96
OCH733
Check code
Abnormal points and detection methods
Causes and checkpoints
When the capacity of connected indoor unit is over, check code <7101> is
displayed.
The model name of connected indoor unit (model code)
is read as incompatible.
The connectable indoor units are:
·P36, P48, HP36, HP48 model: P04 to P54 model (code
2 to 28)
·P60 model: P04 to P72 model (code 2 to 40)
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
7101
(EF)
Capacity code error
Yes
No
Is it set properly?
Set the switch properly.
The model code of the connected indoor
unit can be displayed by an operation of
SW1 on the outdoor unit.
Check the model selection switch (SW4
on the indoor controller board) of the
connected indoor unit.