105
OCH733
1. Notes
• High voltage is applied to the connecter (CNF1, 2) for the fan motor. Pay attention to the service.
• Do not pull out the connector (CNF1, 2) for the motor with the power supply on.
(It causes trouble of the outdoor multi controller circuit
board and fan motor.)
2. Self check
Symptom: The outdoor fan cannot rotate.
Check method of DC fan motor (fan motor/outdoor multi controller circuit board)
Power supply check(Remove the connector (CNF1, 2))
1
While the breaker is OFF, disconnect the compressor wirings (U/V/W) from the outdoor power circuit board.
2
While the breaker is OFF, disconnect the fan motor connector CNF1, 2.
3
When 5 minutes have passed since turning ON the breaker, turn SW7-1 ON.
4
Check the voltage of the outdoor multi controller circuit board.
Measure the voltage in the outdoor multi controller circuit
board.
TEST POINT
1
: V
DC
(between 1 (+) and 4 (-) of the fan connector): V
DC
290–330 V DC(When PAM stops), 380 V DC (When PAM is operating)
TEST POINT
2
: V
CC
(between 5 (+) and 4 (-) of the fan connector): V
CC
15 V DC
TEST POINT
3
: V
CC
(between 6 (+) and 4 (-) of the fan connector): V
CC
0-6.5 V DC
No
Fail
Fail
Wiring contact check
Contact of fan motor connector (CNF1, 2)
Fuse check
Check the fuse (F500) on outdoor
controller board.
Correct the wiring.
Is the fan motor normal?
Replace outdoor multi controller circuit board.
Replace defective the fan motor.
Replace defective the fan motor.
Replace outdoor multi
controller circuit board.
Is the voltage normal?
Is there contact failure?
Yes
Yes
No
Did the fuse blow?
No
Yes
Check the operation of fan.
Complete.
Yes
OK
Check the operation.
OK
Disconnect the FAN motor connector and
measure the resistance of connector pins.
Refer to “8-7. HOW TO CHECK THE PARTS”.
Replace outdoor multi controller circuit board
(MULTI.B.) and the defective fan motor.
Replace outdoor multi controller
circuit board (MULTI.B.).
Complete.
No
Yes
Note: Turn SW7-1 OFF after the troubleshooting completes.
The fan sometimes starts on-off cycle operation during low-load operation or cooling at low ambient temperature.
It is not abnormal; the operation ensures reliability of the product.
Содержание PUMY-HP36NKMU1
Страница 33: ...33 OCH733 6 WIRING DIAGRAM PUMY P36NKMU3 PUMY P48NKMU3 PUMY P36NKMU3 BS PUMY P48NKMU3 BS ...
Страница 34: ...34 OCH733 PUMY P60NKMU3 PUMY P60NKMU3 BS ...
Страница 35: ...35 OCH733 PUMY HP36NKMU1 PUMY HP48NKMU1 ...
Страница 155: ...155 OCH733 ...