102
OCH733
Switch
Step
Function
Operation in Each Switch Setting
Remarks
Purpose
Additional Information
ON
OFF
When to Set
SW5 Function switch
7
During the outdoor unit is in HEA
T
operation, additionally increase about 50 to 70 pulses of the LEV opening on the indoor unit which is in F
AN, ST
OP
, COOL
or thermo-OFF
*
1
.
Active
Inactive
Can be set when OFF or during operation
To additionally increase about 50 to 70 pulses of the LEV opening for units other than in HEA
T operation.
To avoid
a refrigerant shortage (less capacity) due to
refrigerant
liquid accumulation in the units which is not in operation.
A
refrigerant
flow
noise
might
be
generated
in units other than the one in operation.
8
During the outdoor unit is in operation, fully closing the linear expansion valve on the indoor unit which is in F
AN or
COOL.
*
2
Enable
Normal
Before turning the
power ON.
To reduce the room temperature increase by setting
the
LEV
opening
lower
for
the
units
in
thermo-OFF
operation.
The refrigerant is more likely to collect in the units with
thermo-OFF operation, and causing the units refrigerant
shortage. (Results in less capacity and increase of discharge temperature.)
SW6 Function switch
1
—
—
—
—
<Initial settings>
—
—
2
—
—
—
—
—
—
3
—
—
—
—
—
—
4
Change of defrosting control
Enable (For high humidity)
Normal
Can be set when OFF or during operation
To shorten the defrosting prohibition time in high humidity (or heavy snow) region, in order to reduce malfunctions caused by frost .
The performance of the HEA
T operation is somewhat
reduced since the defrosting operation is frequently performed.
5
—
—
—
—
—
6
Switching the target discharge pressure (Pdm)
Enable
Normal
To raise the performance by setting the Pdm higher during HEA
T operation.
Power consumption is raised due to a higher frequency
. (The
performance would not be raise at the maximum operating frequency
.)
7
Switching (1) the target evaporation temperature (ETm)
Enable
Normal
To raise/reduce the performance by changing the target ETm during COOL
operation.
Switch to raise the performance: raises the performance Switch to reduce the performance: prevents dew condensation
Switching it to raise the performance, it raises the power
consumption, and produces more dew condensation. Switching it to reduce the performance, it makes the
performance insufficient.
8
Switching (2) the target evaporation temperature (ETm)
Enable
Normal
SW7 Function switch
1
Ignore current sensor abnormality and rotational frequency abnormality of outdoor fan motor
Enable
Normal
After turning the power ON
<Initial settings>
To perform a test run for electrical parts alone without running the compressor
. Also, to perform the
troubleshooting of electrical parts without operating the outdoor unit’
s fan.
Make sure to connect the connectors to the compressor after checking the electrical parts. Be careful not to get electrical shock while working on electrical parts.
2
Setting to energize the freeze stat heater (optional part)
During heating operation only
*
3
Include when the heating operation is OFF
.
*
4
Can be set when OFF or during operation
It
re
du
ce
s sno
w
on
the
b
ase
, e
ve
n it
blo
ws
insid
e
the
unit, by setting the base heater ON while the HEA
T
operation is stopped.
Power consumption raises while the operation is stopped.
3
High heating performance mode
(except for PUMY
-HP
model)
Enable
Normal
Anytime
To raise the performance of HEA
T
operation if it is insufficient.
The performance may not be raised depending on the capacity
of indoor units in operation, or outside air temperature.
4
Maximum frequency down at 1 hour after COOL
operation
Enable
Normal
Can be set when OFF or during operation
To reduce dew condensation on the indoor unit by lowering the frequency
.
The performance might be insufficient.
5
Simultaneous cooling and heating with external heater
Enable
Disable
Anytime
The simultaneous operation of cooling and heating will be possible by installing an external heater to the CITY
MUL
TI indoor unit.
For the installation of external heater and the indoor unit setting, refer to the indoor unit service manual.
6
Manual defrost
Manual defrost
Normal
During compressor running in HEA
T
mode.
Turn ON when it is necessary to perform the defrosting operation forcedly
.
(
Ef
fective only at startup, or 10
minutes after the last defrosting operation)
It performs the defrosting operation forcedly
.
(HEA
T operation is stopped temporarily
.)
SW9 Function Switch
1
Auto change over from remote controller
(IC with the minimum address)
Enable
Disable
Before turning the
power ON
<Initial settings>
Enables the indoor unit with the minimum address
to select
AUT
O mode, and switches the operation
mode of the other indoor units to the same mode.
Cannot be set when the centralized control is ON.
2
Switching the Silent/ Demand mode
Demand control
Silent mode
Can be set when OFF or during operation
—
About the Silent mode/Demand control setting, refer to
"8-10. OUTDOOR UNIT
INPUT/OUTPUT
CONNECT
OR".
3
— *
5
—
—
—
—
—
4
—
—
—
—
—
—
*
1
SW5-7 Opens the indoor-
linear
expansion valve as a countermeasure against the indoor unit in F
AN, COOL, ST
OP
, or thermo-OFF operation with refrigerant-shortage status due to an accumulation of liquid refrigerant in the indoor unit.
*
2
SW5-8 Countermeasure against room temperature rise for indoor unit in F
AN and COOL
mode.
*
3
During heating operation and the ambient temperature is 39
°F (
4
°C)
or below
, the freeze prevention heater is energized.
*
4
During heating mode is OFF (include thermo-OFF in cooling mode), and the ambient temperature is 39
°F (
4
°C)
or below
, the freeze prevention heater is energized.
*
5 Use it for Model Switch. ((H)P36/48)
SW6-6
OFF
ON
Target Pdm (kg/cm²)
31.5
33.5
SW6-7
OFF
ON
OFF
ON
SW6-8
OFF
OFF
ON
ON
Target ETm (
°F
(°C
))
48(9)
52(1
1)
43(6)
57(14)
1
ON OFF
2
3
4
5
6
7
8
<Initial settings>
1
ON OFF
2
3
4
5
6
7
8
1
ON OFF
2
3
4
5
6
1
ON OFF