57
OCH756
SW2 setting
Display detail
Explanation for display
Unit
The fan step when the last error
occurred
0 to 16
0 to 16
Step
The LEV-C opening pulse
0 to 500
0 to 500
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
Example: When 130 pulse
0.5 s 0.5 s 2 s
Pulse
The return water temperature (THW2)
when the last error occurred
0 to 60
0 to 60
°C
The indoor pipe temperature/Liquid
(TH2) when the last error occurred
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Example: When –15°C 0.5 s 0.5 s 2 s
°C
The indoor pipe temperature/Cond./Eva.
(TH5) or outdoor condensing tempera-
ture (T63HS) when the last error
occurred
Condenser: T63HS
Evaporator: TH5
-39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Example: When –15°C 0.5 s 0.5 s 2 s
°C
The outdoor pipe temperature/Cond./
Eva.(TH6 or T63HS) when the last error
occurred
Condenser: T63HS
Evaporator: TH6
-39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Example: When –15°C
0.5 s 0.5 s 2 s
°C
The ambient temperature (TH7) when
the last error occurred
−39 to 88
−39 to 88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
Example: When −15°C
0.5 s 0.5 s 2 s
°C
The outdoor heat sink temperature
(TH8) when the last error occurred
−40 to 200
−40 to 200
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
°C
The discharge superheat when the last
error occurred
0 to 255
SHd = TH4 or TH33*−T
63HS
*
Chose higer one
0 to 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
Example: When 150°C
0.5 s 0.5 s 2 s
°C
The degree of subcooling (SC) when the
last error occurred
0 to 255
SC = T63HS
−TH2
0 to 255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
Example: When 115°C
0.5 s 0.5 s 2 s
°C
1
ON
2 3 4 5 6
The black square (
■
) indicates a switch position.
1
ON
2 3 4 5 6
30
1
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
15
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
15
50
1
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
1