1. SPECIFICATIONS
HEAT SOURCE
84
WR2
MEE15K036
I.WR2 SERIES
1. SPECIFICATIONS
Model
PQRY-P200YLM-A
Power source
3-phase 4-wire 380-400-415 V 50/60 Hz
Cooling capacity
*1 kW
22.4
(Nominal)
kcal/h
20,000
*1 BTU/h
76,400
Power input
kW
3.71
Current input
A
6.2-5.9-5.7
EER
kW/kW
6.03
Temp. range of
Indoor
W.B.
15.0~24.0°C (59~75°F)
cooling
Circulating water
°C
10.0~45.0°C (50~113°F)
Heating capacity
*2 kW
25.0
(Nominal)
kcal/h
21,500
*2 BTU/h
85,300
Power input
kW
3.97
Current input
A
6.7-6.3-6.1
COP
kW/kW
6.29
Temp. range of
Indoor
D.B.
15.0~27.0°C (59~81°F)
heating
Circulating water
°C
10.0~45.0°C (50~113°F)
Indoor unit
Total capacity
50~150% of heat source unit capacity
connectable
Model/Quantity
P15~P250/1~20
Sound pressure level (measured in anechoic room)
dB <A>
46
Sound power level (measured in anechoic room)
dB <A>
60
Refrigerant
High pressure
mm (in.)
15.88 (5/8) Brazed
piping diameter
Low pressure
mm (in.)
19.05 (3/4) Brazed
Circulating water
Water flow rate
m
3
/h
5.76
L/min
96
cfm
3.4
Pressure drop
kPa
24
Operating volume range
m
3
/h
3.0 ~ 7.2
Compressor
Type
Inverter scroll hermetic compressor
Manufacture
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Starting method
Inverter
Motor output
kW
4.8
Case heater
kW
-
Lubricant
MEL32
External finish
Galvanized steel sheets
External dimension H x W x D
mm
1,100 x 880 x 550
in.
43-5/16 x 34-11/16 x 21-11/16
Protection devices
High pressure protection
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Inverter circuit (COMP.)
Over-heat protection, Over-current protection
Compressor
Over-heat protection
Refrigerant
Type x original charge
R410A x 5.0 kg (12 lbs)
Control
Indoor LEV and BC controller
Net weight
kg (lbs)
172 (380)
Heat exchanger
plate type
Water volume in plate
I
5.0
Water pressure Max.
MPa
2.0
HIC circuit (HIC: Heat Inter-Changer)
-
Drawing
External
WKS94C743
Wiring
WKE94G131
Standard attachment
Document
Installation Manual
Accessory
Refrigerant conn. pipe
Optional parts
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1
BC controller: CMB-P104, 105, 106, 108, 1010, 1013, 1016V-G1
Main BC controller: CMB-P108, 1010, 1013, 1016V-GA1
Sub BC controller: CMB-P104, 108V-GB1, CMB-P1016V-HB1
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the heat source unit needs to be kept below 40°C D.B.
The ambient relative humidity of the heat source unit needs to be kept below 80%.
The heat source unit should not be installed at outdoor.
Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
Notes:
Unit converter
1.Nominal cooling conditions (subject to JIS B8615-2)
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Water temperature: 30°C (86°F)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.Nominal heating conditions (subject to JIS B8615-2)
Indoor: 20°CD.B. (68°FD.B.) ,Water temperature: 20°C (68°FD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
BTU/h
=kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.