8-5. INTERNAL SWITCH FUNCTION TABLE
PUMY-P36NKMU3
PUMY-P48NKMU3 PUMY-P60NKMU3
PUMY-P36NKMU3-BS
PUMY-P48NKMU3-BS PUMY-P60NKMU3-BS
PUMY-HP36NKMU1 PUMY-HP48NKMU1
Switch
Step
Function
Operation in Each Switch Setting
Remarks
Purpose
Additional Information
ON
OFF
When to Set
SWU1 ones digit
SWU2 tens digit
Rotary switch
Before turning the power ON
<Initial settings>
SW1 Digital Display Switch
1–8
Can be set either during operation or not.
<Initial settings>
SW2 Function Switch
1
Selects operating system startup
With centralized controller
Without centralized controller
Before turning the power ON
<Initial settings>
Turn ON when the centralized controller is connected to the outdoor unit.
SW2-1 must be turned ON if a central controller is connected to the system.
An example of this
would be a
TC-24, EW
-50A,
AG150,
AE50 or
AE200. If SW2-1 is not turned on, while using a central controller
, in rare circumstances
problems may be encountered such as indoor units not responding to group commands. Therefore, turning SW2-1 ON is recommended if a central controller is used.
2
Connection Information Clear Switch
Clear
Do not clear
When relocating units or connecting additional units.
—
3
Abnormal data clear switch input
Clear abnormal data
Normal
OFF to ON any time after the power is turned on.
To delete an error history
.
4
Pump down
ON
OFF
During compressor running
To facilitate outdoor unit the pumping down operation. Frequency = Fixed to 65 Hz Indoor-linear expansion valve = Fully open Outdoor fan step = Fixed to 10
Please refer to a section referring to the pumping down on outdoor units Installation Manuals. It might not be possible to collect all the refrigerant if the amount is excessive.
5
—
—
—
—
—
—
—
6
—
—
—
—
—
—
—
SW4/ SW8/ (SW9) Model Switch
1–6
MODEL
SELECTION 1:ON 0:OFF
Before the power is turned ON.
<Initial settings> Set for each capacity
.
—
—
SW3 T
rial
operation
1
ON/OFF from outdoor unit
ON
OFF
Any time after the power is turned ON.
<Initial settings>
—
—
2
Mode setting
Heating
Cooling
—
—
SW5 Function switch
1
—
—
—
Can be set when of
f or during
operation
<Initial settings>
—
—
2
Change the indoor unit's LEV opening at startup
Enable
Normal
To set the LEV opening at startup higher than usua
l.
(+150 pulses) To improve the operation with the LEV almost clogged.
The refrigerant flow noise at start-
up become louder
.
3
—
—
—
—
—
4
Auxiliary heater
Enable
Disable
Before the power is turned ON.
Turn ON when an auxiliary heater is connected. (It transmits a connection permission signal of the auxiliary heater to the connected CITY
MUL
TI indoor unit.)
Turn ON only when the auxiliary heater is connected and operated.
5
Change the indoor unit's LEV opening at defrost
Enable
Normal
Can be set when OFF or during operation
To set the LEV opening higher than usual during defrosting operation. (Only Qj
[
10 is valid, + 300 pulses)
To avoid the discharge temperature increase
and provide efficient defrosting operation.
The refrigerant flow noise during
the defrosting operation becomes louder
.
6
Switching the target sub cool (Heating mode)
Enable
Normal
To decrease the target sub cool value.
To reduce the discharge temperature decrease due to refrigerant liquid accumulation in the units.
A refrigerant flow noise might be
generated if the sub cool value is too small.
The black square (
■
) indicates a switch position.
1
ON OFF
2
3
4
5
6
7
8
SWU2
(tens digit)
0
1 2
3 4
5
67
89
SWU1
(ones digit)
0
1 2
3 4
5
67
89
1
ON OFF
2
3
4
5
6
SWU2
(tens digit)
0
1 2
3 4
5
67
89
SWU1
(ones digit)
0
1 2
3 4
5
67
89
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
ON OFF
1
ON OFF
2
3
ON OFF
PUMY-P36NKMU3
SW4
SW8
SW9
PUMY-HP36NKMU1
PUMY-P48NKMU3
PUMY-HP48NKMU1
1
ON OFF
2
3
4
5
6
1
ON OFF
2
PUMY-P60NKMU3
SW4
SW8
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
4
5
6
1
ON OFF
2
3
ON OFF
1
ON OFF
2
3
ON OFF
SW4
SW8
SW9
3
ON OFF
SW9
1
ON OFF
2
1
ON OFF
2
3
4
5
6
7
8
Continue to the next page
Содержание PUMY-HP36NKMU1
Страница 33: ...33 OCH733 6 WIRING DIAGRAM PUMY P36NKMU3 PUMY P48NKMU3 PUMY P36NKMU3 BS PUMY P48NKMU3 BS ...
Страница 34: ...34 OCH733 PUMY P60NKMU3 PUMY P60NKMU3 BS ...
Страница 35: ...35 OCH733 PUMY HP36NKMU1 PUMY HP48NKMU1 ...
Страница 155: ...155 OCH733 ...