21
OCH733
4-3. STANDARD OPERATION DATA (REFERENCE DATA)
Operation
PUMY-P36NKMU3
PUMY-P36NKMU3-BS
PUMY-P48NKMU3
PUMY-P48NKMU3-BS
PUMY-P60NKMU3
PUMY-P60NKMU3-BS
Operating
conditions
Ambient
temperature
Indoor
DB/WB
80°F/67°F
[26.7°C / 19.4°C]
70°F/60°F
[21.1°C/15.6°C]
80°F/67°F
[26.7°C/19.4°C]
70°F/60°F
[21.1°C/15.6°C]
80°F/67°F
[26.7°C/19.4°C]
70°F/60°F
[21.1°C/15.6°C]
Outdoor
95°F/75°F
[35.0°C/23.9°C]
47°F / 43°F
[8.3°C/6.1°C]
95°F/ 75°F
[35.0°C / 23.9°C]
47°F/43°F
[8.3°C/6.1°C]
95°F/75°F
[35.0°C/23.9°C]
47°F/43°F
[8.3°C/6.1°C]
Indoor unit No. of connected units
Unit
3
4
4
No. of units in operation
3
4
4
Model
―
12 × 3
12 × 4
15 × 4
Piping
Main pipe
Ft (m)
9.84 (3)
9.84 (3)
9.84 (3)
Branch pipe
14.76 (4.5)
14.76 (4.5)
14.76 (4.5)
Total pipe length
54.13 (16.5)
68.90 (21)
68.90 (21)
Fan speed
―
Hi
Hi
Hi
Amount of refrigerant
LBS. OZ. (kg)
17 LBS. (7.7)
17 LBS. 3 OZ. (7.8)
19 LBS. 6 OZ. (8.8)
Outdoor
unit
Electric current
A
10.2
13.3
15.6
17.1
19.3
20.4
Voltage
V
230
230
230
Compressor frequency
Hz
47
66
64
81
53
64
LEV
opening
Indoor unit
Pulse
268
438
247
313
386
498
Pressure High pressure/Low pressure
PSIG
[MPaG]
370/116
[2.55/0.80]
406/104
[2.80/0.72]
419/112
[2.89/0.77]
409/97
[2.82/0.67]
397/144
[2.74/0.99]
425/97
[2.93/0.67]
Temp. of
each
section
Outdoor
unit
Discharge
°F[°C]
139.1 [59.5] 145.8 [63.2] 154.2 [67.9] 149.2 [65.1] 141.8 [61.0] 154.4 [68.0]
Heat exchanger outlet
101.3 [38.5]
34.3 [1.3]
99.7[37.6]
32.2 [0.1]
99.9 [37.7]
33.1 [0.6]
Accumulator inlet
49.5 [9.7]
33.4 [0.8]
47.1 [8.4]
31.3 [−0.4]
52.7 [11.5]
32.2 [0.1]
Compressor inlet
45.3 [7.4]
33.6 [0.9]
42.4 [5.8]
32.7 [0.4]
53.4 [11.9]
30.9 [-0.6]
Indoor unit Lev inlet
83.7 [28.7]
100.2 [37.9]
71.1 [21.7]
98.8 [37.1]
89.6 [32.0]
104.0 [40.0]
Heat exchanger inlet
49.6 [9.8]
132.3 [55.7]
47.5 [8.6]
134.6 [57.0]
56.1 [13.4]
141.8 [61.0]
Operation
PUMY-HP36NKMU1
PUMY-HP48NKMU1
Operating
conditions
Ambient
temperature
Indoor
DB/WB
80°F/67°F
[26.7°C / 19.4°C]
70°F/60°F
[21.1°C/15.6°C]
80°F/67°F
[26.7°C/19.4°C]
70°F/60°F
[21.1°C/15.6°C]
Outdoor
95°F/75°F
[35.0°C/23.9°C]
47°F / 43°F
[8.3°C/6.1°C]
95°F/ 75°F
[35.0°C / 23.9°C]
47°F/43°F
[8.3°C/6.1°C]
Indoor unit No. of connected units
Unit
3
4
No. of units in operation
3
4
Model
―
12 × 3
12 × 4
Piping
Main pipe
Ft (m)
9.84 (3)
9.84 (3)
Branch pipe
14.76 (4.5)
14.76 (4.5)
Total pipe length
54.13 (16.5)
68.90 (21)
Fan speed
―
Hi
Hi
Amount of refrigerant
LBS. OZ. (kg)
17 LBS. (7.7)
17 LBS. 3 OZ. (7.8)
Outdoor
unit
Electric current
A
10.2
13.3
15.6
17.1
Voltage
V
230
230
Compressor frequency
Hz
47
66
64
81
LEV
opening
Indoor unit
Pulse
112
128
112
132
Pressure High pressure/Low pressure
PSIG
[MPaG]
2.57/0.98
2.78/0.64
2.83/0.77
2.82/0.55
Temp. of
each
section
Outdoor
unit
Discharge
°F[°C]
139.1 [59.5]
145.8 [63.2]
154.2 [67.9]
149.2 [65.1]
Heat exchanger outlet
101.3 [38.5]
34.3 [1.3]
99.7 [37.6]
32.2 [0.1]
Accumulator inlet
49.5 [9.7]
33.4 [0.8]
47.1 [8.4]
31.3 [-0.4]
Compressor inlet
45.3 [7.4]
33.6 [0.9]
42.4 [5.8]
32.7 [0.4]
Indoor unit Lev inlet
83.7 [28.7]
100.2 [37.9]
71.1 [21.7]
98.8 [37.1]
Heat exchanger inlet
49.6 [9.8]
132.3 [55.7]
47.5 [8.6]
134.6 [57.0]
Содержание PUMY-HP36NKMU1
Страница 33: ...33 OCH733 6 WIRING DIAGRAM PUMY P36NKMU3 PUMY P48NKMU3 PUMY P36NKMU3 BS PUMY P48NKMU3 BS ...
Страница 34: ...34 OCH733 PUMY P60NKMU3 PUMY P60NKMU3 BS ...
Страница 35: ...35 OCH733 PUMY HP36NKMU1 PUMY HP48NKMU1 ...
Страница 155: ...155 OCH733 ...