44
OCH756
Outdoor power circuit board
PUD-SWM60VAAR1
PUD-SWM80VAAR1
PUD-SWM100VAAR1
PUD-SWM120VAAR1
PUD-SHWM60VAAR1
PUD-SHWM80VAAR1
PUD-SHWM100VAAR1
PUD-SHWM120VAAR1
CNAC1, CNAC2
230 VAC
Connect to the outdoor controller
circuit board (CNAC)
NI, LI
Voltage of 230 VAC is
input (Connect to the ter-
minal block (TB1))
EI, E4
Connect to the earth
(Check WIRING
DIAGRAM for E4)
E2, E3
Connect to the earth
(Check WIRING
DIAGRAM for E2)
CN4
Connect to the outdoor
controller circuit board (CN4)
CN2
Connect to the outdoor controller circuit board (CN2)
1
–
5
: Transmitting signal to outdoor controller circuit
board (0–5 VDC)
2
–
5
: Zero cross signal (0–5 VDC)
3
–
4
: 18 VDC
6
–
5
: 16 VDC
7
–
5
: 16 VDC
CNDC
280–380 VDC (
1
+,
3
−)
Connect to the outdoor
controller circuit board
(CNDC)
U/V/W
Connect to the compres-
sor (MC) Voltage among
phases: 10–180 VAC
N1
N
L
P1
N2
W2
V2
U2
P2
N3
W3
V3
U3
P3
Brief Check of DIP-IPM and DIODE MODULE
If they are short-circuited, it means that they are broken.
Measure the resistance in the following points (connectors, etc.).
1. Check of DIP-IPM
2. Check of DIODE MODULE
Note: The marks,
shown in the diagram are not actually printed on the board.
P2 - U2 , P2 - V2 , P2 - W2 , N2 - U2 , N2 - V2 , N2 - W2
P3 - U3 , P3 - V3 , P3 - W3 , N3 - U3 , N3 - V3 , N3 - W3
P1 - L , P1 - N , L - N1 , N - N1
L , N , N1 , N2 , N3 , P1 , P2 , P3 , U2 , U3 , V2 , V3 , W2 , and W3
CN6
Thermistor
<Heat sink>
(TH8)
IC600
DIP-IPM
IC500
DIP-IPM
TB1A, TB2A, TB3A,
Connect to DCL
TB1B, TB2B, TB3B
Connect to DCL
Содержание PUD-SHWM100VAA
Страница 15: ...15 OCH756 5 OUTLINES AND DIMENSIONS Unit mm ...
Страница 17: ...17 OCH756 PUD SHWM140VAAR1 ...