42
OCH733
• Name, Symbol, and the Maximum Units for Connection
Permissible
Length
Prohibited items
• Longest length via outdoor units: L
1
+L
2
+L
3
+L
4,
L
1
+L
2
+L
3+
L
5,
L
1
+L
2
+L
6
+L
7
[
1640 ft [500 m] (AWG 16 [1.25 mm² ])
• Longest transmission cable length: L
1,
L
3
+L
4
, L
3+
L
5,
L
2
+L
6
, L
7
[
656 ft [200 m] (AWG 16 [1.25 mm²])
• M-NET Remote controller cable length:
R
1
,
R
2
+
R
3
,
R
4
[
33 ft [10 m] (AWG 20 to AWG 16 [0.5 to 1.25 mm²])
If the length exceeds 33 ft [10 m], use AWG 16 [1.25 mm²] shielded wire. The length of
this section (L
8
) should be included in the calculation of the maximum length and overall
length.
• Never connect together the terminal blocks (TB5) for transmission wires for M-NET control indoor units (M-IC) that have
been connected to different outdoor units (OC).
• Set all addresses to ensure that they are not overlapped.
• M-NET remote controller and MA remote controller cannot be connected with the M-NET control indoor unit of the same
group wiring together.
A
B
C
E
D
M-IC
(51)
TB5
M-NET RC
(01)
TB5
(03)
M-IC
TB5
(02)
TB5
(04)
M-IC
TB5
(05)
TB5
(07)
M-IC
TB5
(06)
(101)
(105)
(104)
(155)
OC
(53)
OC
Power Supply
Unit
A
: Group
B
: Group
C
: Group
D
: Shielded Wire
E
: Sub M-NET Remote Controller
( ): Address example
TB7
TB3
M1 M2 S
TB7
M1 M2 S
M1 M2 S
TB3
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
A B
A B
A B
A B
M1 M2 S
System
controller
NO
NO
M-IC
M-IC
M-IC
M-NET RC M-NET RC
M-NET RC