63
OCH756
SW2 setting
Display detail
Explanation for display
Unit
The operation mode when the fourth-to-
last error occurred
This setting shows the operation mode when the
fourth-to-last error occurred as well as the default
setting (Please refer to the following).
Mode
The operating frequency when the
fourth-to-last error occurred
0 to 255
0 to 255
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
Hz
The compressor current when the
fourth-to-last error occurred
0 to 50
0 to 50
A
The primary current when the fourth-to-
last error occurred
0 to 500
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0.1 A
The DC bus voltage when the fourth-to-
last error occurred
100 to 1023
100 to 1023
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
V
The fan step when the fourth-to-last
error occurred
0 to 16
0 to 16
Step
The return water temperature (THW2)
when the fourth-to-last error occurred
0 to 60
0 to 60
°C
The indoor liquid pipe temperature
(TH2) when the fourth-to-last error
occurred
−39 to 88
−39 to 88
Indoor liquid pipe temperature (TH2)
Σ(TH2(N))/n
(When it is 0 or less, “–” and numbers are displayed
by turns.)
°C
The indoor pipe temperature/Cond./Eva.
(TH5) when the fourth-to-last error
occurred
−39 to 88
−39 to 88
Indoor pipe temperature/Cond./Eva. (TH5)
Σ(TH5(N))/n
(When it is 0 or less, “–” and numbers are displayed
by turns.)
°C
The discharge temperature (TH4) when
the fourth-to-last error occurred
−20 to 217
−20 to 217
(When it is 0 or less, “–” and numbers are displayed
by turns.)
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
°C
The outdoor liquid pipe temperature
(TH3) when the fourth-to-last error
occurred
−39 to 88
(When it is 0 or less, “–” and numbers are displayed
by turns.)
°C
The black square (
■
) indicates a switch position.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
(SW2)