but it should not make the highest
address of connected A-IC exceed 50.
Outdoor Unit
51 to 100
Use the smallest address of all the Branch Box plus 50.
The address automatically becomes “100” if it is set as “01–50”.
MA Remote Controller
-
Address setting is not necessary.
TB7
TB3
(51)
L
5
L
1
OC
TB7
(53)
OC
L
6
L
7
M1 M2 S M1 M2 S
S
M1 M2 S
TB3
M1 M2 S
M1 M2 S
M1 M2
TB3A
A-IC
(01)
A-IC
(02)
A-IC
(03)
A-IC
(04)
A-IC
MA-RC
MA-RC
MA-RC
MA-RC
WL-RC
WL-RC
WL-RC
WL-RC
(05)
A-IC
(06)
A-IC
(07)
A-IC
(08)
S1
S2
S3
TB
S1
S2
TB5/TB15
1
2
A
B
A
B
A
B
A
B
1
2
1
2
1
2
S3
TB
S1
S2
S3
TB
S1
S2
S3
TB
S1
S2
S3
TB
S1
S2
S3
TB
S1
S2
S3
TB
S1
S2
S3
TB
S1
S2
S3
TB3B
S1
S2
S3
TB3C
S1
S2
S3
TB3D
S1
S2
S3
TB3E
S1
S2
S3
TB3A
S1
S2
S3
TB3B
S1
S2
S3
TB3C
S1
S2
S3
M1
M2
S
TB5
M1
M2
S
TB5
L
2
A
A
A
M-IC
(09)
M-IC
(10)
MA-RC
MA-RC
TB5
M1
M2
1
2
A
B
A
B
1
2
S
TB5
M1
M2
S
L
3
L
4
Power
Supply
Unit
System
controller
Branch Box
Branch Box
A
: Shielded wire
( ): Address example
m
1
TB5/TB15
TB5/TB15
TB15
TB15
TB5/TB15
L
8
(01)
(06)