60
OCH756
SW2 setting
Display detail
Explanation for display
Unit
The fan step when the second-to-last
error occurred
0 to 16
0 to 16
Step
The return water temperature (THW2)
when the second-to-last error occurred
0 to 60
0 to 60
°C
The indoor liquid pipe temperature
(TH2) when the second-to-last error
occurred
(The average temperature when 2 or
more indoor units are connected)
−39 to 88
−39 to 88
Indoor liquid pipe temperature (TH2)
Σ(TH2(N))/n
(When it is 0 or less, “–” and numbers are displayed
by turns.)
°C
The indoor pipe temperature/Cond./Eva.
(TH5) when the second-to-last error
occurred
(The average temperature when 2 or
more indoor units are connected)
−39 to 88
−39 to 88
Indoor pipe temperature/Cond./Eva. (TH5)
Σ(TH5(N))/n
(When it is 0 or less, “–” and numbers are displayed
by turns.)
°C
The discharge temperature (TH4) when
the second-to-last error occurred
−20 to 217
−20 to 217
(When it is 0 or less, “–” and numbers are displayed
by turns.)
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
°C
The outdoor liquid pipe temperature
(TH3) when the second-to-last error
occurred
−39 to 88
−39 to 88
(When it is 0 or less, “–” and numbers are displayed
by turns.)
°C
The outdoor 2-phase pipe temperature
(TH6) when the second-to-last error
occurred
−39 to 88
−39 to 88
(When it is 0 or less, “–” and numbers are displayed
by turns.)
°C
The ambient temperature (TH7) when
the second-to-last error occurred
−39 to 88
−39 to 88
(When it is 0 or less, “–” and numbers are displayed
by turns.)
°C
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
The black square (
■
) indicates a switch position.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6