48
OCH756
9-7. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS
Function of switches
The black square (
■
) indicates a switch position.
Type of
Switch Switch No.
Function
Action by the switch operation
Effective timing
ON
OFF
DIP
switch
SW1
1
No function
—
—
—
2
Abnormal history clear
Clear
Normal
off or operating
3
Refrigerant address
setting
When power supply ON
4
5
6
SW4
1
No function
—
—
—
2
No function
—
—
—
SW8
1
Use of existing pipe
Used
Not used
Always
2
No function
—
—
—
3
Separate indoor/outdoor
unit power supplies
Used
Not used
When power supply ON
Push
switch
SWP
Pump down
Start
Normal
Under suspension
DIP
switch
SW5
1
No function
—
—
—
2
Power failure
automatic recovery*
1
Auto recovery
No auto recovery
When power supply ON
3,4
No function
—
—
—
5
Capacity operation
Passive mode
Active mode
When power supply ON
6
DHW operation
Quick mode
ECO mode
When power supply ON
SW7*
2
1
Mode select
*3
Demand function
Low noise mode
When power supply ON
2
Service check function
*4
Backup data
Normal
Always
3
No function
—
—
—
4,5
Max. current change
function
*5
V-type
SW7-4 SW7-5 Max. current
OFF
OFF
Default
ON
OFF
21.0 A
OFF
ON
15.2 A
ON
ON
13.0 A
When power supply ON
6
Defrost setting
For high humidity
Normal
Always
SW9
1
No function
—
—
—
2
No function
—
—
—
3,4
Starting Ambient temp.
of flash injection
(PUD-SHWM only)
SW9-3 SW9-4
Ambient temp.
OFF
OFF
≤ −6°C (Initial setting)
OFF
ON
≤ −3°C
ON
OFF
≤ 0°C
ON
ON
≤ 3°C
Always
DIP
switch
SW6
1
Model select
2
3
4
5
6
7
8
Switch
Type
of
switch
DIP
switch
Push
switch
SW1
1
2
No.
Function
Effective timing
Action by the switch operation
No function
Abnormal history clear
Refrigerant address
setting
When power supply ON
Clear
Normal
off or operating
SWP
6
5
4
3
Under suspension
Pump down
Start
Normal
SW4
SW8
1
2
1
2
3
No function
No function
Use of existing pipe
Used
Not used
No function
—
—
—
—
—
—
—
—
Separate indoor/outdoor
unit power supplies
Used
Not used
Always
—
When power supply ON
ON
OFF
1 2 3
0
1
2
3
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3
4
5
4 5 6
ON
1 2 3 4 5 6
ON
—
—
—
Y-type
SW7-4 SW7-5 Max. current
OFF
OFF
Default
ON
OFF
10.0 A
OFF
ON
9.5 A
ON
ON
8.5 A
*
1
“Power failure automatic recovery” can be set by either remote controller or this DIP SW. If one of them is set to ON, “Auto
recovery” activates. Please set “Auto recovery” basically by remote controller because all units do not have DIP SW.
Please refer to the indoor unit installation manual.
*
2
Please do not use SW7-2,4,5,6 usually. Trouble might be caused by the usage condition.
*
3
SW7-1 is setting change over of Demand. It is effective only in the case of external input. (Local wiring is necessary. Refer
to the next page: Special function.)
*
4
This function displays the backup data when errors occurred. (Last 4 data at the maximum)
*
5
This function cannot exceed the default current limit.
PUD-SWM60/80/100/120VAA
PUD-SHWM60/80/100/120/140VAA
PUD-SWM80/100/120YAA
PUD-SHWM80/100/120/140YAA
Содержание PUD-SHWM100VAA
Страница 15: ...15 OCH756 5 OUTLINES AND DIMENSIONS Unit mm ...
Страница 17: ...17 OCH756 PUD SHWM140VAAR1 ...