11
OCH733
10
Model
PUMY-HP36NKMU1
PUMY-HP48NKMU1
Power source
208/230 V AC, 60 Hz
Cooling capacity
*1
(Nominal)
*1
*1
kW
10.6
14.1
kcal/h
9,100
12,100
Btu/h
36,000
48,000
Power input
W
2310
3545
Current input
A
11.3/10.2
17.3/15.6
EER
kW/kW
15.5
13.5
Temp. range of
cooling
Indoor
W.B.
59 to 75°F [15 to 24°C]
Outdoor
D.B.
23 to 115°F [−5 to 46°C]*3*4
Heating capacity
*2
(Nominal)
*2
*2
kW
12.3
15.8
kcal/h
10,600
13,600
Btu/h
42,000
54,000
Power input
W
3020
3880
Current input
A
14.7/13.3
18.9/17.1
COP
kW/kW
4.08
4.08
Temp. range of
heating
Indoor
D.B.
59 to 81°F [15 to 27°C]
Outdoor
W.B.
−13 to 59
°F [
−25 to 15
°C]
Indoor unit
connectable
Total capacity
50 to 130% of outdoor unit capacity
Model/
Quantity
CITY MULTI
P04-P36/11
P04-P54/12
Sound pressure level
(measured in anechoic room)
dB <A>
49/53
51/54
Refrigerant
piping diameter
Liquid pipe
in (mm)
3/8 (9.52)
Gas pipe
in (mm)
5/8 (15.88)
FAN
Type x Quantity
Propeller Fan × 2
Airflow rate
m3/min
110
L/s
1,834
cfm
3,885
Control, Driving mechanism
DC control
Motor output
kW
0.074 + 0.074
External static press.
0
Compressor
Type x Quantity
Scroll hermetic compressor × 1
Manufacture
Mitsubishi Electric Corporation
Starting method
Inverter
Motor output
kW
2.8
3.4
Case heater
kW
0
Lubricant
FV50S (2.3 liter)
External finish
Galvanized Steel Sheet
<MUNSELL 3Y 7.8/1.1>
External dimension H x W x D
mm
1,338 × 1,050 × 330 (+25)
in
52-11/16 × 41-11/32 × 13 (+1)
Protection devices High pressure protection
High pressure Switch, High pressure Sensor
Inverter circuit (COMP./FAN)
Overcurrent detection, Overheat detection (Heat sink thermistor)
Compressor
Compressor thermistor, Over current detection
Fan motor
Overheating, Voltage protection
Refrigerant
Type x original charge
R410A 4.8 kg
Control
Linear Expansion Valve
Net weight
kg (lb)
126 (278)
Heat exchanger
Cross Fin and Copper tube
HIC circuit (HIC: Heat Inter-Changer)
HIC circuit
Defrosting method
Reversed refrigerant circuit
Drawing
External
BK01V261
BH78B813
Wiring
Standard
attachment
Document
Installation Manual
Accessory
Grounded lead wire × 2, conduit plate
Optional parts
Joint: CMY-Y62-G-E
Header: CMY-Y64/68-G-E
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items
shall be referred to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
Notes:
*1. Nominal cooling conditions (subject to ISO 15042)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
*2. Nominal heating conditions (subject to ISO 15042)
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
*3. 50 to 115°F (10 to 46°C)D.B.: When connecting PKFY-P06NBMU, PKFY-P08NHMU,
PKFY-P04/06/08/12NLMU, PFFY-P06/08/12NEMU, and PFFY-P06/08/12NRMU type indoor unit.
*4. 5 to 115°F (-15 to 46°C)D.B.: When using an optional air protect guide (PAC-SH95AG-E).
However, this condition does not apply to the indoor units listed in *3.