120
OCH668G
No.
SW1 setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678
1
2
3
4
5
6
7
8
192
0000001
1
Actual frequency of abnormality
0–255 (Hz)
Display of actual frequency at time of abnormality
193
1000001
1
Fan step number
at time of
abnormality
0–15
Display of fan step number at time of abnormality
195
1100001
1
IC1 LEV opening pulse
at time of abnormality
0–2000 (pulse)
Display of opening pulse of indoor LEV at time of
abnormality
196
0010001
1
IC2 LEV opening pulse
at time of abnormality
197
1010001
1
IC3 LEV opening pulse
at time of abnormality
198
01
10001
1
IC4 LEV opening pulse
at time of abnormality
199
11
10001
1
IC5 LEV opening pulse
at time of abnormality
200
0001001
1
High pressure sensor
data at time of abnormality
−99.9–999.9 (kgf/cm²)
Display of data from
High pressure sensor
, all
thermistors, and SC/SH at
time of abnormality
.
201
1001001
1
TH4 (Compressor) sensor data at time of
abnormality
−99.9–999.9 (°C)
202
0101001
1
TH6 (Suction pipe) sensor data at time of
abnormality
203
1101001
1
TH3 (Outdoor liquid pipe) sensor data at time of abnormality
204
001
1001
1
TH8 (Heat sink)
sensor data at time of
abnormality
205
101
1001
1
OC SC (cooling) at time of
abnormality
−99.9–999.9(°C)
During heating: subcool (SC)
During cooling; superheat (SH) (Fixed to "0" during cooling operation)
Display of indoor SC/SH data at time of abnormality
206
01
11001
1
IC1 SC/SH at time of
abnormality
207
1111
00
11
IC2 SC/SH at time of
abnormality
208
0000101
1
IC3 SC/SH at time of
abnormality
209
1000101
1
IC4 SC/SH at time of
abnormality
210
0100101
1
IC5 SC/SH at time of
abnormality
211
1100101
1
IC6 Capacity code
0–255
Display of indoor unit
capacity code
The No.1 unit will start from the M-NET
address with the
lowest number
212
0010101
1
IC7 Capacity code
213
1010101
1
IC8 Capacity code
214
01
10101
1
IC6 operation mode
ST
OP
Fan
Cooling
thermo-ON
Cooling
thermo-OFF
Heating
thermo-ON
Heating
thermo-OFF
Display of indoor unit
operation mode
215
11
10101
1
IC7 operation mode
216
0001
101
1
IC8 operation mode
217
1001
101
1
IC6 LEV opening pulse
0–2000 (pulse)
Display of opening pulse of
indoor LEV
218
0101
1001
IC7 LEV opening pulse
219
1101
1001
IC8 LEV opening pulse