9-2-2. Cross section area of Wire for Main Power and ON/OFF capacities
1. Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
2. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10%.
3. Specific wiring requirements should adhere to the wiring regulations of the region.
4. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57). For
example, use wiring such as YZW.
5. Install an earth line longer than power cables.
Connect to Branch box (PAC-MK·BC)
Indoor unit
V1
V2
Type 1 PEAD-RP·JAQ(L), PEAD-M·JA(L)
26.9
2.4
Type 2 SEZ-KD·VA, SEZ-M·DA, PCA-RP·KAQ, PCA-M·KA, PLA-RP·EA, PLA-M·EA,
SLZ-KF·VA, SLZ-M·FA
19.8
Type 3 MLZ-KA·VA, MLZ-KP·VF
9.9
Type 4 MSZ-LN·VG, MSZ-AP·VF, MSZ-AP·VG, MFZ-KJ·VE, MSZ-EF·VG-E2/ER2/ET2,
MSZ-EF·VGK-E1/ER1/ET1, MSZ-AP·VGK, MFZ-KT·VG, MSZ-LN·VG2
7.4
Type 5 MSZ-FH·VE, MSZ-GF·VE, MSZ-SF·VE, MSZ-EF·VE, MSZ-SF·VA, MSZ-GE·VA,
MSZ-EF·VG-E1/ER1/ET1
6.8
Type 6 Branch box (PAC-MK·BC)
5.1
3.0
Connect to Connection kit (PAC-LV11M)
Indoor unit
V1
V2
Type 7 MSZ-LN·VG, MSZ-AP·VF, MSZ-AP·VG, MSZ-EF·VG-E2/ER2/ET2,
MSZ-EF·VGK-E1/ER1/ET1, MSZ-AP·VGK, MFZ-KT·VG, MSZ-LN·VG2
7.4
2.4
Type 8 MSZ-SF·VA, MSZ-SF·VE, MSZ-EF·VE, MSZ-FH·VE, MSZ-GE·VA, MSZ-EF·VG-E1/ER1/ET1
6.8
Type 9 Connection kit (PAC-LV11M)
3.5
Connect to CITY MULTI
Indoor unit
V1
V2
Type 10 PEFY-P·VMA(L)-E(2), PEFY-P·VMA3-E
38.0
1.6
Type 11 PEFY-P·VMHS-E-F, PEFY-P·VMHS-E
26.8
Type 12 PEFY-P·VMA(L)-E3, PEFY-M·VMA(L)-A
18.6
3.0
Type 13
PMFY-P·VBM-E, PLFY-P·VBM-E, PLFY-P·VEM-E, PLFY-EP·VEM-E, PLFY-P·VFM-E,
PEFY-P·VMS1(L)-E, PCFY-P·VKM-E, PKFY-P·VHM-E, PKFY-P·VKM-E, PFFY-P·VCM-E,
PFFY-P·VKM-E, PFFY-P·VLRMM-E, PKFY-P·VLM-E/ET, PLFY-M·VEM-E/ET
19.8
2.4
Type 14 PKFY-P·VBM-E
3.5
Type 15 PLFY-P·VLMD-E, PEFY-P·VMH-E, PEFY-P·VMR-E-L/R, PEFY-P·VMH-E-F,
PFFY-P·VLEM-E, PFFY-P·VLRM-E, GUF-RD(H)4
0
0
C: Multiple of tripping current at tripping time 0.01 s
Please pick up “C” from the tripping characteristic of the breaker.
<Example of “F2” calculation>
Condition PLFY-P·VBM-E × 4 + PEFY-P·VMA-E
× 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65
→ 16 A breaker (Tripping current = 8 × 16 A at 0.01 s)
*
5
Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + ··· + V2 × (Quantity of Type15) +
V3 × (Wire length[km])
<Example of "G1" calculation>
When connecting 3 units of the SEZ-KD respectively to a branch box with a wire that is 20 m long and 1.5 mm² in diameter, then con
-
necting the branch box and PEFY-VMA to a single breaker with a wire that is 100 m long in total and 2.5 mm² in diameter.
G1 = 2.4 × 3 + 3 + 1.6 + 48 × 0.02 × 3 + 56 × 0.1
= 20.28
G1
Current sensitivity
30 or less
30 mA 0.1 seconds or less
100 or less
100 mA 0.1 seconds or less
6000
600
60
10
Tripping Time [s]
1
0.1
0.01
1
2
Rated Tripping current (x)
3 4
6 8
C
10
20
Sample chart
SAMPLE
<Outdoor unit> When power is supplied to outdoor unit and branch box separately
Model
Power Supply
Minimum Wire Cross-sectional area (mm²)
Breaker for Wiring
*
1
Breaker for Current Leakage
Main Cable
Ground
Outdoor Unit
SP112–140V
~/N 220-230-240 V, 50 Hz
~/N 220 V, 60 Hz
6
6
32 A
32 A 30 mA 0.1 seconds or less
SP112–140Y
3N~380-400-415 V, 50 Hz
3N~380 V, 60 Hz *
2
1.5
1.5
16 A
16 A 30 mA 0.1 seconds or less
<Outdoor unit> When power is supplied to branch box from the outdoor unit
Model
Power Supply
Minimum Wire Cross-sectional area (mm²)
Breaker for Wiring
*
1
Breaker for Current Leakage
Main Cable
Ground
Outdoor Unit
SP112–140V
~/N 220-230-240 V, 50 Hz
~/N 220 V, 60 Hz
6
6
40 A
40 A 30 mA 0.1 seconds or less
SP112–140Y
3N~380-400-415 V, 50 Hz
3N~380 V, 60 Hz *
2
2.5
2.5
25 A
25 A 30 mA 0.1 seconds or less
*
1
A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*
2
In multi-phase appliances, the colour of the neutral conductor of the supply cord, if any, shall be blue.
<Indoor units> When power is supplied to indoor unit and outdoor unit separately
Total operating current of the indoor unit
Minimum wire thickness (mm²)
Ground-fault interrupter
*
3
Local switch (A)
Breaker for wiring
(NFB)
Main Cable
Branch
Ground
Capacity
Fuse
F0 = 16 A or less
*
4
1.5
1.5
1.5
20 A current sensitivity *
5
16
16
20
F0 = 25 A or less
*
4
2.5
2.5
2.5
30 A current sensitivity *
5
25
25
30
F0 = 32 A or less
*
4
4.0
4.0
4.0
40 A current sensitivity *
5
32
32
40
Apply to IEC61000-3-3 about max. permissive system impedance.
*
3
The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*
4
Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + {V1 × (Quantity of Type 3)/C} + ··· + {V1 × (Quantity of Type 15)/C}
Wire thickness
V3
1.5 mm²
48
2.5 mm²
56
4.0 mm²
66